ML20195B827: Difference between revisions

From kanterella
Jump to navigation Jump to search
StriderTol Bot change
StriderTol Bot change
 
Line 19: Line 19:


=Text=
=Text=
{{#Wiki_filter:.
{{#Wiki_filter:7
7
}c l
}c                 ,
l ATTACHMENT 1 PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 LICENSE CHANGE APPLICATION ECR 96-01511 ~
l l
" Interim" Pages j
ATTACHMENT 1 PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 LICENSE CHANGE APPLICATION ECR 96-01511 ~
i Unit 2 Unit 3 3.3 3.3-65 8 3.3-188-B 3.3-188 B 3.3-189 8 3.3-189 i
                                              " Interim" Pages                   j
B 3.3-190 B 3.3-190 9906030115 990525
                                                .                                i Unit 2                       Unit 3 3.3                     3.3-65 8 3.3-188-                   B 3.3-188       ;
~
B 3.3-189                   8 3.3-189       i B 3.3-190                   B 3.3-190       ,
PDR ADOCK 05000277 P
                                  ~
PDR L
9906030115 990525 PDR   ADOCK 05000277 P               PDR l
L


LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)
LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)
Loss of Power Instrumentation REQUIRED CHANNELS         SURVE!LLANCE               ALLOWABLE FUNCTION                     PER BUS         REQUIREMENTS                 VALUE
Loss of Power Instrumentation REQUIRED CHANNELS SURVE!LLANCE ALLOWABLE FUNCTION PER BUS REQUIREMENTS VALUE 1.
: 1. 4 kV Emergency sus Undervoltage (Loss of Voltage)
4 kV Emergency sus Undervoltage (Loss of Voltage) a.
: a. Bus undervoltage                         1         SR 3.3.8.1.3     NA SR 3.3.8.1.4
Bus undervoltage 1
: 2. 4 kV Emergency Bus Undervoltage (Degraded Voltage Low Setting) l~       a. Bus Undervoltage                         2         SR 3.3.8.1.1     t 2286 V and s 2706 V (1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
SR 3.3.8.1.3 NA SR 3.3.8.1.4 2.
: b. Time Delay                               2         SR 3.3.8.1.1     t 1.5 seconds and (1 per       SR 3.3.8.1.2     s 2.1 seconds source)       - SR 3.3.8.1.4
4 kV Emergency Bus Undervoltage (Degraded Voltage Low Setting) l~
: 3. 4 kV Emergency Bus Undervoltage (Degraded Voltage High Setting) l       a. Bus Undervoltage                         2         SR 3.3.8.1.1     2 3409 Y and 5 3829 V (1 per       SR 3.3.8.1.2 tource)       SR 3.3.8.1.4
a.
: b. Time Delay                               2         SR 3.3.8.1.1     4 23.0 seconds and (1 per       SR. 3.3.8.1.2     s 37.0 seconds source)       SR 3.3.8.1.4
Bus Undervoltage 2
                  -4   4 kV Emergency Bus undervoltage (Degraded Voltage LOCA)
SR 3.3.8.1.1 t 2286 V and s 2706 V (1 per SR 3.3.8.1.2 source)
                      . a .' Bus Undervoltage                           2         SR 3.3.8.1.1     2 3766 V and 5 3836 V (a)
SR 3.3.8.1.4 b.
(1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
Time Delay 2
: b. Time Delay                               2         SR 3.3.8.1.1     t 9.2 seconds and (1 per       SR 3.3.8.1.2     5 10.8 seconds (a) source)       SR 3.3.8.1.4
SR 3.3.8.1.1 t 1.5 seconds and (1 per SR 3.3.8.1.2 s 2.1 seconds source)
: 5. 4 kV Emergency Bus Undervoltage (Degraded Voltage non-LOCA)
- SR 3.3.8.1.4 3.
: a. Bus Undervoltage-                         2         SR 3.3.8.1.1     2 4116 Y and s 4186 V (a)
4 kV Emergency Bus Undervoltage (Degraded Voltage High Setting) l a.
