{{#Wiki_filter:Tennessee Valley Authority, Post Office Box 2000, Decatur, Aiabama 35609-2000 May18, 2010 10 CFR 2.201 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2 and 3 Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296 | {{#Wiki_filter:Tennessee Valley Authority, Post Office Box 2000, Decatur, Aiabama 35609-2000 May18, 2010 10 CFR 2.201 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2 and 3 Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296 | ||
==Subject:== | ==Subject:== | ||
Reply to Notice of Violation; EA-09-307 | Reply to Notice of Violation; EA-09-307 | ||
==Reference:== | ==Reference:== | ||
Letter from NRC to TVA, "Final Significance Determination of Yellow and White Findings and Notice of Violation (NRC Inspection Report Nos. | |||
05000259/2010007, 05000260/2010007 and 05000296/2010007), Browns Ferry Nuclear Plant," dated April 19, 2010 In response to the referenced letter, enclosed please find our reply to the notice of violation. | |||
There is one regulatory commitment contained in this letter as identified in Enclosure 2. | |||
Should you have any questions concerning this submittal, please contact Stan Day at (256) 729-2636. | |||
Respectfully, K. J. Poison Vice President | |||
==Enclosures:== | |||
: 1. NRC Inspection Report Nos. 05000259/2010007, 05000260/2010007, 05000296/2010007 Reply to Notice of Violation | |||
: 2. Regulatory Commitment cc (See page 2): | |||
U.S. Nuclear Regulatory Commission Page 2 May 18, 2010 cc (Enclosures): | U.S. Nuclear Regulatory Commission Page 2 May 18, 2010 cc (Enclosures): | ||
NRC Regional Administrator | NRC Regional Administrator -,Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant | ||
-,Region II NRC Senior Resident Inspector | |||
-Browns Ferry Nuclear Plant ENCLOSURE 1 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 NRC INSPECTION REPORT NOS. 0500025912010007, 05000260/2010007, 05000296/2010007 REPLY TO NOTICE OF VIOLATION Restatement of Violation 1 Title 10 of the Code of Federal Regulations (10 CFR), Part 50.48(b)(1) requires that all nuclear power plants licensed to operate prior to January 1, 1979, must satisfy the applicable requirements of 10 CFR Part 50, Appendix R, Sections Ill.G, Ill.J, and 111.0.Section IIL.G requires fire protection of safe shutdown capability. | ENCLOSURE 1 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 NRC INSPECTION REPORT NOS. 0500025912010007, 05000260/2010007, 05000296/2010007 REPLY TO NOTICE OF VIOLATION | ||
Section III.G.1 requires fire protection features shall be provided for structures, systems, and components important to safe shutdown. | |||
These features shall be capable of limiting fire damage, such that one train of systems necessary for achieving and maintaining hot shutdown conditions is free of fire damage.Section II.G.2 requires, in part, that where cables and equipment of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area outside of primary containment, one of the following means of ensuring that one of the redundant trains is free of fire damage shall be provided: a. separation of cables and equipment by a fire barrier having a 3-hour rating; or b. separation of cables and equipment by a horizontal distance of more than 20 feet with no intervening combustibles or fire hazards. Fire detection and automatic fire suppression shall be installed in the fire area; or c. enclosure of cables and equipment of one redundant train in a fire barrier having a 1-hour fire rating. Fire detection and automatic suppression shall be installed in the fire area.Contrary to the above, since the restart of each unit (Unit 2-1991, Unit 3-1995, Unit 1-2007) and as of January 20, 2010, the date of the inspection report, the licensee had not met nor has met, as of the date of this NOV, the requirements of 10 CFR Part 50, Appendix R, Section Ill.G, in that: (i) fire protection features capable of limiting fire damage were not provided for structures, systems, and components important for safe shutdown. | Restatement of Violation 1 Title 10 of the Code of Federal Regulations (10 CFR), Part 50.48(b)(1) requires that all nuclear power plants licensed to operate prior to January 1, 1979, must satisfy the applicable requirements of 10 CFR Part 50, Appendix R, Sections Ill.G, Ill.J, and 111.0. | ||
Specifically, the Tennessee Valley Authority (licensee) failed to provide fire protection features capable of limiting the fire damage such that one train of systems necessary to achieve and maintain hot shutdown conditions was free from fire damage in Fire Area 8 along with 19 other fire areas designated in the Browns Ferry Fire Protection Report, as required by 10 CFR Part 50, Appendix R, Section III.G.1.(ii) where cables and equipment of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area, the licensee did not ensure that one of the redundant trains was free of fire damage by providing one of the following means: (a) a 3-hour rated fire barrier; (b) 20 feet of spatial separation (free of intervening combustibles and fire hazards) with detection and suppression installed in the fire area; or (c) a 1-hour rated fire barrier with detection and suppression installed in the fire area. Specifically, cables associated with the RHRSW Pump Al, RHR Pump 1A, and LPCI injection valve 1-FCV-74-53 in Fire Area 1/Fire Zone 1-4 are some of the many examples in which the licensee failed to ensure that one train of cables of redundant systems or equipment necessary to achieve and maintain hot shutdown conditions, located in the same fire area, outside of primary containment was free of fire damage by one of the means described in 10 CFR Part 50, Appendix R, Section III.G.2.This violation of 10 CFR Part 50, Appendix R, Section 11I.G is associated with a Yellow significance determination process finding for Units 1, 2, and 3 in the Mitigating Systems cornerstone. | Section IIL.G requires fire protection of safe shutdown capability. | ||
E-1 Reply to Violation 1 The reason for the violation, or, if contested, the basis for disputing the violation or severity level, The root cause for this violation is a combination of: 1. An entrenched 10 CFR 50, Appendix R compliance position, 2. A lack of rigorous review and resolution of regulatory documents, and 3. Passive management of the Browns Ferry Nuclear Plant (BFN) Appendix R Program and failure to aggressively implement identified actions.The initial implementation of the Appendix R Fire Protection Program requirements at BFN in the 1980s included extensive use of Operator Manual Actions (OMAs). The Tennessee Valley Authority (TVA) failed to re-evaluate Appendix R compliance as NRC requirements evolved and were clarified over a period of years.When the NRC SE for the BFN Appendix R safe shutdown system analysis was issued on December 8, 1988, licensees were not required to formally apply for OMA exemptions. | Section III.G.1 requires fire protection features shall be provided for structures, systems, and components important to safe shutdown. These features shall be capable of limiting fire damage, such that one train of systems necessary for achieving and maintaining hot shutdown conditions is free of fire damage. | ||
At that time, the NRC approved OMAs through a variety of means. The 1988 SE approved the OMAs covered by the SE. Several subsequent SEs issued from 1989 through BFN, Unit 1, restart in 2007 also addressed OMAs without explicitly approving exemptions. | Section II.G.2 requires, in part, that where cables and equipment of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area outside of primary containment, one of the following means of ensuring that one of the redundant trains is free of fire damage shall be provided: | ||
In 2000, the NRC implemented the Reactor Oversight Process that included inspection of safe shutdown capability. | : a. separation of cables and equipment by a fire barrier having a 3-hour rating; or | ||
Training materials provided to NRC inspectors in 2001 stated that the NRC did not consider OMAs to be approved unless they were formally exempted in accordance with 10 CFR 50.12, even if they had been previously addressed by NRC-issued SERs. The Nuclear Energy Institute (NEI) took issue with that position, and responded, in early 2002, with a basis for the acceptability of using OMAs to meet Appendix R requirements. | : b. separation of cables and equipment by a horizontal distance of more than 20 feet with no intervening combustibles or fire hazards. Fire detection and automatic fire suppression shall be installed in the fire area; or | ||
