{{#Wiki_filter:Entergy Operations, Inc.
{{#Wiki_filter:W3F1-2018-0037 June 27, 2018 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555  
17265 River Road Killona, LA 70057-3093 Tel 504-739-6685 jjarrel@entergy.com John P. Jarrell III Manager, Regulatory Assurance Waterford 3 W3F1-2018-0037 June 27, 2018 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555


==Subject:==
==Subject:==
Closure of Commitment Associated with Control Element Assembly Drop Time License Amendment Waterford Steam Electric Station, Unit 3 (Waterford 3)
Closure of Commitment Associated with Control Element Assembly Drop Time License Amendment Waterford Steam Electric Station, Unit 3 (Waterford 3)
Docket No. 50-382 License No. NPF-38
Docket No. 50-382 License No. NPF-38  


==References:==
==References:==
Line 32: Line 31:
: 4. NRC Letter, Verification Letter of the Approval Version of Westinghouse Electric Company Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), (TAC No.
: 4. NRC Letter, Verification Letter of the Approval Version of Westinghouse Electric Company Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), (TAC No.
MF3096), January 8, 2018 [ADAMS Accession Number ML17338A453].
MF3096), January 8, 2018 [ADAMS Accession Number ML17338A453].
: 5. PROPRIETARY - Westinghouse Letter CWTR3-18-14 to Entergy Operations, Inc., Transmittal of Thermal Conductivity Degradation Justification Applicable to Waterford-3, March 23, 2018.
: 5. PROPRIETARY - Westinghouse Letter CWTR3-18-14 to Entergy Operations, Inc., Transmittal of Thermal Conductivity Degradation Justification Applicable to Waterford-3, March 23, 2018.  


==Dear Sir or Madam:==
==Dear Sir or Madam:==
This letter serves as notification by Entergy Operations, Inc. (Entergy) of completion of Commitment 4 associated with License Amendment 246 (Control Element Assembly Drop Times).
This letter serves as notification by Entergy Operations, Inc. (Entergy) of completion of Commitment 4 associated with License Amendment 246 (Control Element Assembly Drop Times).
Entergy Operations, Inc.
17265 River Road Killona, LA 70057-3093 Tel 504-739-6685 jjarrel@entergy.com John P. Jarrell III Manager, Regulatory Assurance Waterford 3


W3F1-2018-0037 Page 2 of 3 Commitment 4 states the following:
W3F1-2018-0037 Page 2 of 3 Commitment 4 states the following:
Line 45: Line 45:
This letter contains no new commitments.
This letter contains no new commitments.
If you have any questions or require additional information, please contact the Regulatory Assurance Manager, John P. Jarrell, at (504) 739-6685.
If you have any questions or require additional information, please contact the Regulatory Assurance Manager, John P. Jarrell, at (504) 739-6685.
Sincerely, JPJ/MMZ
Sincerely, JPJ/MMZ  


==Enclosure:==
==Enclosure:==
Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 (with attachment)
Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 (with attachment)  


W3F1-2018-0037 Page 3 of 3 cc:   Mr. Kriss Kennedy, Regional Administrator U.S. NRC, Region IV RidsRgn4MailCenter@nrc.gov U.S. NRC Project Manager for Waterford 3 April.Pulvirenti@nrc.gov U.S. NRC Senior Resident Inspector for Waterford 3 Frances.Ramirez@nrc.gov Chris.Speer@nrc.gov
W3F1-2018-0037 Page 3 of 3 cc:
Mr. Kriss Kennedy, Regional Administrator U.S. NRC, Region IV RidsRgn4MailCenter@nrc.gov U.S. NRC Project Manager for Waterford 3 April.Pulvirenti@nrc.gov U.S. NRC Senior Resident Inspector for Waterford 3 Frances.Ramirez@nrc.gov Chris.Speer@nrc.gov  


