| title = Unusual Event Declared Due | | title = Unusual Event Declared Due to Loss of Offsite Power | ||
| event text = UE SU1.1 declared due to momentary loss of power from the qualified off-site source. Both Emergency Diesel Generators started and loaded to supply power to both of the Emergency Buses. | | event text = UE SU1.1 declared due to momentary loss of power from the qualified off-site source. Both Emergency Diesel Generators started and loaded to supply power to both of the Emergency Buses. | ||
'A' Service Water Pump did not start on Blackout sequencer. Sufficient Service Water flow is available from the other three operating pumps. All other systems operated as designed." | 'A' Service Water Pump did not start on Blackout sequencer. Sufficient Service Water flow is available from the other three operating pumps. All other systems operated as designed." |
Latest revision as of 21:44, 1 March 2018
Where | |
---|---|
Robinson South Carolina (NRC Region 2) | |
Reporting | |
Emergency class: | Unusual Event |
10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
LER: | 05000261/LER-2016-005 |
Time - Person (Reporting Time:+-3.55 h-0.148 days <br />-0.0211 weeks <br />-0.00486 months <br />) | |
Opened: | Martin Bowskill 13:44 Oct 8, 2016 |
NRC Officer: | Daniel Mills |
Last Updated: | Oct 9, 2016 |