The NEI position reinforced the mindset that OMAs, as used at BFN, were an acceptable Appendix R strategy.After dialog with the industry, the NRC published a draft rulemaking in 2005 to define requirements for using OMAs to comply with requirements of Appendix R, paragraph III.G.2.The proposed rulemaking was withdrawn on March 6, 2006. The NRC reiterated in the same March 6, 2006, Federal Register notice that OMAs cannot be relied upon in lieu of compliance with Appendix R, III.G.2 requirements. | : c. enclosure of cables and equipment of one redundant train in a fire barrier having a 1-hour fire rating. Fire detection and automatic suppression shall be installed in the fire area. | ||
In the same year as the draft rulemaking, the NRC issued Regulatory Issue Summary RIS 2005-30, "Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements," dated December 20, 2005. This RIS clarified: | Contrary to the above, since the restart of each unit (Unit 2-1991, Unit 3-1995, Unit 1-2007) and as of January 20, 2010, the date of the inspection report, the licensee had not met nor has met, as of the date of this NOV, the requirements of 10 CFR Part 50, Appendix R, Section Ill.G, in that: | ||
* Requirements to analyze post-fire spurious actuations that could impact safe shutdown,* Use of operator manual actions with respect to protection of associated circuits, and* Use of emergency control stations in accordance with Appendix R, Section llI.G.l.a. | (i) fire protection features capable of limiting fire damage were not provided for structures, systems, and components important for safe shutdown. Specifically, the Tennessee Valley Authority (licensee) failed to provide fire protection features capable of limiting the fire damage such that one train of systems necessary to achieve and maintain hot shutdown conditions was free from fire damage in Fire Area 8 along with 19 other fire areas designated in the Browns Ferry Fire Protection Report, as required by 10 CFR Part 50, Appendix R, Section III.G.1. | ||
BFN missed the opportunity to identify that site use of emergency control stations differed significantly from NRC guidance contained in the RIS. This issue ultimately led to BFN's misclassification of III.G.1 areas.TVA met with the NRC in a public meeting on April 5, 2006, to discuss Appendix R requirements for Unit 1 restart. The NRC stated that:* TVAmust be in compliance with Appendix R," All OMAs determined to be risk-significant must be corrected, and* Non-risk-significant OMAs would be given enforcement discretion for three years starting March 6, 2006.E-2 TVA initiated a Corrective Action Program (CAP) Problem Evaluation Report (PER) to address the issues identified in the meeting and referred to guidance associated with manual actions stated in the March 6, 2006 Federal Register notice. This PER was subsequently revised to expand the scope to include the need for OMA exemption requests or plant modifications to reduce OMAs for all three units. PER actions were deferred multiple times, until an exemption request was submitted to the NRC by letter dated January 27, 2009, 37 days before the end of the enforcement discretion period.TVA took no action between 2006 and 2009 to comply with Appendix R requirements by modifying the plant based on the assumption that TVA would be automatically granted OMA exemptions upon request.The following contributing causes have also been identified for this violation: | (ii) where cables and equipment of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area, the licensee did not ensure that one of the redundant trains was free of fire damage by providing one of the following means: (a) a 3-hour rated fire barrier; (b) 20 feet of spatial separation (free of intervening combustibles and fire hazards) with detection and suppression installed in the fire area; or (c) a 1-hour rated fire barrier with detection and suppression installed in the fire area. Specifically, cables associated with the RHRSW Pump Al, RHR Pump 1A, and LPCI injection valve 1-FCV-74-53 in Fire Area 1/Fire Zone 1-4 are some of the many examples in which the licensee failed to ensure that one train of cables of redundant systems or equipment necessary to achieve and maintain hot shutdown conditions, located in the same fire area, outside of primary containment was free of fire damage by one of the means described in 10 CFR Part 50, Appendix R, Section III.G.2. | ||
: 1. Lack of process infrastructure to accommodate organizational change led to the licensing and fire protection organizations' failure to keep up with changing regulatory climate, 2. Lack of effective turnover from the BFN, Unit 1, restart team to other BFN personnel, 3. An absence of effective corporate governance and oversight of the areas of Licensing and-Fire Protection, and 4. Ineffective use of CAP to identify Appendix R issues and drive them to resolution. | This violation of 10 CFR Part 50, Appendix R, Section 11I.G is associated with a Yellow significance determination process finding for Units 1, 2, and 3 in the Mitigating Systems cornerstone. | ||
NRC interpretation and enforcement of Appendix R requirements evolved substantially between 2005 and the NRC Triennial Fire Protection/Appendix R Inspection of BFN in the fall of 2009.Numerous BFN organizational changes took place in key positions (licensing, engineering, site and corporate management) between 2005 and the investigation of the root cause of this event.The timing of many of these changes exacerbated the situation. | E-1 | ||
Reply to Violation 1 The reason for the violation, or, if contested, the basis for disputing the violation or severity level, The root cause for this violation is a combination of: | |||
: 1. An entrenched 10 CFR 50, Appendix R compliance position, | |||
: 2. A lack of rigorous review and resolution of regulatory documents, and | |||
: 3. Passive management of the Browns Ferry Nuclear Plant (BFN) Appendix R Program and failure to aggressively implement identified actions. | |||
The initial implementation of the Appendix R Fire Protection Program requirements at BFN in the 1980s included extensive use of Operator Manual Actions (OMAs). The Tennessee Valley Authority (TVA) failed to re-evaluate Appendix R compliance as NRC requirements evolved and were clarified over a period of years. | |||
When the NRC SE for the BFN Appendix R safe shutdown system analysis was issued on December 8, 1988, licensees were not required to formally apply for OMA exemptions. At that time, the NRC approved OMAs through a variety of means. The 1988 SE approved the OMAs covered by the SE. Several subsequent SEs issued from 1989 through BFN, Unit 1, restart in 2007 also addressed OMAs without explicitly approving exemptions. | |||
In 2000, the NRC implemented the Reactor Oversight Process that included inspection of safe shutdown capability. Training materials provided to NRC inspectors in 2001 stated that the NRC did not consider OMAs to be approved unless they were formally exempted in accordance with 10 CFR 50.12, even if they had been previously addressed by NRC-issued SERs. The Nuclear Energy Institute (NEI) took issue with that position, and responded, in early 2002, with a basis for the acceptability of using OMAs to meet Appendix R requirements. The NEI position reinforced the mindset that OMAs, as used at BFN, were an acceptable Appendix R strategy. | |||
After dialog with the industry, the NRC published a draft rulemaking in 2005 to define requirements for using OMAs to comply with requirements of Appendix R, paragraph III.G.2. | |||
The proposed rulemaking was withdrawn on March 6, 2006. The NRC reiterated in the same March 6, 2006, Federal Register notice that OMAs cannot be relied upon in lieu of compliance with Appendix R, III.G.2 requirements. In the same year as the draft rulemaking, the NRC issued Regulatory Issue Summary RIS 2005-30, "Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements," dated December 20, 2005. This RIS clarified: | |||
* Requirements to analyze post-fire spurious actuations that could impact safe shutdown, | |||
* Use of operator manual actions with respect to protection of associated circuits, and | |||
* Use of emergency control stations in accordance with Appendix R, Section llI.G.l.a. | |||