(1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
Bus Undervoltage 2
: b. Time Delay                               2         SR 3.3.5.1.1     a 57.8 seconds and 5 64.2 (1 per       SR 3.3.8.1.2       seconds (a) source)       SR   3.3.8.1.4 (a) Prior .to the laplementation of modification 96 01511, the Allowable Values of the Functions below are:
SR 3.3.8.1.1 2 3409 Y and 5 3829 V (1 per SR 3.3.8.1.2 tource)
4.s       a 3691 V and 5 3713 V, with internal time delay set t 0.9 seconds and 51.1 seconds, 4.b       t 8.4 seconds and s 9.6 seconds, 5.a       a 4065 y and s 4089 V, with internal time delay' set t 0.9 seconds and 51.1 seconds,
SR 3.3.8.1.4 b.
                                                                                                                  ~ ~ '
Time Delay 2
5.b       t 57.0 seconds and s 63.0 seconds.
SR 3.3.8.1.1 4 23.0 seconds and (1 per SR. 3.3.8.1.2 s 37.0 seconds source)
l PBAPS UNIT 2                                           3.3-65                           Amendment No.
SR 3.3.8.1.4
  . ~ .
-4 4 kV Emergency Bus undervoltage (Degraded Voltage LOCA)
. a.' Bus Undervoltage 2
SR 3.3.8.1.1 2 3766 V and 5 3836 V (a)
(1 per SR 3.3.8.1.2 source)
SR 3.3.8.1.4 b.
Time Delay 2
SR 3.3.8.1.1 t 9.2 seconds and (1 per SR 3.3.8.1.2 5 10.8 seconds (a) source)
SR 3.3.8.1.4 5.
4 kV Emergency Bus Undervoltage (Degraded Voltage non-LOCA) a.
Bus Undervoltage-2 SR 3.3.8.1.1 2 4116 Y and s 4186 V (a)
(1 per SR 3.3.8.1.2 source)
SR 3.3.8.1.4 b.
Time Delay 2
SR 3.3.5.1.1 a 57.8 seconds and 5 64.2 (1 per SR 3.3.8.1.2 seconds (a) source)
SR 3.3.8.1.4 (a) Prior.to the laplementation of modification 96 01511, the Allowable Values of the Functions below are:
4.s a 3691 V and 5 3713 V, with internal time delay set t 0.9 seconds and 51.1 seconds, 4.b t 8.4 seconds and s 9.6 seconds, 5.a a 4065 y and s 4089 V, with internal time delay' set t 0.9 seconds and 51.1 seconds,
~ ~ '
5.b t 57.0 seconds and s 63.0 seconds.
l PBAPS UNIT 2 3.3-65 Amendment No.
. ~.


LOP Instrumentation B 3.3.8.1 BASES (continued)
LOP Instrumentation B 3.3.8.1 BASES (continued)
            ' APPLICABLE       The LOP instrumentation is required for Engineered Safety
' APPLICABLE The LOP instrumentation is required for Engineered Safety
            ~ SAFETY ANALYSES, - Features to function in any accident with a loss of offsite LC0, and         power. The required channels of. LOP instrumentation ensure APPLICABILITY     that the ECCS and other assumed systems powered from the       ,
~ SAFETY ANALYSES, - Features to function in any accident with a loss of offsite LC0, and power. The required channels of. LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the i
DGs, provide plant protection in the event of any of the       i Reference 1 (UFSAR) analyzed accidents in which a loss of offsite power is assumed. The first level is loss of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition. These degraded grid relays disconnect       i the Class IE buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class 1E equipment from achieving its safety function. The degraded grid relays also prevent the Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class IE distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that
Reference 1 (UFSAR) analyzed accidents in which a loss of offsite power is assumed. The first level is loss of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition. These degraded grid relays disconnect i
                                ' the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.
the Class IE buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class 1E equipment from achieving its safety function. The degraded grid relays also prevent the Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class IE distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that
Accident analyses credit the loading of the DG based on the     ;
' the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.
loss of offsite power during a loss of coolant accident.       l The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite         i power.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
l The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite i
power.
