ML18249A075: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
Line 2: Line 2:
| number = ML18249A075
| number = ML18249A075
| issue date = 09/26/2018
| issue date = 09/26/2018
| title = Vogtle Electric Generating Plant, Units 1 and 2 - Closeout of Generic Letter 2016-01, Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools (CAC Nos. MF9410 and MF9411; EPID L-2016-LRC-0001)
| title = Closeout of Generic Letter 2016-01, Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools (CAC Nos. MF9410 and MF9411; EPID L-2016-LRC-0001)
| author name = Broaddus D A
| author name = Broaddus D A
| author affiliation = NRC/NRR/DORL/LSPB
| author affiliation = NRC/NRR/DORL/LSPB

Revision as of 03:28, 5 April 2019

Closeout of Generic Letter 2016-01, Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools (CAC Nos. MF9410 and MF9411; EPID L-2016-LRC-0001)
ML18249A075
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 09/26/2018
From: Broaddus D A
Special Projects and Process Branch
To: Gayheart C A
Southern Nuclear Operating Co
WALL S P, 415-2855
References
CAC MF9410, CAC MF9411, EPID L-2016-LRC-0001, GL-16-001, OMB 3150-0231
Download: ML18249A075 (3)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 September 26, 2018 0MB Control No. 3150-0231 Ms. Cheryl A. Gayheart Regulatory Affairs Director Southern Nuclear Operating Company, Inc. 3535 Colonnade Parkway Birmingham, AL 35243

SUBJECT:

VOGTLE ELECTRIC GENERATING PLANT, UNITS 1 AND 2-CLOSEOUT OF GENERIC LETTER 2016-01, "MONITORING OF NEUTRON-ABSORBING MATERIALS IN SPENT FUEL POOLS" (CAC NOS. MF9410 AND MF9411; EPID L-2016-LRC-0001)

Dear Ms. Gayheart:

On April 7, 2016, the U.S. Nuclear Regulatory Commission (NRC) issued Generic Letter (GL) 2016-01, "Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools" (Agencywide Documents Access and Management System (ADAMS) Accession No. ML 16097A169), to address the degradation of neutron-absorbing materials (NAMs) in wet storage systems for reactor fuel at power and non-power reactors.

The generic letter requested that licensees provide information to allow the NRC staff to verify continued compliance through effective monitoring to identify and mitigate any degradation or deformation of NAMs credited for criticality control in spent fuel pools (SFPs). By letter dated November 2, 2016 (ADAMS Accession No. ML 16307A297), as supplemented by letter dated May 31, 2018 (ADAMS Accession No. ML 181518046), Southern Nuclear Operating Company, Inc. (the licensee), responded to GL 2016-01 for Vogtle Electric Generating Plant, Units 1 and 2 (Vogtle 1 and 2). In the licensee's response to GL 2016-01, as supplemented, the licensee stated that, for Vogtle 2, no NAMs are currently credited to meet NRC subcritically requirements in the SFP. The NRC staff performed a thorough review of the licensee's response, any documents referenced therein, and other applicable licensing basis documents.

Based on the review, the NRC staff concludes that the licensee has correctly identified that the Vogtle 2 licensing basis is consistent with the criteria for Category 1 as defined in GL 2016-01. In the licensee's response to GL 2016-01, as supplemented, the licensee stated that, for Vogtle 1, it relies on continual monitoring industry operating experience, including ongoing participation in the Electric Power Research Institute (EPRI) Neutron Absorber Users Group (NAUG) and its related programs, to evaluate the condition of the Boral in its SFP. The licensee indicated that the NAUG, through EPRI, has completed a study which analyzes the criticality impact of blisters and pits on Boral. This study is described in EPRI document 3002013119, "Evaluation of the Impact of Neutron Absorber Material Blistering and Pitting on Spent Fuel Pool Reactivity," May 2018 (ADAMS Accession No. ML 18226A292).