Enclosure to W3F1-2018-0037 Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 (2 pages)
Enclosure to W3F1-2018-0037 Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 (2 pages)
Line 59: Line 60:
Entergy has satisfied this regulatory commitment by completion of part a) and has determined that part b) is not needed, as the existing safety analysis remains bounded and therefore no licensing basis analyses are affected.
Entergy has satisfied this regulatory commitment by completion of part a) and has determined that part b) is not needed, as the existing safety analysis remains bounded and therefore no licensing basis analyses are affected.
Westinghouse topical report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), describes the fuel performance evaluation methodology and the PAD5 computer code which is the principal design tool for evaluating fuel rod performance and meets the review guidance criteria per Sections 4.2 and 15.02 of NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR Edition (SRP). NRC Letter, Verification Letter of the Approval Version of Westinghouse Electric Company Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), dated January 8, 2018 (Reference 4), provided NRC approval of the PAD5 computer code as a long term fuel evaluation model and associated methods. The Final Safety Evaluation for Topical Report WCAP-17642-P/NP, Westinghouse Performance Analysis and Design Model (PAD5),
Westinghouse topical report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), describes the fuel performance evaluation methodology and the PAD5 computer code which is the principal design tool for evaluating fuel rod performance and meets the review guidance criteria per Sections 4.2 and 15.02 of NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR Edition (SRP). NRC Letter, Verification Letter of the Approval Version of Westinghouse Electric Company Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), dated January 8, 2018 (Reference 4), provided NRC approval of the PAD5 computer code as a long term fuel evaluation model and associated methods. The Final Safety Evaluation for Topical Report WCAP-17642-P/NP, Westinghouse Performance Analysis and Design Model (PAD5),
(Reference 3) identifies that this model and associated method accounts for TCD that is applicable to Combustion Engineering Pressurized Water Reactors, and therefore, to Waterford 3.
(Reference 3) identifies that this model and associated method accounts for TCD that is applicable to Combustion Engineering Pressurized Water Reactors, and therefore, to Waterford 3.  


Enclosure to W3F1-2018-0037 Page 2 of 2 Per item a) of the above commitment, Westinghouse has performed an analysis which justifies the TCD allowance used in Waterford 3 (Reference 5). This analysis uses PAD5 to document a code-to-code benchmark to validate that the thermal effects of TCD are sufficiently accounted for in the analyses. The Attachment to this Enclosure contains the summary and conclusions for the TCD allowance justification.
Enclosure to W3F1-2018-0037 Page 2 of 2 Per item a) of the above commitment, Westinghouse has performed an analysis which justifies the TCD allowance used in Waterford 3 (Reference 5). This analysis uses PAD5 to document a code-to-code benchmark to validate that the thermal effects of TCD are sufficiently accounted for in the analyses. The Attachment to this Enclosure contains the summary and conclusions for the TCD allowance justification.  


Enclosure Attachment to W3F1-2018-0037 Westinghouse Electric Company Document CE-18-110, Rev. 0, Attachment 2, Summary and Conclusions for Thermal Conductivity Degradation Allowance Justification (Non-Proprietary)
Enclosure Attachment to W3F1-2018-0037 Westinghouse Electric Company Document CE-18-110, Rev. 0, Attachment 2, Summary and Conclusions for Thermal Conductivity Degradation Allowance Justification (Non-Proprietary)
(6 pages)
(6 pages)  


Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 CE-18-110, Rev. 0, Attachment 2 Summary and Conclusions for Thermal Conductivity Degradation Allowance Justification (Non-Proprietary) 2018 Westinghouse Electric Company LLC. All rights reserved.
Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 2018 Westinghouse Electric Company LLC. All rights reserved.
Core Engineering & Software Development Memo Template Version 2-0
Core Engineering & Software Development Memo Template Version 2-0 CE-18-110, Rev. 0, Attachment 2 Summary and Conclusions for Thermal Conductivity Degradation Allowance Justification (Non-Proprietary)  
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)


Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 1 of 5 The PAD5 benchmark study is performed as a code-to-code comparison, which shows temperature, RIP and gap conductance differences between the PAD5 and FATES3B code when applied to Waterford-3. The PAD5 code has considered a wide array of thermal data from the Halden reactor, including data at a wide range of powers and burnups. The benchmark study indicates the differences in the thermal model behavior between the two codes including any models that contribute to fuel temperature predictions. The differences in fuel temperatures and rod internal pressures were reviewed with respect to how they are used in the Waterford-3 safety analyses.
Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 1 of 5 Core Engineering & Software Development Memo Template Version 2-0 The PAD5 benchmark study is performed as a code-to-code comparison, which shows temperature, RIP and gap conductance differences between the PAD5 and FATES3B code when applied to Waterford-3. The PAD5 code has considered a wide array of thermal data from the Halden reactor, including data at a wide range of powers and burnups. The benchmark study indicates the differences in the thermal model behavior between the two codes including any models that contribute to fuel temperature predictions. The differences in fuel temperatures and rod internal pressures were reviewed with respect to how they are used in the Waterford-3 safety analyses.
A review of the fuel performance design criteria listed in Reference 3 was performed based on the benchmark study. Table A provides a summary of the evaluations for each criterion. The design criteria that were reviewed include Rod Internal Pressure (RIP) - no clad liftoff, Departure from Nucleate Boiling (DNB) propagation, clad stress, clad strain, clad oxidation and hydriding, fuel melt, clad fretting, clad fatigue, clad flattening, and rod axial growth.
A review of the fuel performance design criteria listed in Reference 3 was performed based on the benchmark study. Table A provides a summary of the evaluations for each criterion. The design criteria that were reviewed include Rod Internal Pressure (RIP) - no clad liftoff, Departure from Nucleate Boiling (DNB) propagation, clad stress, clad strain, clad oxidation and hydriding, fuel melt, clad fretting, clad fatigue, clad flattening, and rod axial growth.
The review of the fuel performance criteria has shown that all fuel performance limits will be met considering the effects of TCD.
The review of the fuel performance criteria has shown that all fuel performance limits will be met considering the effects of TCD.
Line 80: Line 81:
The results of the Non-LOCA analyses are unchanged with respect to the PAD5 benchmark study.
The results of the Non-LOCA analyses are unchanged with respect to the PAD5 benchmark study.
Therefore, this comparison demonstrates that in all cases the limiting results and conclusions remain unchanged.
Therefore, this comparison demonstrates that in all cases the limiting results and conclusions remain unchanged.
The TCD allowance included in the Control Rod Drop Time LAR is confirmed to be acceptable based on the PAD5 benchmark study.
The TCD allowance included in the Control Rod Drop Time LAR is confirmed to be acceptable based on the PAD5 benchmark study.  
Core Engineering & Software Development Memo Template Version 2-0
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)
    *** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)


Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 2 of 5 Table A: Summary of Fuel Performance Design Criteria Criterion                                       Evaluation RIP - No Clad Liftoff           Bounded Clad Strain                     Limit remains met Clad Fatigue                   Limit remains met Fuel Melt                       Bounded DNB Propagation                 Bounded Clad Stress                     Bounded Oxidation/Hydriding             Not Impacted Clad Fretting                   Not Impacted Clad Flattening                 Not Impacted Rod Axial Growth               Not Impacted Core Engineering & Software Development Memo Template Version 2-0
Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 2 of 5 Core Engineering & Software Development Memo Template Version 2-0 Table A: Summary of Fuel Performance Design Criteria Criterion Evaluation RIP - No Clad Liftoff Bounded Clad Strain Limit remains met Clad Fatigue Limit remains met Fuel Melt Bounded DNB Propagation Bounded Clad Stress Bounded Oxidation/Hydriding Not Impacted Clad Fretting Not Impacted Clad Flattening Not Impacted Rod Axial Growth Not Impacted  
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)


Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 3 of 5 Figure A: PCT Comparison Between PAD5 Based Inputs and FATES3B Based Inputs 2100 Peak Cladding Temperature (deg F) 2000 17000   19000     21000     23000       25000     27000       29000       31000       33000 Rod Average Burnup (MWD/MTU)
Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 3 of 5 Core Engineering & Software Development Memo Template Version 2-0 Figure A: PCT Comparison Between PAD5 Based Inputs and FATES3B Based Inputs 2000 2100 17000 19000 21000 23000 25000 27000 29000 31000 33000 Peak Cladding Temperature (deg F)
Rod Average Burnup (MWD/MTU)
STRIKIN-II AOR (1.0 DEG/PD)
STRIKIN-II AOR (1.0 DEG/PD)
STRIKIN-II (1.0 DEG/PD) w/ PAD5 FAT, RIP & Gas Composition STRIKIN-II AOR (0.8 DEG/PD)
STRIKIN-II (1.0 DEG/PD) w/ PAD5 FAT, RIP & Gas Composition STRIKIN-II AOR (0.8 DEG/PD)
STRIKIN-II (0.8 DEG/PD) w/ PAD5 FAT, RIP & Gas Composition Core Engineering & Software Development Memo Template Version 2-0
STRIKIN-II (0.8 DEG/PD) w/ PAD5 FAT, RIP & Gas Composition
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)


Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 4 of 5 Figure B: Comparison of Fuel Melt Limit 5100 5050 5000 Temperature (deg F) 4950 4900 4850 4800 4750 4700 0       10000         20000         30000         40000       50000         60000       70000 Rod Average Burnup (MWD/MTU)
Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 4 of 5 Core Engineering & Software Development Memo Template Version 2-0 Figure B: Comparison of Fuel Melt Limit 4700 4750 4800 4850 4900 4950 5000 5050 5100 0
PAD5 Melt Limit           FATES3B Melt Limit           Analysis of Record Melt Limit Core Engineering & Software Development Memo Template Version 2-0
10000 20000 30000 40000 50000 60000 70000 Temperature (deg F)
Rod Average Burnup (MWD/MTU)
PAD5 Melt Limit FATES3B Melt Limit Analysis of Record Melt Limit
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)


Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 5 of 5 References
Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 5 of 5 Core Engineering & Software Development Memo Template Version 2-0 References 1.
: 1. NRC ADAMS ACCESSION NUMBER ML15289A143, WATERFORD STEAM ELECTRIC STATION, UNIT 3 - ISSUANCE OF AMENDMENT RE: CHANGES TO TECHNICAL SPECIFICATION 3.1.3.4 REGARDING CONTROL ELEMENT ASSEMBLY DROP TIMES (CAC NO. MF6459)
NRC ADAMS ACCESSION NUMBER ML15289A143, WATERFORD STEAM ELECTRIC STATION, UNIT 3 - ISSUANCE OF AMENDMENT RE: CHANGES TO TECHNICAL SPECIFICATION 3.1.3.4 REGARDING CONTROL ELEMENT ASSEMBLY DROP TIMES (CAC NO. MF6459) 2.
: 2. NRC ADAMS ACCESSION NUMBER ML12235A463, ST. LUCIE PLANT, UNIT 2 - ISSUANCE OF AMENDMENT REGARDING EXTENDED POWER UPRATE (TAC. NO. ME5843)
NRC ADAMS ACCESSION NUMBER ML12235A463, ST. LUCIE PLANT, UNIT 2 - ISSUANCE OF AMENDMENT REGARDING EXTENDED POWER UPRATE (TAC. NO. ME5843) 3.
: 3. WCAP-16500-P-A, CE 16x16 Next Generation Fuel Core Reference Report, August 2007.
WCAP-16500-P-A, CE 16x16 Next Generation Fuel Core Reference Report, August 2007.  
Core Engineering & Software Development Memo Template Version 2-0
*** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)}}
  *** This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)}}

Latest revision as of 18:04, 5 January 2025

Closure of Commitment Associated with Control Element Assembly Drop Time License Amendment
ML18178A678
Person / Time
Site: Waterford Entergy icon.png
Issue date: 06/27/2018
From: Jarrell J
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TAC MF3096, W3F1-2018-0037
Download: ML18178A678 (13)


Text

W3F1-2018-0037 June 27, 2018 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

Subject:

Closure of Commitment Associated with Control Element Assembly Drop Time License Amendment Waterford Steam Electric Station, Unit 3 (Waterford 3)

Docket No. 50-382 License No. NPF-38

References:

1. W3F1-2015-0040, License Amendment Request to Revise Control Element Assembly Drop Times, July 2, 2015 [ADAMS Accession Number ML15197A106].
2. NRC License Amendment 246, Control Element Assembly Drop Times, November 13, 2015 [ADAMS Accession Number ML15289A143].
3. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Final Safety Evaluation for Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5)

Westinghouse Electric Company Project 700, September 28, 2017 [ADAMS Accession Number ML17257A338].

