ENS 54127
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
17:40 Jun 20, 2019 | |
| Title | Inoperability of Containment Shield Building |
| Event Description | At 1340 EDT on June 20, 2019, a breach in excess of allowable margin in the Unit 2 Shield Building annulus was identified. T.S. LCO 3.6.15, Condition A was entered. The breach is expected to be repaired within the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> allowed LCO time.
No other equipment issues were identified. The Shield Building ensures that the release of radioactive material from the containment atmosphere is restricted to those leakage paths and associated leakage rates assumed in the accident analysis during a Loss of Coolant Accident (LOCA). This event is being reported pursuant to 10 CFR 50.72(b)(3)(v)(C). NRC Resident Inspector has been notified. The breach consists of a tear in a flexible boot seal for a penetration associated with the suction path for gas treatment fans. There is no release of radioactive material associated with this event. |
| Where | |
|---|---|
| Watts Bar Tennessee (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material | |
| LER: | 05000391/LER-2019-002 Breach Due to Penetration Boot Seal Separation Results in Shield Building Inoperability |
| Time - Person (Reporting Time:+0.32 h0.0133 days <br />0.0019 weeks <br />4.38336e-4 months <br />) | |
| Opened: | Brian Mcilnay 17:59 Jun 20, 2019 |
| NRC Officer: | Thomas Kendzia |
| Last Updated: | Jun 20, 2019 |
| 54127 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_54127&oldid=1725616"