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
The OPERABILITY of the LOP instrumentation is dependent upon   l the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1. Each Function must have-a required number of OPERABLE channels       ,
The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.
per 4 kV emergency bus with their setpoints within the         j specified Allowable Values except the bus undervoltage relay which does not have an Allowable.Value. A degraded voltage     l channel is inoperable if its actual trip setpoint is not
Each Function must have-a required number of OPERABLE channels per 4 kV emergency bus with their setpoints within the j
                              ' within its required Allowable Value. Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.     (Note-Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage
specified Allowable Values except the bus undervoltage relay which does not have an Allowable.Value. A degraded voltage l
[                               and timer trip setpoint Allowable Vaulues for the indicated l                                                                                   Sontinued)
channel is inoperable if its actual trip setpoint is not
I' PBAPS UNIT 2                         B 3.3-188                     Revision No.
' within its required Allowable Value.
Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.
(Note-Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage
[
and timer trip setpoint Allowable Vaulues for the indicated l
Sontinued)
I' PBAPS UNIT 2 B 3.3-188 Revision No.
a i''
a i''
: c.                .
 
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE       functions remain at the previously approved values on a SAFETY ANALYSES, relay by relay basis.) The loss of voltage channel is LCO and           inoperable if it will not start the diesel on a loss of APPL.ICABILITY     power to a 4 kV emergency bus.
c.
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE functions remain at the previously approved values on a SAFETY ANALYSES, relay by relay basis.) The loss of voltage channel is LCO and inoperable if it will not start the diesel on a loss of APPL.ICABILITY power to a 4 kV emergency bus.
(continued)
(continued)
The Allowable Values are specified for each applicable-Function in the Table 3.3.8.1-1. The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. O with a trip setpoint within the Allowable Value,peration             is acceptable. Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the limiting values determined by the voltage regulation calculation. The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy potentialtransformeraccuracy,measuringandtestequIpment accuracy margin, and includes a calibration leave alone zone. IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values. IISCP then includes relay drift, calibration leave alone zones, and margins.         Note: Table 3.3.8.1-1 contains a note that prior to the imple(mentation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The set assumes a nominal 35/1 potential transformer ratio. point The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 2 LOP instrumentation are listed below on a function by Function basis.
The Allowable Values are specified for each applicable-Function in the Table 3.3.8.1-1.
In addition, since some equi powered from Unit 3 sources,pment   the Unitrequired by Unit 2 is 3 LOP in'strumentation supporting the required sources must also be OPERABLE. The OPERABILITY requirements for the Unit 3 LOP instrumentation is the same as described in this section, except Function 4 (4 kV   Emergency       Bus Undervoltage,   Degraded                         is not required     to be OPERABLE     since this FunctionVoltage    is rela LOCA)ted to a LOCA on Unit 3 only. theUnit3instrumentationis listed in Unit 3 Table 3.3.8.1-1.
The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. O with a trip setpoint within the Allowable Value,peration is acceptable. Trip setpoints are those predetermined values of output at which an action should take place.
The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state.
The Allowable Values were set equal to the limiting values determined by the voltage regulation calculation.
The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy potentialtransformeraccuracy,measuringandtestequIpment accuracy margin, and includes a calibration leave alone zone.
IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values.
IISCP then includes relay drift, calibration leave alone zones, and margins.
Note: Table 3.3.8.1-1 contains a note that prior to the imple(mentation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The set assumes a nominal 35/1 potential transformer ratio. point The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 2 LOP instrumentation are listed below on a function by Function basis.
In addition, since some equi powered from Unit 3 sources,pment required by Unit 2 is the Unit 3 LOP in'strumentation supporting the required sources must also be OPERABLE.
The OPERABILITY requirements for the Unit 3 LOP instrumentation is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA)ted is not required to be OPERABLE since this Function is rela to a LOCA on Unit 3 only. theUnit3instrumentationis listed in Unit 3 Table 3.3.8.1-1.
: 1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)
: 1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)
When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient power for Therefore, proper       operation the power  suppl of the applicable equipment.
