| title = Unanalyzed Condition Due To Missing Fire Barriers
| title = Unanalyzed Condition Due to Missing Fire Barriers
| event text = As part of an extent of condition review related to ENS report 50362 (Unanalyzed Condition Due to Lack of Appropriate Fuse Protection), it was identified that, within the past three years, three additional examples existed of missing fire barriers that could have impacted separation of redundant safe shutdown trains.  For the affected areas associated with each of the three missing barriers, compensatory measures (hourly fire watches) had been in place for three years prior to the discovery of the condition.  However, it was determined the missing barriers met the reporting criteria for 10 CFR 50.72(b)(3)(ii)(B) as unanalyzed conditions that significantly degraded plant safety.
| event text = As part of an extent of condition review related to ENS report 50362 (Unanalyzed Condition Due to Lack of Appropriate Fuse Protection), it was identified that, within the past three years, three additional examples existed of missing fire barriers that could have impacted separation of redundant safe shutdown trains.  For the affected areas associated with each of the three missing barriers, compensatory measures (hourly fire watches) had been in place for three years prior to the discovery of the condition.  However, it was determined the missing barriers met the reporting criteria for 10 CFR 50.72(b)(3)(ii)(B) as unanalyzed conditions that significantly degraded plant safety.
The first condition was the use of rodofoam material in Auxiliary Building seismic joint seals.  Rodofoam is a combustible foam material and does not provide a fire rating equivalent to the barriers in which it was used.  This issue was corrected in a plant modification.
The first condition was the use of rodofoam material in Auxiliary Building seismic joint seals.  Rodofoam is a combustible foam material and does not provide a fire rating equivalent to the barriers in which it was used.  This issue was corrected in a plant modification.

Latest revision as of 20:49, 1 March 2018

ENS 50475 +/-
Where
Prairie Island Xcel Energy icon.png
Minnesota (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+-0.98 h-0.0408 days <br />-0.00583 weeks <br />-0.00134 months <br />)
Opened: Darrell Lapcinski
17:54 Sep 19, 2014
NRC Officer: Howie Crouch
Last Updated: Nov 18, 2014
50475 - NRC Website