{{#Wiki_filter: | {{#Wiki_filter:ADMINISTRATIVE CONTROLS 6.5.11 Ventilation Filter Testing Program (VFTP) | ||
A program shall be established to implement the following required testing of Engineered Safeguards (ES) ventilation systems filters at the frequencies specified in Regulatory Guide 1.52, Revision 2. The VFTP is applicable to the Control Room Emergency Ventilation System (CREVS). | A program shall be established to implement the following required testing of Engineered Safeguards (ES) ventilation systems filters at the frequencies specified in Regulatory Guide 1.52, Revision 2. The VFTP is applicable to the Control Room Emergency Ventilation System (CREVS). | ||
: a. Demonstrate that an inplace cold DOP test of the high efficiency particulate (HEPA) filters shows 99.95% DOP removal when tested in accordance with Regulatory Guide 1.52, Revision 2, at the system design flowrate of 2000 cfm +/- 10%. b. Demonstrate that an inplace halogenated hydrocarbon test of the charcoal adsorbers shows 99.95% halogenated hydrocarbon removal when tested in accordance with Regulatory Guide 1.52, Revision 2, at the system design flow rate of 2000 cfm | : a. Demonstrate that an inplace cold DOP test of the high efficiency particulate (HEPA) filters shows 99.95% DOP removal when tested in accordance with Deleted: for the CREVS Regulatory Guide 1.52, Revision 2, at the system design flowrate of 2000 cfm +/- 10%. | ||
+/- 10%. c. Demonstrate that a laboratory test of a sample of the charcoal adsorber meets the laboratory testing criteria of ASTM D3803-1989 when tested at 30°C and 95% relative humidity for a methyl iodide penetration of | : b. Demonstrate that an inplace halogenated hydrocarbon test of the charcoal adsorbers shows 99.95% halogenated hydrocarbon removal when tested in Deleted: for the CREVS accordance with Regulatory Guide 1.52, Revision 2, at the system design flow rate of 2000 cfm +/- 10%. | ||
: | : c. Demonstrate that a laboratory test of a sample of the charcoal adsorber meets the laboratory testing criteria of ASTM D3803-1989 when tested at 30°C and 95% relative humidity for a methyl iodide penetration of: Deleted: when obtained asdescribed in Regulatory Guide 1.52, Revision 2, for CREVS | ||
, and | : 1. 2.5% for 2 inch charcoal adsorber beds, and Deleted: ; | ||
: 2. 0.5% for 4 inch charcoal adsorber beds, Deleted: . | |||
: d. Demonstrate that the pressure drop across the combined HEPA filters, other filters in the system, and charcoal adsorbers is < 6 inches of water when tested at the following system design flowrate of 2000 cfm | when obtained as described in Regulatory Guide 1.52, Revision 2. Formatted: Indent: Left: 1" | ||
+/- 10%. The provision of SR 4.0.2 and SR 4.0.3 are applicable to the VFTP test frequencies. | : d. Demonstrate that the pressure drop across the combined HEPA filters, other Deleted: for the CREVS, filters in the system, and charcoal adsorbers is < 6 inches of water when tested at the following system design flowrate of 2000 cfm +/- 10%. | ||
Deleted: ¶ The provision of SR 4.0.2 and SR 4.0.3 are applicable to the VFTP test frequencies. CREVS 2,000 cfm¶ ARKANSAS - UNIT 2 6-15 Amendment No. 255,}} |
Latest revision as of 20:39, 14 November 2019
ML080080482 | |
Person / Time | |
---|---|
Site: | Arkansas Nuclear |
Issue date: | 01/08/2008 |
From: | Plant Licensing Branch III-2 |
To: | |
Shared Package | |
ML080080471 | List: |
References | |
TAC MD5380 | |
Download: ML080080482 (1) | |
Text
ADMINISTRATIVE CONTROLS 6.5.11 Ventilation Filter Testing Program (VFTP)
A program shall be established to implement the following required testing of Engineered Safeguards (ES) ventilation systems filters at the frequencies specified in Regulatory Guide 1.52, Revision 2. The VFTP is applicable to the Control Room Emergency Ventilation System (CREVS).
- a. Demonstrate that an inplace cold DOP test of the high efficiency particulate (HEPA) filters shows 99.95% DOP removal when tested in accordance with Deleted: for the CREVS Regulatory Guide 1.52, Revision 2, at the system design flowrate of 2000 cfm +/- 10%.
- b. Demonstrate that an inplace halogenated hydrocarbon test of the charcoal adsorbers shows 99.95% halogenated hydrocarbon removal when tested in Deleted: for the CREVS accordance with Regulatory Guide 1.52, Revision 2, at the system design flow rate of 2000 cfm +/- 10%.
- c. Demonstrate that a laboratory test of a sample of the charcoal adsorber meets the laboratory testing criteria of ASTM D3803-1989 when tested at 30°C and 95% relative humidity for a methyl iodide penetration of: Deleted: when obtained asdescribed in Regulatory Guide 1.52, Revision 2, for CREVS
- 1. 2.5% for 2 inch charcoal adsorber beds, and Deleted: ;
- 2. 0.5% for 4 inch charcoal adsorber beds, Deleted: .
when obtained as described in Regulatory Guide 1.52, Revision 2. Formatted: Indent: Left: 1"
- d. Demonstrate that the pressure drop across the combined HEPA filters, other Deleted: for the CREVS, filters in the system, and charcoal adsorbers is < 6 inches of water when tested at the following system design flowrate of 2000 cfm +/- 10%.
Deleted: ¶ The provision of SR 4.0.2 and SR 4.0.3 are applicable to the VFTP test frequencies. CREVS 2,000 cfm¶ ARKANSAS - UNIT 2 6-15 Amendment No. 255,