When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient power for Therefore, proper operation of the applicable equipment.
offsite power to DG power.y to the bus is transferred fromThis ensures that will be available to the required equipment.
the power suppl offsite power to DG power.y to the bus is transferred fromThis ensures that will be available to the required equipment.
                                                                                                -(continued)
-(continued)
PBAPS UNIT 2                             B 3.3-189                       Revision No.
PBAPS UNIT 2 B 3.3-189 Revision No.


4
4 LOP Instrumentation
  ~
~
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE       1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)
B 3.3.8.1 BASES APPLICABLE
SAFETY ANALYSIS,   (continued)                                                         ;
: 1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)
LCC. and                                                                               1 APFLICABILITY   The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function )er associated emeregncy bus is only required to be OPERABLE when the associated DG and offsite         :
SAFETY ANALYSIS, (continued)
circuit are required to be OPERABLE. This ensures no single           I instrument failure can preclude the start of three of four DGs.   (One channel inputs to each of the four DGs.       Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, }AC Sources-Shutdown," for Applicability Bases for the DGs.
LCC. and 1
: 2. 3. 4. 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)
APFLICABILITY The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function )er associated emeregncy bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.
(One channel inputs to each of the four DGs.
Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, }AC Sources-Shutdown," for Applicability Bases for the DGs.
2.
3.
4.
: 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)
A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large ECCS motors without risking damage to the motors that could disabia the ECCS function.
A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large ECCS motors without risking damage to the motors that could disabia the ECCS function.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus.
Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded "oltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage             ,
This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
High Setting, and Degraded Voltage Low Setting. These relays monitor the followiny voltage levels with the following time delays: the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source volta e is inverse time delay ; the reduced Function 3 abruptly  tb _ero relay, 3409       volts
Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded "oltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the followiny voltage levels with the following time delays:
                                                  - 3829 vo(lts in c) proximate y 30 seconds when source volta e is reduced aaruptly to 2940 inverse time delay ; the Function 4 relay, 3766 -
the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source volta e is reduced abruptly tb _ero volts (lts in c) proximate y 30 inverse time delay ; the Function 3 relay, 3409 - 3829 vo seconds when source volta e is reduced aaruptly to 2940 volts (lts in approximate y 10 seconds; and the Function 5 inverse time delay ; the Function 4 relay, 3766 -
volts 3836 vo(lts in approximate y 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds.
3836 vo relay, 4116 - 4186 volts in approximately 60 seconds.
(Note: Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The Function 2 and 3 relays are inverse time delay relays. These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for Tc.ontinued)
(Note: Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The Function 2 and 3 relays are inverse time delay relays. These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for Tc.ontinued)
PBAPS UNIT 2                         B 3.3-190                       Revision No.
PBAPS UNIT 2 B 3.3-190 Revision No.


      ~
~
LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)
LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)
Loss of Power Instrtmentation REQUIRED CHANNELS       SURVEILLANCE               ALLOW 48LE FUNCTION                     PER SUS         REQUIREMENTS                 VALUE
Loss of Power Instrtmentation REQUIRED CHANNELS SURVEILLANCE ALLOW 48LE FUNCTION PER SUS REQUIREMENTS VALUE 1.
: 1. 4 kV Emergency Bus undervoltage (Loss of Voltage)
4 kV Emergency Bus undervoltage (Loss of Voltage) a.
: a. Bus Undervoltage                           1         SR 3.3.8.1.3       NA SR 3.3.8.1.4
Bus Undervoltage 1
: 2. 4 kV Dergency Bus Undervoltage (Degraded Voltage Low Setting) l     a. Bus Undervoltage                           2         3R   3.3.8.1.1   t 2286 V and s 2706 V (1 per       SR   3.3.8.1.2 source)       SR 3.3.8.1.4
SR 3.3.8.1.3 NA SR 3.3.8.1.4 2.
: b. Time Delay                                 2         SR 3.3.8.1.1       t 1.5 seconds and (1 per       SR 3.3.8.1.2       s 2.1 seconds source)       SR 3.3.8.1.4
4 kV Dergency Bus Undervoltage (Degraded Voltage Low Setting) l a.