4. NRC Letter, Verification Letter of the Approval Version of Westinghouse Electric Company Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), (TAC No.

MF3096), January 8, 2018 [ADAMS Accession Number ML17338A453].

5. PROPRIETARY - Westinghouse Letter CWTR3-18-14 to Entergy Operations, Inc., Transmittal of Thermal Conductivity Degradation Justification Applicable to Waterford-3, March 23, 2018.

Dear Sir or Madam:

This letter serves as notification by Entergy Operations, Inc. (Entergy) of completion of Commitment 4 associated with License Amendment 246 (Control Element Assembly Drop Times).

Entergy Operations, Inc.

17265 River Road Killona, LA 70057-3093 Tel 504-739-6685 jjarrel@entergy.com John P. Jarrell III Manager, Regulatory Assurance Waterford 3

W3F1-2018-0037 Page 2 of 3 Commitment 4 states the following:

The radial power fall-off curve limits shall be verified each cycle as part of the Westinghouse reload analysis methodology until a new licensing basis long term fuel methodology is approved for Waterford 3. Upon NRC approval of a new long term fuel evaluation model and associated methods that explicitly account for thermal conductivity degradation (TCD) that is applicable to Waterford Unit 3 design, Entergy will, within 6 months:

a) Demonstrate that Waterford Unit 3 safety analysis remain conservatively bounded in licensing basis analyses when compared to the NRC-approved new long term fuel evaluation model that is applicable to Waterford Unit 3 design, and/or b) Provide a schedule for reanalysis using the NRC-approved new long term fuel evaluation model that is applicable to Waterford 3 design for any affected licensing basis analyses.

Entergy has satisfied this regulatory commitment by completion of part a) and has determined that part b) is not needed, as the existing safety analysis remains bounded and therefore no licensing basis analyses are affected. Additional information related to this commitment closure is provided in the Enclosure.

Closure of this commitment has been validated by Entergys standard commitment closure verification process.

This letter contains no new commitments.

If you have any questions or require additional information, please contact the Regulatory Assurance Manager, John P. Jarrell, at (504) 739-6685.

Sincerely, JPJ/MMZ

Enclosure:

Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 (with attachment)

W3F1-2018-0037 Page 3 of 3 cc:

Mr. Kriss Kennedy, Regional Administrator U.S. NRC, Region IV RidsRgn4MailCenter@nrc.gov U.S. NRC Project Manager for Waterford 3 April.Pulvirenti@nrc.gov U.S. NRC Senior Resident Inspector for Waterford 3 Frances.Ramirez@nrc.gov Chris.Speer@nrc.gov

Enclosure to W3F1-2018-0037 Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 (2 pages)

Enclosure to W3F1-2018-0037 Page 1 of 2 Waterford Steam Electric Station, Unit 3 Closure of Control Element Assembly Drop Time License Amendment Commitment 4 On July 2, 2015, Entergy submitted a License Amendment Request (Reference 1) to revise the control element assembly drop times associated with Technical Specification 3.1.3.4 for Waterford Steam Electric Station, Unit 3 (Waterford 3). License Amendment 246 was issued on November 13, 2015. As documented in the safety evaluation (Reference 2), Commitment 4 states the following:

Commitment: The radial power fall-off curve limits shall be verified each cycle as part of the Westinghouse reload analysis methodology until a new licensing basis long term fuel methodology is approved for Waterford 3. Upon NRC approval of a new long term fuel evaluation model and associated methods that explicitly account for thermal conductivity degradation (TCD) that is applicable to Waterford Unit 3 design, Entergy will, within 6 months:

a) Demonstrate that Waterford Unit 3 safety analysis remain conservatively bounded in licensing basis analyses when compared to the NRC-approved new long term fuel evaluation model that is applicable to Waterford Unit 3 design, and/or b) Provide a schedule for reanalysis using the NRC-approved new long term fuel evaluation model that is applicable to Waterford 3 design for any affected licensing basis analyses.

