Line 16: Line 16:
| event date = 08/17/2017 12:05 EDT
| event date = 08/17/2017 12:05 EDT
| last update date = 08/17/2017
| last update date = 08/17/2017
| title = Actuation Of Turbine Driven Auxiliary Feedwater Pump Due To Loss Of 6.9Kv Shutdown Board
| title = Actuation of Turbine Driven Auxiliary Feedwater Pump Due to Loss of 6.9Kv Shutdown Board
| event text = On August 17, 2017, at 1205 Eastern Daylight Time (EDT), the Watts Bar Nuclear Plant (WBN) lost power to the 1B-B 6.9kV Shutdown Board.  The loss of power to this safety related bus resulted in an automatic start of the Unit 1 Turbine Driven Auxiliary Feedwater Pump (TDAFWP).  The motor driven AFW pumps did not start and were not expected to start for this event.  No other system actuations occurred as a result of loss of power to the 1B-B 6.9kV Shutdown Board.  Power to the 1B-B Shutdown Board was restored at 1505 EDT on August 17, 2017.
| event text = On August 17, 2017, at 1205 Eastern Daylight Time (EDT), the Watts Bar Nuclear Plant (WBN) lost power to the 1B-B 6.9kV Shutdown Board.  The loss of power to this safety related bus resulted in an automatic start of the Unit 1 Turbine Driven Auxiliary Feedwater Pump (TDAFWP).  The motor driven AFW pumps did not start and were not expected to start for this event.  No other system actuations occurred as a result of loss of power to the 1B-B 6.9kV Shutdown Board.  Power to the 1B-B Shutdown Board was restored at 1505 EDT on August 17, 2017.
During the loss of power to the 1B-B Shutdown Board, a reduction in containment and control rod drive mechanism cooling occurred. At 1233 EDT, lower containment average temperature exceeded the procedural limitations specified, and Technical Specification 3.6.5 Condition A was entered for containment average air temperature not within limits.  Lower containment average temperature was restored to within limits at 1525 EDT on August 17, 2017.  This is reportable as a potential loss of safety function.   
During the loss of power to the 1B-B Shutdown Board, a reduction in containment and control rod drive mechanism cooling occurred. At 1233 EDT, lower containment average temperature exceeded the procedural limitations specified, and Technical Specification 3.6.5 Condition A was entered for containment average air temperature not within limits.  Lower containment average temperature was restored to within limits at 1525 EDT on August 17, 2017.  This is reportable as a potential loss of safety function.   

Latest revision as of 20:42, 1 March 2018

ENS 52912 +/-
Where
Watts Bar Tennessee Valley Authority icon.png
Tennessee (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(iv)(A), System Actuation

10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material

10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
Time - Person (Reporting Time:+1.32 h0.055 days <br />0.00786 weeks <br />0.00181 months <br />)
Opened: Brian Mcilnay
17:24 Aug 17, 2017
NRC Officer: Mark Abramovitz
Last Updated: Aug 17, 2017
52912 - NRC Website