BFN missed the opportunity to identify that site use of emergency control stations differed significantly from NRC guidance contained in the RIS. This issue ultimately led to BFN's misclassification of III.G.1 areas. | |||
TVA met with the NRC in a public meeting on April 5, 2006, to discuss Appendix R requirements for Unit 1 restart. The NRC stated that: | |||
* TVAmust be in compliance with Appendix R, | |||
" All OMAs determined to be risk-significant must be corrected, and | |||
* Non-risk-significant OMAs would be given enforcement discretion for three years starting March 6, 2006. | |||
E-2 | |||
TVA initiated a Corrective Action Program (CAP) Problem Evaluation Report (PER) to address the issues identified in the meeting and referred to guidance associated with manual actions stated in the March 6, 2006 Federal Register notice. This PER was subsequently revised to expand the scope to include the need for OMA exemption requests or plant modifications to reduce OMAs for all three units. PER actions were deferred multiple times, until an exemption request was submitted to the NRC by letter dated January 27, 2009, 37 days before the end of the enforcement discretion period. | |||
TVA took no action between 2006 and 2009 to comply with Appendix R requirements by modifying the plant based on the assumption that TVA would be automatically granted OMA exemptions upon request. | |||
The following contributing causes have also been identified for this violation: | |||
: 1. Lack of process infrastructure to accommodate organizational change led to the licensing and fire protection organizations' failure to keep up with changing regulatory climate, | |||
: 2. Lack of effective turnover from the BFN, Unit 1, restart team to other BFN personnel, | |||
: 3. An absence of effective corporate governance and oversight of the areas of Licensing and-Fire Protection, and | |||
: 4. Ineffective use of CAP to identify Appendix R issues and drive them to resolution. | |||
NRC interpretation and enforcement of Appendix R requirements evolved substantially between 2005 and the NRC Triennial Fire Protection/Appendix R Inspection of BFN in the fall of 2009. | |||
Numerous BFN organizational changes took place in key positions (licensing, engineering, site and corporate management) between 2005 and the investigation of the root cause of this event. | |||
The timing of many of these changes exacerbated the situation. | |||
The infrastructure (procedures, processes, and communications) to ensure that supervisors, managers, and executives were equipped with the necessary knowledge and information was not adequate for site and corporate leadership to stay current with Appendix R requirements. | The infrastructure (procedures, processes, and communications) to ensure that supervisors, managers, and executives were equipped with the necessary knowledge and information was not adequate for site and corporate leadership to stay current with Appendix R requirements. | ||
One of the deficiencies was the lack of effective corporate governance and oversight to 1) verify that TVA was cognizant of evolving Appendix R requirements and interpretations, and 2)provide appropriate advice to BFN and corporate decision-makers in an effective manner.Between March and May 2007, the BFN, Unit 1, restart licensing staff was disbanded and left BFN. No formal mechanisms were in place to ensure that open fire protection issues from Unit 1 restart were turned over to other BFN personnel and subsequently tracked to completion. | One of the deficiencies was the lack of effective corporate governance and oversight to 1) verify that TVA was cognizant of evolving Appendix R requirements and interpretations, and 2) provide appropriate advice to BFN and corporate decision-makers in an effective manner. | ||
Prior to 2008, TVA nuclear plants operated as nearly autonomous entities, with the corporate office providing support and advice as requested. | Between March and May 2007, the BFN, Unit 1, restart licensing staff was disbanded and left BFN. No formal mechanisms were in place to ensure that open fire protection issues from Unit 1 restart were turned over to other BFN personnel and subsequently tracked to completion. | ||
The relationship between the NRC and the sites was managed at the sites, as were individual projects like Appendix R. At the same time, the corporate Fire Protection/Appendix R Manager managed the interface with the industry, participated in NEI workshops and task forces, and monitored the evolution of Appendix R requirements. | Prior to 2008, TVA nuclear plants operated as nearly autonomous entities, with the corporate office providing support and advice as requested. The relationship between the NRC and the sites was managed at the sites, as were individual projects like Appendix R. At the same time, the corporate Fire Protection/Appendix R Manager managed the interface with the industry, participated in NEI workshops and task forces, and monitored the evolution of Appendix R requirements. | ||
Personnel from BFN did not participate in industry Appendix R activities and depended upon corporate input to remain current with the nuclear industry. | Personnel from BFN did not participate in industry Appendix R activities and depended upon corporate input to remain current with the nuclear industry. The BFN and corporate fire protection/Appendix R organizations were ineffective in developing and implementing a clear plan to achieve compliance with Appendix R requirements. There was disagreement over the different alternatives between early 2006 and early 2008. During this time (pre-2008), | ||
The BFN and corporate fire protection/Appendix R organizations were ineffective in developing and implementing a clear plan to achieve compliance with Appendix R requirements. | communications between BFN personnel and corporate personnel were ineffective in resolving these differences and no one was accountable to ensure a timely resolution of the issue. | ||
There was disagreement over the different alternatives between early 2006 and early 2008. During this time (pre-2008), communications between BFN personnel and corporate personnel were ineffective in resolving these differences and no one was accountable to ensure a timely resolution of the issue.E-3 TVA missed several opportunities to formally identify, document, analyze, and resolve issues associated with Appendix R. In 2005, the NRC published draft rulemaking to provide a method to request exemptions to Appendix R for using OMAs in lieu of meeting Appendix R requirements. | E-3 | ||
Also in 2005, the NRC issued RIS 2005-30, "Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements." TVA did not identify possible impacts for BFN from this RIS or initiate and track actions to ensure compliance. | |||
TVA missed several opportunities to formally identify, document, analyze, and resolve issues associated with Appendix R. In 2005, the NRC published draft rulemaking to provide a method to request exemptions to Appendix R for using OMAs in lieu of meeting Appendix R requirements. Also in 2005, the NRC issued RIS 2005-30, "Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements." TVA did not identify possible impacts for BFN from this RIS or initiate and track actions to ensure compliance. | |||
In June, 2006, the NRC issued RIS 2006-10, "Regulatory Expectations WithAppendix R Paragraph III.G.2 Operator Manual Actions," dated June 30, 2006. TVA failed to conduct a detailed review of each paragraph of the RIS and to thoroughly consider the actions needed to fully comply with that interpretation of Appendix R requirements. | In June, 2006, the NRC issued RIS 2006-10, "Regulatory Expectations WithAppendix R Paragraph III.G.2 Operator Manual Actions," dated June 30, 2006. TVA failed to conduct a detailed review of each paragraph of the RIS and to thoroughly consider the actions needed to fully comply with that interpretation of Appendix R requirements. | ||