The licensee also stated that the NAUG, through EPRI, is developing an industry-wide program to gather water chemistry and C. Gayheart Baral coupon data for SFPs. This program is described in EPRI document 3002013122, "Roadmap for the lndustrywide Learning Aging Management Program (i-LAMP) for Neutron Absorber Materials in Spent Fuel Pools," May 2018 (ADAMS Accession No. ML 18226A291

). The licensee stated that relevant issues emerging from such industry efforts will be monitored through the licensee's Operating Experience Program and Corrective Action Program. The stated purpose of this program is to inform the condition of the Baral at sites with no coupon, or in-situ, testing of its Baral, with results from other sites using the "sister pool criteria." The NRC staff notes that aspects of the industry-wide program referenced in EPRI Report 3002013122 (i.e., the Baral coupon database, water chemistry database, sister pool criteria, etc.) are not yet complete and some guidelines might not be fully developed until 2020. While the program as described in EPRI Report 3002013122 is not yet complete, the NRC staff did use the information found in EPRI Report 300203119 to support the conclusion that no additional information is needed, at this time, to address the five areas of information described in Appendix A to GL 2016-01 for Baral. The NRC staff also notes that the studies documented in EPRI Reports 3002013119 and 3002013122 are intended to be generic analyses and were not provided as site-specific analyses.

Therefore, the results of the analyses, or any part of those analyses, have currently not been shown as directly applicable to Vogtle 1 and 2. In addition, the NRC staff did not review whether the EPRI Reports could be used to justify equipment operability, design basis changes, or licensing changes requested pursuant to Title 10 of the Code of Federal Regulations, Section 50.90, "Application for amendment of license, construction permit, or early site permit." However, the NRC staff's review determined that the EPRI reports provide the information required to satisfy the request in GL 2016-01 for Baral, at this time. For Vogtle 1 and 2, the NRC staff's review determined that the information provided sufficiently addressed the five areas of information described in Appendix A to GL 2016-01. Based on the review of the information provided, the NRC staff concludes no further information is requested regarding GL 2016-01. Docket Nos. 50-424 and 50-425 cc: ListServ Sincerely, Douglas A. Broaddus, Chief Special Projects and Process Branch Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation C. Gayheart

SUBJECT:

VOGTLE ELECTRIC GENERATING PLANT, UNITS 1 AND 2 -CLOSEOUT OF GENERIC LETTER 2016-01, "MONITORING OF NEUTRON-ABSORBING MA TE RIALS IN SPENT FUEL POOLS" (CAC NOS. MF9410 AND MF9411; EPID L-2016-LRC-0001)

DATED SEPTEMBER 26, 2018 DISTRIBUTION:

PUBLIC PM File Copy RidsACRS_MailCTR Resource RidsNrrDirslrgb Resource RidsNrrDmlrMccb Resource RidsNrrDorlLpl2-1 Resource RidsNrrDorlLspb Resource RidsNrrDssSnpb Resource RidsNrrLAKGoldstein Resource RidsNrrLAJBurkhardt Resource RidsNrrPMVogtle Resource RidsRgn2MailCenter Resource BBenney, NRR SKrepel, NRR SWall, NRR ADAMS Accession No.: ML 18249A075 OFFICE NRR/DORL/LSPB/PM NRR/DORL/LPL2-1 PM* NAME SWall MOrenak DATE 9/25/18 9/18/18 OFFICE NRR/DMLR/MCCB/BC*

NRR/OIRS/IRGB/BC*

NAME SBloom BPham DATE 9/25/18 9/25/18 NRR/DORL/LAiT PTalukdar 9/17/18 NRR/DSS/SNPB/BC*

Rlukes 9/19/18 OFFICIAL RECORD COPY *via email NRR/DORL/LSPB/LA JBurkhardt 9/17/18 NRR/DORL/LSPB/BC DBroaddus 9/26/18