StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 10/29/2004 16:00 EDT | | event date = 10/29/2004 16:00 EDT | ||
| last update date = 10/29/2004 | | last update date = 10/29/2004 | ||
| title = Unanalyzed Condition Discovered | | title = Unanalyzed Condition Discovered in 480 Volt Switchgear Room | ||
| event text = The following information was obtained from the licensee via facsimile: | | event text = The following information was obtained from the licensee via facsimile: | ||
On October 29, 2004, at approximately 1600 hours, control room operators were informed by engineering personnel that raceways were located closer than 20 feet from the redundant division without being protected by a fire barrier wrap in accordance with the requirements of 10CFR50 Appendix R, Section III.G.2. | On October 29, 2004, at approximately 1600 hours, control room operators were informed by engineering personnel that raceways were located closer than 20 feet from the redundant division without being protected by a fire barrier wrap in accordance with the requirements of 10CFR50 Appendix R, Section III.G.2. |
Latest revision as of 22:22, 1 March 2018
Where | |
---|---|
Brunswick ![]() North Carolina (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
LER: | 05000324/LER-2004-003 |
Time - Person (Reporting Time:+-3.58 h-0.149 days <br />-0.0213 weeks <br />-0.0049 months <br />) | |
Opened: | Daniel Hardin 16:25 Oct 29, 2004 |
NRC Officer: | Howie Crouch |
Last Updated: | Oct 29, 2004 |
41160 - NRC Website
| |