ML071100366: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
 
Line 19: Line 19:


=Text=
=Text=
{{#Wiki_filter:SLs 2.0 2.0 SAFETY LIMITS (SLs)2.1 SLs 2.1.1 Reactor Core SLs 2.1.1.1 With the reactor steam dome pressure < 785 psig or core flow < 10% rated core flow: THERMAL POWER shall be 25% RTP.2.1.1.2 With the reactor steam dome pressure 785 psig and core flow 10% rated core flow: For Unit 1, MCPR shall be 1.11 for two recirculation loop operation or 1.13 for single recirculation loop operation.
{{#Wiki_filter:SLs 2.0 2.0 SAFETY LIMITS (SLs) 2.1 SLs 2.1.1 Reactor Core SLs 2.1.1.1 With the reactor steam dome pressure < 785 psig or core flow < 10% rated core flow:
For Unit 2, MCPR for GNF fuel shall be > 1.09 for two recirculation loop operation, or > 1.10 for single recirculation loop operation.
THERMAL POWER shall     be
MCPR for Westinghouse fuel shall be > 1.11 for two recirculation loop operation, or > 1.13 for single recirculation loop operation.
* 25% RTP.
2.1.1.3 Reactor vessel water level shall be greater than the top of active irradiated fuel.2.1.2 Reactor Coolant System Pressure SL Reactor steam dome pressure shall be 1345 psig.2.2 SL Violations With any SL violation, the following actions shall be completed within 2 hours: 2.2.1 Restore compliance with all SLs; and 2.2.2 Insert all insertable control rods.Quad Cities 1 and 2 2.0-1 Amendment No. /226 234}}
2.1.1.2 With the reactor steam dome pressure &#x17d; 785 psig and core flow &#x17d; 10% rated core flow:
For Unit 1, MCPR shall be &#x17d; 1.11 for two recirculation loop operation or &#x17d; 1.13 for single recirculation loop operation.
For Unit 2, MCPR for GNF fuel shall be > 1.09 for two recirculation loop operation, or > 1.10 for single recirculation loop operation.     MCPR for Westinghouse fuel shall be > 1.11 for two recirculation loop operation, or > 1.13 for single recirculation loop operation.
2.1.1.3 Reactor vessel water level     shall be greater than the top of active irradiated fuel.
2.1.2 Reactor Coolant System Pressure SL Reactor steam dome pressure shall be
* 1345 psig.
2.2 SL Violations With any SL violation,   the following actions shall be completed within 2 hours:
2.2.1 Restore compliance with all SLs; and 2.2.2 Insert all   insertable control   rods.
Quad Cities 1 and 2                     2.0-1                     Amendment No. /226 234}}

Latest revision as of 08:11, 23 November 2019

Technical Specifications, Issuance of Amendment Request for Technical Specifications Change for Minimum Critical Power Ratio Safety Limit
ML071100366
Person / Time
Site: Quad Cities Constellation icon.png
Issue date: 05/02/2007
From:
NRC/NRR/ADRO
To:
Williams J, NRR/DORL/LPL3-2, 415-1470
Shared Package
ML071100359 List:
References
TAC MD4008
Download: ML071100366 (1)


Text

SLs 2.0 2.0 SAFETY LIMITS (SLs) 2.1 SLs 2.1.1 Reactor Core SLs 2.1.1.1 With the reactor steam dome pressure < 785 psig or core flow < 10% rated core flow:

THERMAL POWER shall be

2.1.1.2 With the reactor steam dome pressure Ž 785 psig and core flow Ž 10% rated core flow:

For Unit 1, MCPR shall be Ž 1.11 for two recirculation loop operation or Ž 1.13 for single recirculation loop operation.

For Unit 2, MCPR for GNF fuel shall be > 1.09 for two recirculation loop operation, or > 1.10 for single recirculation loop operation. MCPR for Westinghouse fuel shall be > 1.11 for two recirculation loop operation, or > 1.13 for single recirculation loop operation.

2.1.1.3 Reactor vessel water level shall be greater than the top of active irradiated fuel.

2.1.2 Reactor Coolant System Pressure SL Reactor steam dome pressure shall be

  • 1345 psig.

2.2 SL Violations With any SL violation, the following actions shall be completed within 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s:

2.2.1 Restore compliance with all SLs; and 2.2.2 Insert all insertable control rods.

Quad Cities 1 and 2 2.0-1 Amendment No. /226 234