ENS 41160: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 10/29/2004 16:00 EDT
| event date = 10/29/2004 16:00 EDT
| last update date = 10/29/2004
| last update date = 10/29/2004
| title = Unanalyzed Condition Discovered In 480 Volt Switchgear Room
| title = Unanalyzed Condition Discovered in 480 Volt Switchgear Room
| event text = The following information was obtained from the licensee via facsimile:
| event text = The following information was obtained from the licensee via facsimile:
On October 29, 2004, at approximately 1600 hours, control room operators were informed by engineering personnel that raceways were located closer than 20 feet from the redundant division without being protected by a fire barrier wrap in accordance with the requirements of 10CFR50 Appendix R, Section III.G.2.
On October 29, 2004, at approximately 1600 hours, control room operators were informed by engineering personnel that raceways were located closer than 20 feet from the redundant division without being protected by a fire barrier wrap in accordance with the requirements of 10CFR50 Appendix R, Section III.G.2.

Latest revision as of 22:22, 1 March 2018

ENS 41160 +/-
Where
Brunswick Duke Energy icon.png
North Carolina (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
LER: 05000324/LER-2004-003
Time - Person (Reporting Time:+-3.58 h-0.149 days <br />-0.0213 weeks <br />-0.0049 months <br />)
Opened: Daniel Hardin
16:25 Oct 29, 2004
NRC Officer: Howie Crouch
Last Updated: Oct 29, 2004
41160 - NRC Website
Loading map...