Line 12: Line 12:
| identified by = NRC
| identified by = NRC
| Inspection procedure = IP 93800
| Inspection procedure = IP 93800
| Inspector = G Replogle, J Dixon, J Watkins, M Baquera, M Runyan, N O, 'Keefen Okonkwoj,  Dixonj Robles, J Watkins, M Haire, M Runyan, N O, 'Keefeb Correll, G Matharu
| Inspector = G Replogle, J Dixon, J Watkins, M Baquera, M Runyan, N O'Keefe, N Okonkwoj,  Dixonj Robles, J Watkins, M Haire, M Runyan, N O'Keefe, B Correll, G Matharu
| CCA = N/A for ROP
| CCA = N/A for ROP
| INPO aspect =  
| INPO aspect =  
| description = The team determined that the out-of-specification tappet nut to head lever engagement of the turbine-driven AFW pump mechanical overspeed trip mechanism warranted additional NRC review and follow-up considering that this maintenance deficiency led directly to the spurious overspeed trip following the LOOP event and additionally might have affected the reliability of the turbine during a seismic event. Additional review by the NRC will be needed to determine whether this issue represents a performance deficiency. The issue will be identified as URI 05000482/2012008-03, Review Turbine- Driven Auxiliary Feedwater Pump Mechanical Overspeed Trip Device Out of Specification.
| description = The team determined that the out-of-specification tappet nut to head lever engagement of the turbine-driven AFW pump mechanical overspeed trip mechanism warranted additional NRC review and follow-up considering that this maintenance deficiency led directly to the spurious overspeed trip following the LOOP event and additionally might have affected the reliability of the turbine during a seismic event. Additional review by the NRC will be needed to determine whether this issue represents a performance deficiency. The issue will be identified as URI 05000482/2012008-03, Review Turbine- Driven Auxiliary Feedwater Pump Mechanical Overspeed Trip Device Out of Specification.
}}
}}

Latest revision as of 00:19, 22 February 2018

03
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Report IR 05000482/2012008 Section 4OA5
Date counted Mar 31, 2012 (2012Q1)
Type: URI:
cornerstone Mitigating Systems
Identified by: NRC identified
Inspection Procedure: IP 93800
Inspectors (proximate) G Replogle
J Dixon
J Watkins
M Baquera
M Runyan
N O'Keefe
N Okonkwoj
Dixonj Robles
J Watkins
M Haire
M Runyan
N O'Keefe
B Correll
G Matharu
INPO aspect
'