ENS 49638: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 12/16/2013 16:27 CST
| event date = 12/16/2013 16:27 CST
| last update date = 12/16/2013
| last update date = 12/16/2013
| title = Unanalyzed Condition Due To Unfused Direct Current Ammeter Circuits
| title = Unanalyzed Condition Due to Unfused Direct Current Ammeter Circuits
| event text = At 1627 CST on December 16, 2013 Farley Nuclear Plant determined that the following was an unanalyzed condition:
| event text = At 1627 CST on December 16, 2013 Farley Nuclear Plant determined that the following was an unanalyzed condition:
As a result of recent industry operating experience (OE 305419, EN 49411, EN 49419) regarding the impact of un-fused Direct Current (DC) ammeter circuits in the Control Room, Farley performed a review of ammeter circuitry for similar issues. The review determined the described condition to be applicable to Farley resulting in an unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The wiring design for the ammeters contains a shunt in the current flow from each DC battery and battery charger, but the ammeter wiring attached to the shunt does not contain fuses.
As a result of recent industry operating experience (OE 305419, EN 49411, EN 49419) regarding the impact of un-fused Direct Current (DC) ammeter circuits in the Control Room, Farley performed a review of ammeter circuitry for similar issues. The review determined the described condition to be applicable to Farley resulting in an unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The wiring design for the ammeters contains a shunt in the current flow from each DC battery and battery charger, but the ammeter wiring attached to the shunt does not contain fuses.

Latest revision as of 21:52, 1 March 2018

ENS 49638 +/-
Where
Farley Southern Nuclear icon.png
Alabama (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+-0.83 h-0.0346 days <br />-0.00494 weeks <br />-0.00114 months <br />)
Opened: Darrin Gard
21:37 Dec 16, 2013
NRC Officer: Daniel Mills
Last Updated: Dec 16, 2013
49638 - NRC Website
Loading map...