: 3. 4 kV Emergency Bus Undervoltage (Degraded Voltage High Setting) l     a. Bus Undervoltage                         2         SR 3.3.8.1.1       2 3409 V and 5 3829 Y (1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
Bus Undervoltage 2
: b. Time Delay                               2         SR 3.3.8.1.1       t 23.0 seconds and (1 per       SR 3.3.5.1.2       s 37.0 seconds source)       SR 3.3.8.1.4
3R 3.3.8.1.1 t 2286 V and s 2706 V (1 per SR 3.3.8.1.2 source)
: 4. 4 kV Emergency Bus Undervoltage (Degraded Voltage LOCA)
SR 3.3.8.1.4 b.
: a. Sus Undervoltage                         2         SR   3.3.8.1.1   e 3766 V and 5 3836 V (a)
Time Delay 2
(1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
SR 3.3.8.1.1 t 1.5 seconds and (1 per SR 3.3.8.1.2 s 2.1 seconds source)
: b. Time Delay                               2         SR 3.3.8.1.1       t 9.2 seconds and (1 per       SR 3.3.8.1.2       s 10.8 seconds (a) source)       SR 3.3.8.1.4
SR 3.3.8.1.4 3.
: 5. 4 kV Emergency Bus Undervoltage (Degraded Voltage ren-LOCA)
4 kV Emergency Bus Undervoltage (Degraded Voltage High Setting) l a.
: a. Bus undervoltage                           2         SR 3.3.8.1.1       2 4116 V and s 4186 V (a)
Bus Undervoltage 2
(1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
SR 3.3.8.1.1 2 3409 V and 5 3829 Y (1 per SR 3.3.8.1.2 source)
: b. Time Delay                               2         SR 3.3.8.1.1       a 57.8 seconds and 5 64.2 (1 per       SR 3.3.8.1.2       seconds (a) source)       SR 3.3.8.1.4 (a) Prior to the inplementation of modification 96-01511, the Allowable values of the Ftsictions below aret 4.a       a 3691 y and 5 3713 V, with internal time delay set t 0.9 seconds and 51.1 seconds, 4.b       t 8.4 seconds and s 9.6 seconds, 5.s       a 4065 V and s 4089 V, with internal time dels, .et t 0.9 seconds and s 1.1 seconds, 5.b       t 57.0 seconds and s 63.0 seconds.
SR 3.3.8.1.4 b.
PBAPS UNIT 3                                         3.3-65                           Amendment No.
Time Delay 2
  'i
SR 3.3.8.1.1 t 23.0 seconds and (1 per SR 3.3.5.1.2 s 37.0 seconds source)
SR 3.3.8.1.4 4.
4 kV Emergency Bus Undervoltage (Degraded Voltage LOCA) a.
Sus Undervoltage 2
SR 3.3.8.1.1 e 3766 V and 5 3836 V (a)
(1 per SR 3.3.8.1.2 source)
SR 3.3.8.1.4 b.
Time Delay 2
SR 3.3.8.1.1 t 9.2 seconds and (1 per SR 3.3.8.1.2 s 10.8 seconds (a) source)
SR 3.3.8.1.4 5.
4 kV Emergency Bus Undervoltage (Degraded Voltage ren-LOCA) a.
Bus undervoltage 2
SR 3.3.8.1.1 2 4116 V and s 4186 V (a)
(1 per SR 3.3.8.1.2 source)
SR 3.3.8.1.4 b.
Time Delay 2
SR 3.3.8.1.1 a 57.8 seconds and 5 64.2 (1 per SR 3.3.8.1.2 seconds (a) source)
SR 3.3.8.1.4 (a) Prior to the inplementation of modification 96-01511, the Allowable values of the Ftsictions below aret 4.a a 3691 y and 5 3713 V, with internal time delay set t 0.9 seconds and 51.1 seconds, 4.b t 8.4 seconds and s 9.6 seconds, 5.s a 4065 V and s 4089 V, with internal time dels,.et t 0.9 seconds and s 1.1 seconds, 5.b t 57.0 seconds and s 63.0 seconds.
PBAPS UNIT 3 3.3-65 Amendment No.