The NRC presented TVA with another opportunity when it issued a Safety Evaluation (SE) for the restart of BFN, Unit 1 on April 25, 2007. In this SE, the NRC advised TVA of NRC positions regarding Appendix R, paragraphs III.G.1 and III.G.2. TVA failed to formally review this SE, or to document the commitments in the SE in the TVA CAP. Site licensing personnel later formally reviewed this SE in March/April 2009. This review was deficient. | The NRC presented TVA with another opportunity when it issued a Safety Evaluation (SE) for the restart of BFN, Unit 1 on April 25, 2007. In this SE, the NRC advised TVA of NRC positions regarding Appendix R, paragraphs III.G.1 and III.G.2. TVA failed to formally review this SE, or to document the commitments in the SE in the TVA CAP. Site licensing personnel later formally reviewed this SE in March/April 2009. This review was deficient. Contemporaneously with receipt of the SE, TVA Nuclear Assurance conducted a fire protection audit at BFN, and recommended that BFN revisit the definition of III.G.1 versus III.G.2 fire areas. No evidence was found that BFN reacted to this recommendation. | ||
Contemporaneously with receipt of the SE, TVA Nuclear Assurance conducted a fire protection audit at BFN, and recommended that BFN revisit the definition of III.G.1 versus III.G.2 fire areas. No evidence was found that BFN reacted to this recommendation. | |||
The corrective steps that have been taken and the results achieved, WVA implemented the following immediate actions in response to this violation: | The corrective steps that have been taken and the results achieved, WVA implemented the following immediate actions in response to this violation: | ||
: 1. Established compensatory fire watches on all three units to mitigate the possibility of an"Appendix R" fire developing from a smaller fire.2. Evaluated the most critical operator manual actions and revised selected safe shutdown instructions to include the requirements for independent confirmation of operator manual actions in order to improve the likelihood of the success of these actions.Additional corrective actions taken include the following: | : 1. Established compensatory fire watches on all three units to mitigate the possibility of an "Appendix R" fire developing from a smaller fire. | ||
: 1. Establishing corporate governance and oversight of BFN Licensing Activities. | : 2. Evaluated the most critical operator manual actions and revised selected safe shutdown instructions to include the requirements for independent confirmation of operator manual actions in order to improve the likelihood of the success of these actions. | ||
This action included the following. | Additional corrective actions taken include the following: | ||
: 1. Establishing corporate governance and oversight of BFN Licensing Activities. This action included the following. | |||
: a. Established and filled the position of a Corporate Vice President of Nuclear Licensing with governance authority and oversight over site licensing activities. | : a. Established and filled the position of a Corporate Vice President of Nuclear Licensing with governance authority and oversight over site licensing activities. | ||
: b. Established and filled the position of a Corporate Licensing Manager for BFN.c. Established corporate licensing review and approval of site licensing submittals. | : b. Established and filled the position of a Corporate Licensing Manager for BFN. | ||
: c. Established corporate licensing review and approval of site licensing submittals. | |||
: d. Assigned authority to approve NRC submittals to the Site Vice President or Corporate Vice President of Nuclear Licensing. | : d. Assigned authority to approve NRC submittals to the Site Vice President or Corporate Vice President of Nuclear Licensing. | ||
: e. Established daily fleet licensing telephone calls to report regulatory issues and challenge responses. | : e. Established daily fleet licensing telephone calls to report regulatory issues and challenge responses. | ||
: f. Revised a business practice to strengthen the guidance for effective governance and oversight by corporate functional area managers.2. Re-established formal review of incoming regulatory correspondence including independent review and tracking.3. Established and filled position for Corporate Fire Protection Program Manager with authority and oversight over site Fire Protection Programs.E-4 Improvements to the CAP initiated in response to two previous PERs (Nos. 131878 and 136489) addressed the CAP weaknesses observed for this violation. | : f. Revised a business practice to strengthen the guidance for effective governance and oversight by corporate functional area managers. | ||
Additionally a root cause analysis and development of the corrective action plan for PER 223536 has been initiated and is ongoing to address the recently NRC identified substantive crosscutting theme in the area of Problem Identification and Resolution. | : 2. Re-established formal review of incoming regulatory correspondence including independent review and tracking. | ||
Interim guidance to require fire protection program changes go through additional challenge prior to approval and require time line analyses of changes to Safe Shutdown Instruction (SSI)entry conditions and OMAs was issued.At this time, TVA considers it too early to assess the results achieved since these corrective actions have only recently been implemented. | : 3. Established and filled position for Corporate Fire Protection Program Manager with authority and oversight over site Fire Protection Programs. | ||
TVA will conduct an effectiveness review of these corrective actions.The corrective steps that will be taken.The following corrective actions are planned: Prepare and conduct a case study-based seminar covering the lessons learned from this event to operations senior reactor operators, engineers, licensing, fire protection, affected corporate licensing and corporate fire protection personnel, Plant Operations Review Committee and Corrective Action Review Board members, and senior site management. | E-4 | ||
Reinforce the need for rigorous compliance with the Appendix R Fire Protection Program and its significance with respect to achieving safe shutdown.Transition to the National Fire Protection Association (NFPA) 805 as the basis for compliance with Appendix R and include appropriate documentation of the licensing basis of the BFN NFPA-805 program in appropriate licensing basis documents. | |||
Establish review process criteria, identify, and re-review significant incoming regulatory correspondence (e.g., License Amendment SEs, Inspection Reports, and Regulatory Issue Summaries) received between January 2005 and December 2008 against those criteria and enter implementation deficiencies in the Corrective Action Program.The date when full compliance will be achieved.Full compliance for this violation will be achieved upon completing the implementation of the transition to the NFPA 805 basis for compliance with fire protection regulations. | Improvements to the CAP initiated in response to two previous PERs (Nos. 131878 and 136489) addressed the CAP weaknesses observed for this violation. Additionally a root cause analysis and development of the corrective action plan for PER 223536 has been initiated and is ongoing to address the recently NRC identified substantive crosscutting theme in the area of Problem Identification and Resolution. | ||
Full implementation of NFPA 805 compliance approach will not be completed until at least 2014.In the interim, TVA plans to initiate fire protection program improvements prior to completion of the transition to NFPA 805. Current program improvements that are planned include: analysis updates, actions to inhibit Common Accident Signal (CAS) logic, revised actions to bypass diesel generator logic in certain fire areas, improved component selection, ensuring the condensate storage tank suction path is available to high pressure makeup systems (High Pressure Coolant Injection/Reactor Core Isolation Cooling) in all fire areas where high pressure makeup is credited, and reducing the number of time critical and long term OMAs in the 39 fire areas. These improvements include implementation of interim revisions to the safe shutdown procedures resulting from the analysis updates. TVA plans to continue fire protection program improvements during the transition to NPFA 805 with implementation of identified program.changes, where allowed, under the transition requirements with the focus on risk reduction and elimination of OMAs. TVA plans to prioritize these improvements based on those with greater impact on overall fire risk reduction. | Interim guidance to require fire protection program changes go through additional challenge prior to approval and require time line analyses of changes to Safe Shutdown Instruction (SSI) entry conditions and OMAs was issued. | ||
