Line 16: Line 16:
| event date = 10/08/2016 13:17 EDT
| event date = 10/08/2016 13:17 EDT
| last update date = 10/09/2016
| last update date = 10/09/2016
| title = Unusual Event Declared Due To Loss Of Offsite Power
| title = Unusual Event Declared Due to Loss of Offsite Power
| event text = UE SU1.1 declared due to momentary loss of power from the qualified off-site source.  Both Emergency Diesel Generators started and loaded to supply power to both of the Emergency Buses.
| event text = UE SU1.1 declared due to momentary loss of power from the qualified off-site source.  Both Emergency Diesel Generators started and loaded to supply power to both of the Emergency Buses.
'A' Service Water Pump did not start on Blackout sequencer.  Sufficient Service Water flow is available from the other three operating pumps.  All other systems operated as designed."   
'A' Service Water Pump did not start on Blackout sequencer.  Sufficient Service Water flow is available from the other three operating pumps.  All other systems operated as designed."   

Latest revision as of 21:44, 1 March 2018

ENS 52290 +/-
Where
Robinson Duke Energy icon.png
South Carolina (NRC Region 2)
Reporting
Emergency class: Unusual Event
10 CFR 50.72(a) (1) (i), Emergency Class Declaration

10 CFR 50.72(b)(2)(iv)(B), RPS Actuation

10 CFR 50.72(b)(3)(iv)(A), System Actuation
LER: 05000261/LER-2016-005
Time - Person (Reporting Time:+-3.55 h-0.148 days <br />-0.0211 weeks <br />-0.00486 months <br />)
Opened: Martin Bowskill
13:44 Oct 8, 2016
NRC Officer: Daniel Mills
Last Updated: Oct 9, 2016
52290 - NRC Website