Entergy has satisfied this regulatory commitment by completion of part a) and has determined that part b) is not needed, as the existing safety analysis remains bounded and therefore no licensing basis analyses are affected.

Westinghouse topical report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), describes the fuel performance evaluation methodology and the PAD5 computer code which is the principal design tool for evaluating fuel rod performance and meets the review guidance criteria per Sections 4.2 and 15.02 of NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR Edition (SRP). NRC Letter, Verification Letter of the Approval Version of Westinghouse Electric Company Topical Report WCAP-17642-P/NP, Revision 1, Westinghouse Performance Analysis and Design Model (PAD5), dated January 8, 2018 (Reference 4), provided NRC approval of the PAD5 computer code as a long term fuel evaluation model and associated methods. The Final Safety Evaluation for Topical Report WCAP-17642-P/NP, Westinghouse Performance Analysis and Design Model (PAD5),

(Reference 3) identifies that this model and associated method accounts for TCD that is applicable to Combustion Engineering Pressurized Water Reactors, and therefore, to Waterford 3.

Enclosure to W3F1-2018-0037 Page 2 of 2 Per item a) of the above commitment, Westinghouse has performed an analysis which justifies the TCD allowance used in Waterford 3 (Reference 5). This analysis uses PAD5 to document a code-to-code benchmark to validate that the thermal effects of TCD are sufficiently accounted for in the analyses. The Attachment to this Enclosure contains the summary and conclusions for the TCD allowance justification.

Enclosure Attachment to W3F1-2018-0037 Westinghouse Electric Company Document CE-18-110, Rev. 0, Attachment 2, Summary and Conclusions for Thermal Conductivity Degradation Allowance Justification (Non-Proprietary)

(6 pages)

Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 2018 Westinghouse Electric Company LLC. All rights reserved.

Core Engineering & Software Development Memo Template Version 2-0 CE-18-110, Rev. 0, Attachment 2 Summary and Conclusions for Thermal Conductivity Degradation Allowance Justification (Non-Proprietary)

      • This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)

Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 1 of 5 Core Engineering & Software Development Memo Template Version 2-0 The PAD5 benchmark study is performed as a code-to-code comparison, which shows temperature, RIP and gap conductance differences between the PAD5 and FATES3B code when applied to Waterford-3. The PAD5 code has considered a wide array of thermal data from the Halden reactor, including data at a wide range of powers and burnups. The benchmark study indicates the differences in the thermal model behavior between the two codes including any models that contribute to fuel temperature predictions. The differences in fuel temperatures and rod internal pressures were reviewed with respect to how they are used in the Waterford-3 safety analyses.

A review of the fuel performance design criteria listed in Reference 3 was performed based on the benchmark study. Table A provides a summary of the evaluations for each criterion. The design criteria that were reviewed include Rod Internal Pressure (RIP) - no clad liftoff, Departure from Nucleate Boiling (DNB) propagation, clad stress, clad strain, clad oxidation and hydriding, fuel melt, clad fretting, clad fatigue, clad flattening, and rod axial growth.

The review of the fuel performance criteria has shown that all fuel performance limits will be met considering the effects of TCD.

The maximum Large Break Loss of Coolant Accident (LBLOCA) Peak Cladding Temperature (PCT) results are dependent on multiple factors including fuel average temperature, fuel pin pressure and gap conductance. These factors, and others, exert competing influences on the cladding swell and eventual rupture, which block flow channels and thus influence the calculation of PCT due to flow starvation downstream of the flow blockage.

Later in life higher fuel average temperatures and RIP results in increased PCT. However, early in life the low RIP delays rupture and results in increased PCT. The limiting PCT result comes from fuel pellets not coated with ZrB2 and is shown in Figure A. Two different cases are shown because the original FATES3B based STRIKIN-II LBLOCA analysis had two different cases that reported limiting results relative to the 10 CFR 50.46 Appendix K criteria. The cases refer to the break sizes used in the original LBLOCA analysis. In this case, the limiting PCT results are at a burnup 32,000 MWD/MTU. After this point the power decreases to 95% of its full power level and PCT results are no longer limiting.