E-5 Restatement of Violation 2 Technical Specification 5.4.1 .a requires that written procedures be established, implemented, and maintained covering the activities in NRC Regulatory Guide 1.33, "Quality Assurance Program Requirements (Operation)," Revision 2, Appendix A, February 1978.Regulatory Guide 1.33, Appendix A, Section 6.v, requires procedures for combating emergencies, such as plant fires. Embodied within these requirements is the requirement that the procedures are adequate.Procedure 0-SSI-001, "Safe Shutdown Instructions," Revision 2, specified the licensee's fire emergency response for certain major plant fire events.Contrary to the above, the licensee failed to establish, implement, and maintain an adequate procedure for combating a plant fire event. On December 23, 2008, the licensee revised the entry conditions of procedure 0-SSI-001, "Safe Shutdown Instructions," such that response to a major fire event would have been delayed or prevented. | At this time, TVA considers it too early to assess the results achieved since these corrective actions have only recently been implemented. TVA will conduct an effectiveness review of these corrective actions. | ||
This revision resulted in the procedure being inadequate. | The corrective steps that will be taken. | ||
Specifically, the licensee added a reactor vessel water level entry criterion which would have required operators to remain in the emergency operating instructions until reactor vessel water level decreased to less than +2 inches narrow range, thus delaying or preventing establishment of safe shutdown conditions during a postulated major fire event.This violation is associated with a White significance determination process finding for Units 1, 2, and 3 in the Mitigating Systems cornerstone. | The following corrective actions are planned: | ||
Reply to Violation 2 The reason for the violation, or, if contested, the basis for disputing the violation or severity level.The root cause for this violation is that the preparer and reviewers of the entry condition change had inadequate knowledge of the impact of Safe Shutdown Instruction (SSI) entry condition changes on the plant and did not understand the limits of their technical knowledge. | Prepare and conduct a case study-based seminar covering the lessons learned from this event to operations senior reactor operators, engineers, licensing, fire protection, affected corporate licensing and corporate fire protection personnel, Plant Operations Review Committee and Corrective Action Review Board members, and senior site management. Reinforce the need for rigorous compliance with the Appendix R Fire Protection Program and its significance with respect to achieving safe shutdown. | ||
Underlying this lack of understanding were two factors. These factors are a lack of knowledge of the basis for the SSI entry conditions and a lack of documented technical basis for the SSI entry conditions. | Transition to the National Fire Protection Association (NFPA) 805 as the basis for compliance with Appendix R and include appropriate documentation of the licensing basis of the BFN NFPA-805 program in appropriate licensing basis documents. | ||
No contributing causes for this violation have been identified. | Establish review process criteria, identify, and re-review significant incoming regulatory correspondence (e.g., License Amendment SEs, Inspection Reports, and Regulatory Issue Summaries) received between January 2005 and December 2008 against those criteria and enter implementation deficiencies in the Corrective Action Program. | ||
The corrective steps that have been taken and the results achieved.In response to this violation, TVA restored the entry conditions to the BFN SSI to those previously in place prior to the change.The corrective steps that will be taken.Prepare and conduct a case study-based seminar covering the lessons learned from this event to operations senior reactor operators, engineers, licensing, fire protection, affected corporate licensing and corporate fire protection personnel, Plant Operations Review Committee and Corrective Action Review Board members, and senior site management. | The date when full compliance will be achieved. | ||
Reinforce the need for rigorous compliance with the Appendix R Fire Protection Program -and its significance with respect to. achieving safe shutdown.Perform a training needs analysis to define the population and content of the training to address this root cause. Implement the training as specified by the training needs analysis.Transition to the NFPA 805 standard as the basis for compliance with Appendix R and include appropriate documentation of the licensing basis of the BFN NFPA-805 Program in appropriate licensing basis documents. | Full compliance for this violation will be achieved upon completing the implementation of the transition to the NFPA 805 basis for compliance with fire protection regulations. Full implementation of NFPA 805 compliance approach will not be completed until at least 2014. | ||
E-6 Revise appropriate procedure(s) to require that Fire Protection Program changes, including proposed changes to procedures, go through additional challenge prior to approval and revise appropriate procedure(s) to require Time Line analyses of changes to SSI Entry Conditions. | In the interim, TVA plans to initiate fire protection program improvements prior to completion of the transition to NFPA 805. Current program improvements that are planned include: analysis updates, actions to inhibit Common Accident Signal (CAS) logic, revised actions to bypass diesel generator logic in certain fire areas, improved component selection, ensuring the condensate storage tank suction path is available to high pressure makeup systems (High Pressure Coolant Injection/Reactor Core Isolation Cooling) in all fire areas where high pressure makeup is credited, and reducing the number of time critical and long term OMAs in the 39 fire areas. These improvements include implementation of interim revisions to the safe shutdown procedures resulting from the analysis updates. TVA plans to continue fire protection program improvements during the transition to NPFA 805 with implementation of identified program | ||
The date when full compliance will be achieved.Full compliance was achieved for this violation upon restoring the entry conditions to the BFN safe shutdown instructions to those previously in place prior to the change.E-7 ENCLOSURE2 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 REPLY TO NOTICE OF VIOLATION; EA-09-307 REGULATORY COMMITMENT Full compliance for this violation will be achieved upon completing implementation of the NFPA 805 approach to compliance with fire protection requirements. | .changes, where allowed, under the transition requirements with the focus on risk reduction and elimination of OMAs. TVA plans to prioritize these improvements based on those with greater impact on overall fire risk reduction. | ||
Full implementation of NFPA 805 will not be completed until at least 2014.E-8}} | E-5 | ||
Restatement of Violation 2 Technical Specification 5.4.1 .a requires that written procedures be established, implemented, and maintained covering the activities in NRC Regulatory Guide 1.33, "Quality Assurance Program Requirements (Operation)," Revision 2, Appendix A, February 1978. | |||
Regulatory Guide 1.33, Appendix A, Section 6.v, requires procedures for combating emergencies, such as plant fires. Embodied within these requirements is the requirement that the procedures are adequate. | |||
Procedure 0-SSI-001, "Safe Shutdown Instructions," Revision 2, specified the licensee's fire emergency response for certain major plant fire events. | |||
Contrary to the above, the licensee failed to establish, implement, and maintain an adequate procedure for combating a plant fire event. On December 23, 2008, the licensee revised the entry conditions of procedure 0-SSI-001, "Safe Shutdown Instructions," such that response to a major fire event would have been delayed or prevented. This revision resulted in the procedure being inadequate. Specifically, the licensee added a reactor vessel water level entry criterion which would have required operators to remain in the emergency operating instructions until reactor vessel water level decreased to less than +2 inches narrow range, thus delaying or preventing establishment of safe shutdown conditions during a postulated major fire event. | |||
