ENS 40146: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 17: Line 17:
| event date = 09/10/2003 17:46 CDT
| event date = 09/10/2003 17:46 CDT
| last update date = 11/07/2003
| last update date = 11/07/2003
| title = Unanalyzed Condition Due To A Potential Break In Fire Protection Water System
| title = Unanalyzed Condition Due to a Potential Break in Fire Protection Water System
| event text = Potential break of Fire Water Main in Admin Bldg could cause both divisions of Safe Shutdown equipment to be inoperable by flooding the battery rooms for #11 & 12 125VDC Batteries.  Vulnerable section of piping has been isolated to eliminate the flooding concern.  Fire Protection compensatory actions have been established in accordance with the site Fire Protection Program.
| event text = Potential break of Fire Water Main in Admin Bldg could cause both divisions of Safe Shutdown equipment to be inoperable by flooding the battery rooms for #11 & 12 125VDC Batteries.  Vulnerable section of piping has been isolated to eliminate the flooding concern.  Fire Protection compensatory actions have been established in accordance with the site Fire Protection Program.
The licensee informed the NRC resident inspector.
The licensee informed the NRC resident inspector.

Latest revision as of 21:24, 1 March 2018

ENS 40146 +/- *RETRACTED*
Where
Monticello Xcel Energy icon.png
Minnesota (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+-1.73 h-0.0721 days <br />-0.0103 weeks <br />-0.00237 months <br />)
Opened: Chet Desmarais
21:02 Sep 10, 2003
NRC Officer: Howie Crouch
Last Updated: Nov 7, 2003