'i


    ~
~
  '                                                                LOP Instrumentation B 3.3.8.1 BASES (continued) l APPLICABLE       The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite LCO, and         power. The required channels of LOP instrumentation ensure APPLICABILITY     that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (UFSAR) analyzed accidents in which a loss of       i offsite power is assumed. The first level is loss of           l voltage. This loss of voltage level detects and disconnects the Class 1E buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid     i voltage relays which are set to detect a sustained low         !
LOP Instrumentation B 3.3.8.1 BASES (continued)
voltage condition. These degraded grid relays disconnect the Class 1E buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class IE equipment from achieving its safety function. The degraded grid relays also prevent the Class 1E equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss       !
APPLICABLE The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite LCO, and power. The required channels of LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (UFSAR) analyzed accidents in which a loss of i
of voltage relaying and the degraded grid relaying provides protection to the Class 1E distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite       ;
offsite power is assumed. The first level is loss of l
power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperaturc remains below the limits of 10 CFR 50.46.
voltage.
This loss of voltage level detects and disconnects the Class 1E buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid i
voltage relays which are set to detect a sustained low voltage condition. These degraded grid relays disconnect the Class 1E buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class IE equipment from achieving its safety function.
The degraded grid relays also prevent the Class 1E equipment from sustaining damage from prolonged operation at reduced voltage.
The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class 1E distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperaturc remains below the limits of 10 CFR 50.46.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.
The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1. Each Function must have a required number of OPERABLE channels per 4 kV emergency bus with their set)oints within the s)ecified Allowable Values except the aus undervoltage relay w11ch does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value. Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.     (Note:
The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.
Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Vaulues for the indicated
Each Function must have a required number of OPERABLE channels per 4 kV emergency bus with their set)oints within the s)ecified Allowable Values except the aus undervoltage relay w11ch does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value.
_                                          (continued)
Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.
PBAPS UNIT 3                       B 3.3-188                     Revision No.
(Note:
Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Vaulues for the indicated (continued)
PBAPS UNIT 3 B 3.3-188 Revision No.


LOP Instrumentation B 3.3.8.1 BASES APPLICABLE       functions remain at the previously approved values on a SAFETY ANALYSES, relay by relay basis.) The loss of voltage channel is LCO, and         inoperable if it will not start the diesel on a loss of APPLICABILITY   power to a 4 kV emergency bus.
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE functions remain at the previously approved values on a SAFETY ANALYSES, relay by relay basis.) The loss of voltage channel is LCO, and inoperable if it will not start the diesel on a loss of APPLICABILITY power to a 4 kV emergency bus.
(continued)
(continued)
The Allowable Values are specified for each applicable Function in the Table 3.3.8.1-1. The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value is acceptable. Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process   parameter output changes        exceeds state.        the setpoint, The Allowable  Va    lues were set equalthe pro to the limiting values determined by the voltage regulation calculation. The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, potential transformer accuracy, measuring and test equipment and includes a calibration leave alone             >
The Allowable Values are specified for each applicable Function in the Table 3.3.8.1-1.
accuracy zone.      margin IISCP me {hodology utilizes the square root of the sum of the squares ta combine random non-directional accuracy values. 11SCP then includes relay drift, calibration leave alone zones, and margins.           Table 3.3.8.1-1 contains a note that prior to the imple(Note:
The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value is acceptable.
mentation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The set                   l assumes a nominal 35/1 potential transformer ratio. point             i i
Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, lues were set equalthe pro output changes state. The Allowable Va to the limiting values determined by the voltage regulation calculation.
The specific Applicable Safety Analyses, LCO, and                     ,
The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, potential transformer accuracy, measuring and test equipment and includes a calibration leave alone accuracy margin {hodology utilizes the square root of the sum zone.
Applicability discussions for Unit 3 LOP instrumentation are         l listed below on a Function by Function basis.                         !
IISCP me of the squares ta combine random non-directional accuracy values.
i In addition, since some equipment required by Unit 3 is               l powered from Unit 2 sources, the Unit 2 LOP instrumentation           j sunorting the required sources must also be OPERABLE. The             :
11SCP then includes relay drift, calibration leave alone zones, and margins.