This violation is associated with a White significance determination process finding for Units 1, 2, and 3 in the Mitigating Systems cornerstone. | |||
Reply to Violation 2 The reason for the violation, or, if contested, the basis for disputing the violation or severity level. | |||
The root cause for this violation is that the preparer and reviewers of the entry condition change had inadequate knowledge of the impact of Safe Shutdown Instruction (SSI) entry condition changes on the plant and did not understand the limits of their technical knowledge. Underlying this lack of understanding were two factors. These factors are a lack of knowledge of the basis for the SSI entry conditions and a lack of documented technical basis for the SSI entry conditions. No contributing causes for this violation have been identified. | |||
The corrective steps that have been taken and the results achieved. | |||
In response to this violation, TVA restored the entry conditions to the BFN SSI to those previously in place prior to the change. | |||
The corrective steps that will be taken. | |||
Prepare and conduct a case study-based seminar covering the lessons learned from this event to operations senior reactor operators, engineers, licensing, fire protection, affected corporate licensing and corporate fire protection personnel, Plant Operations Review Committee and Corrective Action Review Board members, and senior site management. Reinforce the need for rigorous compliance with the Appendix R Fire Protection Program -and its significance with respect to. achieving safe shutdown. | |||
Perform a training needs analysis to define the population and content of the training to address this root cause. Implement the training as specified by the training needs analysis. | |||
Transition to the NFPA 805 standard as the basis for compliance with Appendix R and include appropriate documentation of the licensing basis of the BFN NFPA-805 Program in appropriate licensing basis documents. | |||
E-6 | |||
Revise appropriate procedure(s) to require that Fire Protection Program changes, including proposed changes to procedures, go through additional challenge prior to approval and revise appropriate procedure(s) to require Time Line analyses of changes to SSI Entry Conditions. | |||
The date when full compliance will be achieved. | |||
Full compliance was achieved for this violation upon restoring the entry conditions to the BFN safe shutdown instructions to those previously in place prior to the change. | |||
E-7 | |||
ENCLOSURE2 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 REPLY TO NOTICE OF VIOLATION; EA-09-307 REGULATORY COMMITMENT Full compliance for this violation will be achieved upon completing implementation of the NFPA 805 approach to compliance with fire protection requirements. Full implementation of NFPA 805 will not be completed until at least 2014. | |||
E-8}} |
Latest revision as of 17:54, 13 November 2019
ML101410013 | |
Person / Time | |
---|---|
Site: | Browns Ferry |
Issue date: | 05/18/2010 |
From: | Polson K Tennessee Valley Authority |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
EA-09-307, IR-10-007 | |
Download: ML101410013 (11) | |
Text
Tennessee Valley Authority, Post Office Box 2000, Decatur, Aiabama 35609-2000 May18, 2010 10 CFR 2.201 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2 and 3 Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296
Subject:
Reply to Notice of Violation; EA-09-307
Reference:
Letter from NRC to TVA, "Final Significance Determination of Yellow and White Findings and Notice of Violation (NRC Inspection Report Nos.
05000259/2010007, 05000260/2010007 and 05000296/2010007), Browns Ferry Nuclear Plant," dated April 19, 2010 In response to the referenced letter, enclosed please find our reply to the notice of violation.
There is one regulatory commitment contained in this letter as identified in Enclosure 2.
Should you have any questions concerning this submittal, please contact Stan Day at (256) 729-2636.
Respectfully, K. J. Poison Vice President
Enclosures:
- 1. NRC Inspection Report Nos. 05000259/2010007, 05000260/2010007, 05000296/2010007 Reply to Notice of Violation
- 2. Regulatory Commitment cc (See page 2):
U.S. Nuclear Regulatory Commission Page 2 May 18, 2010 cc (Enclosures):
NRC Regional Administrator -,Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant
ENCLOSURE 1 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 NRC INSPECTION REPORT NOS. 0500025912010007, 05000260/2010007, 05000296/2010007 REPLY TO NOTICE OF VIOLATION
Restatement of Violation 1 Title 10 of the Code of Federal Regulations (10 CFR), Part 50.48(b)(1) requires that all nuclear power plants licensed to operate prior to January 1, 1979, must satisfy the applicable requirements of 10 CFR Part 50, Appendix R, Sections Ill.G, Ill.J, and 111.0.
Section IIL.G requires fire protection of safe shutdown capability.
Section III.G.1 requires fire protection features shall be provided for structures, systems, and components important to safe shutdown. These features shall be capable of limiting fire damage, such that one train of systems necessary for achieving and maintaining hot shutdown conditions is free of fire damage.
Section II.G.2 requires, in part, that where cables and equipment of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area outside of primary containment, one of the following means of ensuring that one of the redundant trains is free of fire damage shall be provided:
- a. separation of cables and equipment by a fire barrier having a 3-hour rating; or
- b. separation of cables and equipment by a horizontal distance of more than 20 feet with no intervening combustibles or fire hazards. Fire detection and automatic fire suppression shall be installed in the fire area; or
- c. enclosure of cables and equipment of one redundant train in a fire barrier having a 1-hour fire rating. Fire detection and automatic suppression shall be installed in the fire area.
Contrary to the above, since the restart of each unit (Unit 2-1991, Unit 3-1995, Unit 1-2007) and as of January 20, 2010, the date of the inspection report, the licensee had not met nor has met, as of the date of this NOV, the requirements of 10 CFR Part 50, Appendix R, Section Ill.G, in that:
(i) fire protection features capable of limiting fire damage were not provided for structures, systems, and components important for safe shutdown. Specifically, the Tennessee Valley Authority (licensee) failed to provide fire protection features capable of limiting the fire damage such that one train of systems necessary to achieve and maintain hot shutdown conditions was free from fire damage in Fire Area 8 along with 19 other fire areas designated in the Browns Ferry Fire Protection Report, as required by 10 CFR Part 50, Appendix R, Section III.G.1.
(ii) where cables and equipment of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located in the same fire area, the licensee did not ensure that one of the redundant trains was free of fire damage by providing one of the following means: (a) a 3-hour rated fire barrier; (b) 20 feet of spatial separation (free of intervening combustibles and fire hazards) with detection and suppression installed in the fire area; or (c) a 1-hour rated fire barrier with detection and suppression installed in the fire area. Specifically, cables associated with the RHRSW Pump Al, RHR Pump 1A, and LPCI injection valve 1-FCV-74-53 in Fire Area 1/Fire Zone 1-4 are some of the many examples in which the licensee failed to ensure that one train of cables of redundant systems or equipment necessary to achieve and maintain hot shutdown conditions, located in the same fire area, outside of primary containment was free of fire damage by one of the means described in 10 CFR Part 50, Appendix R, Section III.G.2.
This violation of 10 CFR Part 50, Appendix R, Section 11I.G is associated with a Yellow significance determination process finding for Units 1, 2, and 3 in the Mitigating Systems cornerstone.
E-1
Reply to Violation 1 The reason for the violation, or, if contested, the basis for disputing the violation or severity level, The root cause for this violation is a combination of:
- 1. An entrenched 10 CFR 50, Appendix R compliance position,
- 2. A lack of rigorous review and resolution of regulatory documents, and
- 3. Passive management of the Browns Ferry Nuclear Plant (BFN) Appendix R Program and failure to aggressively implement identified actions.
