| event date = 11/04/2004 10:54 EST
| event date = 11/04/2004 10:54 EST
| last update date = 11/04/2004
| last update date = 11/04/2004
| title = Unusual Event Declared Due To A Toxic Gas Release Affecting Normal Operations
| title = Unusual Event Declared Due to a Toxic Gas Release Affecting Normal Operations
| event text = At 1054 EST on 11/04/04, the licensee declared an Unusual Event due to an acidic water spray in the Water Treatment Building affecting normal access.  Licensee entered EAL MU-1, Toxic Gas detected within the Protected Area that impacts normal operations.  There were two personnel in the building at the time of the leak, one Non-licensed operator and his supervisor.  The Non-licensed operator was overcome by fumes and became nauseous and was taken to the onsite dispensary.  The non-licensed operator was treated and taken to the local hospital.  The supervisor did not seem to be affected, but he has been taken to the onsite dispensary for any necessary treatment.
| event text = At 1054 EST on 11/04/04, the licensee declared an Unusual Event due to an acidic water spray in the Water Treatment Building affecting normal access.  Licensee entered EAL MU-1, Toxic Gas detected within the Protected Area that impacts normal operations.  There were two personnel in the building at the time of the leak, one Non-licensed operator and his supervisor.  The Non-licensed operator was overcome by fumes and became nauseous and was taken to the onsite dispensary.  The non-licensed operator was treated and taken to the local hospital.  The supervisor did not seem to be affected, but he has been taken to the onsite dispensary for any necessary treatment.
No unplanned release has occurred and no protective action recommendations are applicable at this time.  The acidic water spray  made contact with a 480 Vac panel in the building and has caused an electrical ground.  Equipment in the building that may potentially affect plant operation if damaged are the clearwell pumps.  The clearwell pumps supply seal water for the Main Circulating water pumps, and the non vital service water pumps.
No unplanned release has occurred and no protective action recommendations are applicable at this time.  The acidic water spray  made contact with a 480 Vac panel in the building and has caused an electrical ground.  Equipment in the building that may potentially affect plant operation if damaged are the clearwell pumps.  The clearwell pumps supply seal water for the Main Circulating water pumps, and the non vital service water pumps.

Latest revision as of 22:22, 1 March 2018

ENS 41173 +/-
Where
Perry FirstEnergy icon.png
Ohio (NRC Region 3)
Reporting
Emergency class: Unusual Event
10 CFR 50.72(a) (1) (i), Emergency Class Declaration
Time - Person (Reporting Time:+-4.72 h-0.197 days <br />-0.0281 weeks <br />-0.00647 months <br />)
Opened: Rick Wiles
11:11 Nov 4, 2004
NRC Officer: Jeff Rotton
Last Updated: Nov 4, 2004
41173 - NRC Website