| title = Low Differential Pressure Resulting In Loss Of Secondary Containment  
| title = Low Differential Pressure Resulting in Loss of Secondary Containment  
| event text = On May 4, 2015 at 1439 [EDT], during maintenance activities on Unit 2 Zone 3 fan discharge exhaust dampers, the control room received a low DP [Differential Pressure] alarm and other confirmatory indications of a loss of building DP.
| event text = On May 4, 2015 at 1439 [EDT], during maintenance activities on Unit 2 Zone 3 fan discharge exhaust dampers, the control room received a low DP [Differential Pressure] alarm and other confirmatory indications of a loss of building DP.
Secondary Containment DP was restored after approximately 2 minutes. The fan exhaust dampers are outside the isolation dampers, therefore, there was no impact on the SGTS [Standby Gas Treatment System] ability to drawdown secondary containment.
Secondary Containment DP was restored after approximately 2 minutes. The fan exhaust dampers are outside the isolation dampers, therefore, there was no impact on the SGTS [Standby Gas Treatment System] ability to drawdown secondary containment.

Latest revision as of 21:47, 1 March 2018

ENS 51040 +/-
Where
Susquehanna Talen Energy icon.png
Pennsylvania (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
LER: 05000387/LER-2015-005
Time - Person (Reporting Time:+3.08 h0.128 days <br />0.0183 weeks <br />0.00422 months <br />)
Opened: Ron Fry
21:44 May 4, 2015
NRC Officer: Dong Park
Last Updated: May 4, 2015
51040 - NRC Website
Loading map...