The initial implementation of the Appendix R Fire Protection Program requirements at BFN in the 1980s included extensive use of Operator Manual Actions (OMAs). The Tennessee Valley Authority (TVA) failed to re-evaluate Appendix R compliance as NRC requirements evolved and were clarified over a period of years.
When the NRC SE for the BFN Appendix R safe shutdown system analysis was issued on December 8, 1988, licensees were not required to formally apply for OMA exemptions. At that time, the NRC approved OMAs through a variety of means. The 1988 SE approved the OMAs covered by the SE. Several subsequent SEs issued from 1989 through BFN, Unit 1, restart in 2007 also addressed OMAs without explicitly approving exemptions.
In 2000, the NRC implemented the Reactor Oversight Process that included inspection of safe shutdown capability. Training materials provided to NRC inspectors in 2001 stated that the NRC did not consider OMAs to be approved unless they were formally exempted in accordance with 10 CFR 50.12, even if they had been previously addressed by NRC-issued SERs. The Nuclear Energy Institute (NEI) took issue with that position, and responded, in early 2002, with a basis for the acceptability of using OMAs to meet Appendix R requirements. The NEI position reinforced the mindset that OMAs, as used at BFN, were an acceptable Appendix R strategy.
After dialog with the industry, the NRC published a draft rulemaking in 2005 to define requirements for using OMAs to comply with requirements of Appendix R, paragraph III.G.2.
The proposed rulemaking was withdrawn on March 6, 2006. The NRC reiterated in the same March 6, 2006, Federal Register notice that OMAs cannot be relied upon in lieu of compliance with Appendix R, III.G.2 requirements. In the same year as the draft rulemaking, the NRC issued Regulatory Issue Summary RIS 2005-30, "Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements," dated December 20, 2005. This RIS clarified:
- Requirements to analyze post-fire spurious actuations that could impact safe shutdown,
- Use of operator manual actions with respect to protection of associated circuits, and
- Use of emergency control stations in accordance with Appendix R, Section llI.G.l.a.
BFN missed the opportunity to identify that site use of emergency control stations differed significantly from NRC guidance contained in the RIS. This issue ultimately led to BFN's misclassification of III.G.1 areas.
TVA met with the NRC in a public meeting on April 5, 2006, to discuss Appendix R requirements for Unit 1 restart. The NRC stated that:
- TVAmust be in compliance with Appendix R,
" All OMAs determined to be risk-significant must be corrected, and
- Non-risk-significant OMAs would be given enforcement discretion for three years starting March 6, 2006.
E-2
TVA initiated a Corrective Action Program (CAP) Problem Evaluation Report (PER) to address the issues identified in the meeting and referred to guidance associated with manual actions stated in the March 6, 2006 Federal Register notice. This PER was subsequently revised to expand the scope to include the need for OMA exemption requests or plant modifications to reduce OMAs for all three units. PER actions were deferred multiple times, until an exemption request was submitted to the NRC by letter dated January 27, 2009, 37 days before the end of the enforcement discretion period.
TVA took no action between 2006 and 2009 to comply with Appendix R requirements by modifying the plant based on the assumption that TVA would be automatically granted OMA exemptions upon request.
The following contributing causes have also been identified for this violation:
- 1. Lack of process infrastructure to accommodate organizational change led to the licensing and fire protection organizations' failure to keep up with changing regulatory climate,
- 3. An absence of effective corporate governance and oversight of the areas of Licensing and-Fire Protection, and
- 4. Ineffective use of CAP to identify Appendix R issues and drive them to resolution.
NRC interpretation and enforcement of Appendix R requirements evolved substantially between 2005 and the NRC Triennial Fire Protection/Appendix R Inspection of BFN in the fall of 2009.
Numerous BFN organizational changes took place in key positions (licensing, engineering, site and corporate management) between 2005 and the investigation of the root cause of this event.
The timing of many of these changes exacerbated the situation.
The infrastructure (procedures, processes, and communications) to ensure that supervisors, managers, and executives were equipped with the necessary knowledge and information was not adequate for site and corporate leadership to stay current with Appendix R requirements.
One of the deficiencies was the lack of effective corporate governance and oversight to 1) verify that TVA was cognizant of evolving Appendix R requirements and interpretations, and 2) provide appropriate advice to BFN and corporate decision-makers in an effective manner.
Between March and May 2007, the BFN, Unit 1, restart licensing staff was disbanded and left BFN. No formal mechanisms were in place to ensure that open fire protection issues from Unit 1 restart were turned over to other BFN personnel and subsequently tracked to completion.
Prior to 2008, TVA nuclear plants operated as nearly autonomous entities, with the corporate office providing support and advice as requested. The relationship between the NRC and the sites was managed at the sites, as were individual projects like Appendix R. At the same time, the corporate Fire Protection/Appendix R Manager managed the interface with the industry, participated in NEI workshops and task forces, and monitored the evolution of Appendix R requirements.
Personnel from BFN did not participate in industry Appendix R activities and depended upon corporate input to remain current with the nuclear industry. The BFN and corporate fire protection/Appendix R organizations were ineffective in developing and implementing a clear plan to achieve compliance with Appendix R requirements. There was disagreement over the different alternatives between early 2006 and early 2008. During this time (pre-2008),
communications between BFN personnel and corporate personnel were ineffective in resolving these differences and no one was accountable to ensure a timely resolution of the issue.
E-3
TVA missed several opportunities to formally identify, document, analyze, and resolve issues associated with Appendix R. In 2005, the NRC published draft rulemaking to provide a method to request exemptions to Appendix R for using OMAs in lieu of meeting Appendix R requirements. Also in 2005, the NRC issued RIS 2005-30, "Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements." TVA did not identify possible impacts for BFN from this RIS or initiate and track actions to ensure compliance.
In June, 2006, the NRC issued RIS 2006-10, "Regulatory Expectations WithAppendix R Paragraph III.G.2 Operator Manual Actions," dated June 30, 2006. TVA failed to conduct a detailed review of each paragraph of the RIS and to thoroughly consider the actions needed to fully comply with that interpretation of Appendix R requirements.
The NRC presented TVA with another opportunity when it issued a Safety Evaluation (SE) for the restart of BFN, Unit 1 on April 25, 2007. In this SE, the NRC advised TVA of NRC positions regarding Appendix R, paragraphs III.G.1 and III.G.2. TVA failed to formally review this SE, or to document the commitments in the SE in the TVA CAP. Site licensing personnel later formally reviewed this SE in March/April 2009. This review was deficient. Contemporaneously with receipt of the SE, TVA Nuclear Assurance conducted a fire protection audit at BFN, and recommended that BFN revisit the definition of III.G.1 versus III.G.2 fire areas. No evidence was found that BFN reacted to this recommendation.
The corrective steps that have been taken and the results achieved, WVA implemented the following immediate actions in response to this violation:
- 1. Established compensatory fire watches on all three units to mitigate the possibility of an "Appendix R" fire developing from a smaller fire.
