ML080080486

From kanterella
Jump to navigation Jump to search

1/8/08 E-Mail Attachment from D. Bice, Entergy Operations, Inc. to A. Wang, NRR/DORL/LP4, Revised Technical Specification Page 6-15 (Clean Copy in Adobe) for ANO, Unit 2, License Amendment Request Re Fuel Handling Ventilation System
ML080080486
Person / Time
Site: Arkansas Nuclear 
(NPF-006)
Issue date: 01/08/2008
From: David Bice
Entergy Operations
To: Wang A
NRC/NRR/ADRO/DORL/LPLIV
Shared Package
ml080080471 List:
References
TAC MD5380
Download: ML080080486 (1)


Text

ARKANSAS - UNIT 2 6-15 Amendment No. 255, ADMINISTRATIVE CONTROLS 6.5.11 Ventilation Filter Testing Program (VFTP)

A program shall be established to implement the following required testing of Engineered Safeguards (ES) ventilation systems filters at the frequencies specified in Regulatory Guide 1.52, Revision 2. The VFTP is applicable to the Control Room Emergency Ventilation System (CREVS).

a.

Demonstrate that an inplace cold DOP test of the high efficiency particulate (HEPA) filters shows 99.95% DOP removal when tested in accordance with Regulatory Guide 1.52, Revision 2, at the system design flowrate of 2000 cfm +/- 10%.

b.

Demonstrate that an inplace halogenated hydrocarbon test of the charcoal adsorbers shows 99.95% halogenated hydrocarbon removal when tested in accordance with Regulatory Guide 1.52, Revision 2, at the system design flow rate of 2000 cfm +/- 10%.

c.

Demonstrate that a laboratory test of a sample of the charcoal adsorber meets the laboratory testing criteria of ASTM D3803-1989 when tested at 30 °C and 95% relative humidity for a methyl iodide penetration of:

1.

2.5% for 2 inch charcoal adsorber beds, and

2.

0.5% for 4 inch charcoal adsorber beds, when obtained as described in Regulatory Guide 1.52, Revision 2.

d.

Demonstrate that the pressure drop across the combined HEPA filters, other filters in the system, and charcoal adsorbers is < 6 inches of water when tested at the following system design flowrate of 2000 cfm +/- 10%.

The provision of SR 4.0.2 and SR 4.0.3 are applicable to the VFTP test frequencies.