Incorporating PAD5 predictions from the code-to-code comparison into the LBLOCA analysis results in PCTs less than those reported as part of the Analysis of Record (AOR). Therefore, results of the LBLOCA analyses are conservative with respect to the PAD5 benchmark study.

With the exception of rod ejection the Non-LOCA safety analyses are performed with the CENTS and HERMITE codes. These codes use generic gap conductances to calculate fuel average temperatures used in Doppler feedback analyses. TCD always causes increases in the steady state fuel temperatures, which decreases the Doppler feedback. Events that have an initial rise in power bias temperatures to make the feedback as least negative as possible. The use of more realistic, but conservative, gap conductances in combination with the incorporation of TCD is bounded by the current generic gap conductances. Thus, there is no impact on the Non-LOCA events analyzed with the CENTS and HERMITE codes.

Control rod ejection is analyzed by increasing the deposited energy in the rod to the melt limit. The energy is transformed into an allowable ejected rod worth that is confirmed by Core Design as part of the reload. As shown in Figure B, the fuel melt limit is increased in PAD5. Increasing the melt limit supports increases in the allowable ejected rod worths providing an overall benefit compared to FATES3B based analyses.

The results of the Non-LOCA analyses are unchanged with respect to the PAD5 benchmark study.

Therefore, this comparison demonstrates that in all cases the limiting results and conclusions remain unchanged.

The TCD allowance included in the Control Rod Drop Time LAR is confirmed to be acceptable based on the PAD5 benchmark study.

      • This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)

Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 2 of 5 Core Engineering & Software Development Memo Template Version 2-0 Table A: Summary of Fuel Performance Design Criteria Criterion Evaluation RIP - No Clad Liftoff Bounded Clad Strain Limit remains met Clad Fatigue Limit remains met Fuel Melt Bounded DNB Propagation Bounded Clad Stress Bounded Oxidation/Hydriding Not Impacted Clad Fretting Not Impacted Clad Flattening Not Impacted Rod Axial Growth Not Impacted

      • This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)

Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 3 of 5 Core Engineering & Software Development Memo Template Version 2-0 Figure A: PCT Comparison Between PAD5 Based Inputs and FATES3B Based Inputs 2000 2100 17000 19000 21000 23000 25000 27000 29000 31000 33000 Peak Cladding Temperature (deg F)

Rod Average Burnup (MWD/MTU)

STRIKIN-II AOR (1.0 DEG/PD)

STRIKIN-II (1.0 DEG/PD) w/ PAD5 FAT, RIP & Gas Composition STRIKIN-II AOR (0.8 DEG/PD)

STRIKIN-II (0.8 DEG/PD) w/ PAD5 FAT, RIP & Gas Composition

      • This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)

Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 4 of 5 Core Engineering & Software Development Memo Template Version 2-0 Figure B: Comparison of Fuel Melt Limit 4700 4750 4800 4850 4900 4950 5000 5050 5100 0

10000 20000 30000 40000 50000 60000 70000 Temperature (deg F)

Rod Average Burnup (MWD/MTU)

PAD5 Melt Limit FATES3B Melt Limit Analysis of Record Melt Limit

      • This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)

Westinghouse Non-Proprietary Class 3 CE-18-110, Rev. 0, Attachment 2 Page 5 of 5 Core Engineering & Software Development Memo Template Version 2-0 References 1.

NRC ADAMS ACCESSION NUMBER ML15289A143, WATERFORD STEAM ELECTRIC STATION, UNIT 3 - ISSUANCE OF AMENDMENT RE: CHANGES TO TECHNICAL SPECIFICATION 3.1.3.4 REGARDING CONTROL ELEMENT ASSEMBLY DROP TIMES (CAC NO. MF6459) 2.

NRC ADAMS ACCESSION NUMBER ML12235A463, ST. LUCIE PLANT, UNIT 2 - ISSUANCE OF AMENDMENT REGARDING EXTENDED POWER UPRATE (TAC. NO. ME5843) 3.

WCAP-16500-P-A, CE 16x16 Next Generation Fuel Core Reference Report, August 2007.

      • This record was final approved on 3/22/2018 7:26:44 PM. ( This statement was added by the PRIME system upon its validation)