- 2. Evaluated the most critical operator manual actions and revised selected safe shutdown instructions to include the requirements for independent confirmation of operator manual actions in order to improve the likelihood of the success of these actions.
Additional corrective actions taken include the following:
- 1. Establishing corporate governance and oversight of BFN Licensing Activities. This action included the following.
- a. Established and filled the position of a Corporate Vice President of Nuclear Licensing with governance authority and oversight over site licensing activities.
- b. Established and filled the position of a Corporate Licensing Manager for BFN.
- c. Established corporate licensing review and approval of site licensing submittals.
- d. Assigned authority to approve NRC submittals to the Site Vice President or Corporate Vice President of Nuclear Licensing.
- e. Established daily fleet licensing telephone calls to report regulatory issues and challenge responses.
- f. Revised a business practice to strengthen the guidance for effective governance and oversight by corporate functional area managers.
- 2. Re-established formal review of incoming regulatory correspondence including independent review and tracking.
- 3. Established and filled position for Corporate Fire Protection Program Manager with authority and oversight over site Fire Protection Programs.
E-4
Improvements to the CAP initiated in response to two previous PERs (Nos. 131878 and 136489) addressed the CAP weaknesses observed for this violation. Additionally a root cause analysis and development of the corrective action plan for PER 223536 has been initiated and is ongoing to address the recently NRC identified substantive crosscutting theme in the area of Problem Identification and Resolution.
Interim guidance to require fire protection program changes go through additional challenge prior to approval and require time line analyses of changes to Safe Shutdown Instruction (SSI) entry conditions and OMAs was issued.
At this time, TVA considers it too early to assess the results achieved since these corrective actions have only recently been implemented. TVA will conduct an effectiveness review of these corrective actions.
The corrective steps that will be taken.
The following corrective actions are planned:
Prepare and conduct a case study-based seminar covering the lessons learned from this event to operations senior reactor operators, engineers, licensing, fire protection, affected corporate licensing and corporate fire protection personnel, Plant Operations Review Committee and Corrective Action Review Board members, and senior site management. Reinforce the need for rigorous compliance with the Appendix R Fire Protection Program and its significance with respect to achieving safe shutdown.
Transition to the National Fire Protection Association (NFPA) 805 as the basis for compliance with Appendix R and include appropriate documentation of the licensing basis of the BFN NFPA-805 program in appropriate licensing basis documents.
Establish review process criteria, identify, and re-review significant incoming regulatory correspondence (e.g., License Amendment SEs, Inspection Reports, and Regulatory Issue Summaries) received between January 2005 and December 2008 against those criteria and enter implementation deficiencies in the Corrective Action Program.
The date when full compliance will be achieved.
Full compliance for this violation will be achieved upon completing the implementation of the transition to the NFPA 805 basis for compliance with fire protection regulations. Full implementation of NFPA 805 compliance approach will not be completed until at least 2014.
In the interim, TVA plans to initiate fire protection program improvements prior to completion of the transition to NFPA 805. Current program improvements that are planned include: analysis updates, actions to inhibit Common Accident Signal (CAS) logic, revised actions to bypass diesel generator logic in certain fire areas, improved component selection, ensuring the condensate storage tank suction path is available to high pressure makeup systems (High Pressure Coolant Injection/Reactor Core Isolation Cooling) in all fire areas where high pressure makeup is credited, and reducing the number of time critical and long term OMAs in the 39 fire areas. These improvements include implementation of interim revisions to the safe shutdown procedures resulting from the analysis updates. TVA plans to continue fire protection program improvements during the transition to NPFA 805 with implementation of identified program
.changes, where allowed, under the transition requirements with the focus on risk reduction and elimination of OMAs. TVA plans to prioritize these improvements based on those with greater impact on overall fire risk reduction.
E-5
Restatement of Violation 2 Technical Specification 5.4.1 .a requires that written procedures be established, implemented, and maintained covering the activities in NRC Regulatory Guide 1.33, "Quality Assurance Program Requirements (Operation)," Revision 2, Appendix A, February 1978.
Regulatory Guide 1.33, Appendix A, Section 6.v, requires procedures for combating emergencies, such as plant fires. Embodied within these requirements is the requirement that the procedures are adequate.
Procedure 0-SSI-001, "Safe Shutdown Instructions," Revision 2, specified the licensee's fire emergency response for certain major plant fire events.
Contrary to the above, the licensee failed to establish, implement, and maintain an adequate procedure for combating a plant fire event. On December 23, 2008, the licensee revised the entry conditions of procedure 0-SSI-001, "Safe Shutdown Instructions," such that response to a major fire event would have been delayed or prevented. This revision resulted in the procedure being inadequate. Specifically, the licensee added a reactor vessel water level entry criterion which would have required operators to remain in the emergency operating instructions until reactor vessel water level decreased to less than +2 inches narrow range, thus delaying or preventing establishment of safe shutdown conditions during a postulated major fire event.
This violation is associated with a White significance determination process finding for Units 1, 2, and 3 in the Mitigating Systems cornerstone.
Reply to Violation 2 The reason for the violation, or, if contested, the basis for disputing the violation or severity level.
The root cause for this violation is that the preparer and reviewers of the entry condition change had inadequate knowledge of the impact of Safe Shutdown Instruction (SSI) entry condition changes on the plant and did not understand the limits of their technical knowledge. Underlying this lack of understanding were two factors. These factors are a lack of knowledge of the basis for the SSI entry conditions and a lack of documented technical basis for the SSI entry conditions. No contributing causes for this violation have been identified.
The corrective steps that have been taken and the results achieved.
In response to this violation, TVA restored the entry conditions to the BFN SSI to those previously in place prior to the change.
The corrective steps that will be taken.
Prepare and conduct a case study-based seminar covering the lessons learned from this event to operations senior reactor operators, engineers, licensing, fire protection, affected corporate licensing and corporate fire protection personnel, Plant Operations Review Committee and Corrective Action Review Board members, and senior site management. Reinforce the need for rigorous compliance with the Appendix R Fire Protection Program -and its significance with respect to. achieving safe shutdown.
Perform a training needs analysis to define the population and content of the training to address this root cause. Implement the training as specified by the training needs analysis.
Transition to the NFPA 805 standard as the basis for compliance with Appendix R and include appropriate documentation of the licensing basis of the BFN NFPA-805 Program in appropriate licensing basis documents.
E-6
Revise appropriate procedure(s) to require that Fire Protection Program changes, including proposed changes to procedures, go through additional challenge prior to approval and revise appropriate procedure(s) to require Time Line analyses of changes to SSI Entry Conditions.
The date when full compliance will be achieved.
Full compliance was achieved for this violation upon restoring the entry conditions to the BFN safe shutdown instructions to those previously in place prior to the change.
E-7
ENCLOSURE2 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 REPLY TO NOTICE OF VIOLATION; EA-09-307 REGULATORY COMMITMENT Full compliance for this violation will be achieved upon completing implementation of the NFPA 805 approach to compliance with fire protection requirements. Full implementation of NFPA 805 will not be completed until at least 2014.
E-8