OP RABILITY requirements for the Unit 2 LOP instrumentation           i is the same as described in this section, except Function 4           !
Table 3.3.8.1-1 contains a note that prior to the imple(Note:
(4 kV Emergency is not required to beBus Undervoltage, OPERABLE         Degraded since         Voltage this Function is LOCA)ted rela to a LOCA on Unit 2 only. theUnit2instrumentationis listed in Unit 2 Table 3.3.8.1-1.
mentation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The set assumes a nominal 35/1 potential transformer ratio. point i
i The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 3 LOP instrumentation are l
listed below on a Function by Function basis.
i In addition, since some equipment required by Unit 3 is powered from Unit 2 sources, the Unit 2 LOP instrumentation j
sunorting the required sources must also be OPERABLE. The OP RABILITY requirements for the Unit 2 LOP instrumentation i
is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA)ted is not required to be OPERABLE since this Function is rela to a LOCA on Unit 2 only. theUnit2instrumentationis listed in Unit 2 Table 3.3.8.1-1.
: 1. 4 kV Emeraency Bus Undervoittae (Loss of Voltaae)
: 1. 4 kV Emeraency Bus Undervoittae (Loss of Voltaae)
When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the                   ,
When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient i
respective emergency bus is unable to supply sufficient               i power for proper operation of the a)plicable equipment.               q Therefore, the power supply to the aus is transferred from             ;
power for proper operation of the a)plicable equipment.
offsite power to DG power. This ensures that adequate power will be available to the required equipment.
q Therefore, the power supply to the aus is transferred from offsite power to DG power. This ensures that adequate power will be available to the required equipment.
                                                                            ~(continued)
~(continued)
PBAPS UNIT 3                       B 3.3-189                     Revision No.
PBAPS UNIT 3 B 3.3-189 Revision No.


LOP Instrumentation B 3.3.8.1 BASES I
LOP Instrumentation B 3.3.8.1 BASES I
APPLICABLE       1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)
APPLICABLE
          -SAFETY ANALYSIS,   (cont < nued)
: 1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)
LCO, and APPLICABILITY                                                                     Loss The       singleFunction  per associated channel       of 4 emergency     bus is on Bus kV Emergency              Und required     to circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.     (One channel inputs to each of the four DGs.         Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, )AC Sources-Shutdown," for Applicability Bases for the DGs.
-SAFETY ANALYSIS, (cont < nued)
: 2. 3. 4. 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaael A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be ins'ifficient for starting large ECCS motors without risking damage to the motors that could disable the ECCS function.
LCO, and APPLICABILITY The single channel of 4 kV Emergency Bus Und Loss Function per associated emergency bus is on required to circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop               ;
(One channel inputs to each of the four DGs.
below the Degraded Voltage Function Allowable Values                   !
Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, )AC Sources-Shutdown," for Applicability Bases for the DGs.
(degraded voltage with a time delay) and the source breakers           '
2.
trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
3.
Four Functions are provided to monitor degraded voltage at             ,
4.
four different levels. These-Functions are the Degraded                 i' Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the following voltage levels with the-following time delays: the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source volta e is                 l inverse time delay ; the       i reduced Function abruptly       to zero 3 relay, 3409    voltsvo(lts in approximate y 30
: 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaael A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be ins'ifficient for starting large ECCS motors without risking damage to the motors that could disable the ECCS function.
                                                          - 3829 seconds when source volta e is reduced abruptly to 2940 inverse time delay ; the Function 4 relay, 3766 -
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
volts   (lts in approximate y 10 seconds; and the Function 5 3836 vo                                                                 i relay, 4116 - 4186 volts in approximately 60 seconds.                   !
Four Functions are provided to monitor degraded voltage at four different levels. These-Functions are the Degraded i
(Note: Table 3.3.8.1-1 contains a note that prior to the               !
Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the following voltage levels with the-following time delays:
implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain-at the previously approved values on a relay by relay basis.) The Function 2 and 3 relays are inverse time delay relays. These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for
the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source volta e is i
                                                                                      'YEontinued)
inverse time delay ; the reduced abruptly to zero volts (lts in approximate y 30 Function 3 relay, 3409 - 3829 vo seconds when source volta e is reduced abruptly to 2940 inverse time delay ; the Function 4 relay, 3766 -
PBAPS UNIT 3                         B 3.3-190                       Revision No.
volts (lts in approximate y 10 seconds; and the Function 5 3836 vo i
relay, 4116 - 4186 volts in approximately 60 seconds.
(Note: Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain-at the previously approved values on a relay by relay basis.) The Function 2 and 3 relays are inverse time delay relays.
These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for
'YEontinued)
PBAPS UNIT 3 B 3.3-190 Revision No.
l
l


7.
7.
l ATTACHMENT 2 -
l ATTACHMENT 2 -
PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 l
PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 LICENSE CHANGE APPLICATION ECR 96-01511
License Nos. DPR-44 DPR-56 LICENSE CHANGE APPLICATION ECR 96-01511
" Final" Pages Unit 2 Unit 3 3.3-65 3.3-65 B 3.3-188 B 3.3-188 8 3.3-189 B 3.3-189 B 3.3-190 B 3.3-190
                                      " Final" Pages Unit 2                         Unit 3 3.3-65     .
' sky..
3.3-65 B 3.3-188                       B 3.3-188 8 3.3-189                     B 3.3-189   '
B 3.3-190                     B 3.3-190
  ' sky ..


LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)
LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)
Loss of Power Instrumentation REQUIRED CHANNELS       SURVE!LLANCE             ALLOWABLE FUNCTION                 PER BUS       REQUIREMENTS               VALUE
Loss of Power Instrumentation REQUIRED CHANNELS SURVE!LLANCE ALLOWABLE FUNCTION PER BUS REQUIREMENTS VALUE 1.
: 1. 4 kV Emergency Bus Undervoltage (Loss of Voltage)
4 kV Emergency Bus Undervoltage (Loss of Voltage) a.
: a. Sus Undervoltage                     1         SR 3.3.8.1.3   NA st 3.3.8.1.4
Sus Undervoltage 1
: 2. 4 kV Emergency Bus Undervoltage (Degraded Voltage Low setting) l         a. Bus undervottage                     2         SR 3.3.8.1.1   a 2286 V and 5 2706 V (1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4
SR 3.3.8.1.3 NA st 3.3.8.1.4 2.
: b. Time Delay                           2         sa 3.3.8.1.1   t 1.5 seconds and (1 per       SR 3.3.8.1.2   s 2.1 seconds source)       SR 3.3.8.1.4
4 kV Emergency Bus Undervoltage (Degraded Voltage Low setting) l a.
: 3. 4 kV Emergency Bus Undervoltage (Degraded Voltage High setting) l         a. Bus undervoltage                     2         SR 3.3.8.1.1   t 3409 V and s 3829 V       l (1 per       SR 3.3.8.1.2                               i source)       SR 3.3.8.1.4
Bus undervottage 2
: b. Time Delay                           2         SR 3.3.8.1.1   t 23.0 seconds and (1 per       SR 3.3.8.1.2   s 37.0 seconds source)       st 3.3.8.1.4 4 4 kV Emergency Bus Undervoltage (Degraded Voltage LOCA)
SR 3.3.8.1.1 a 2286 V and 5 2706 V (1 per SR 3.3.8.1.2 source)
                . a. Sus undervoltage                     2         SR 3.3.8.1.1   2 3766 y and 5 3836 V (1 per       SR   3.3.8.1.2-source)       SR 3.3.8.1.4 l
SR 3.3.8.1.4 b.
1
Time Delay 2
: b. Time Delay                           2         SR 3.3.8.1.1   t 9.2 seconds and           i (1 per       SR 3.3.8.1.2   s 10.8 seconds source)       SR 3.3.8.1.4
sa 3.3.8.1.1 t 1.5 seconds and (1 per SR 3.3.8.1.2 s 2.1 seconds source)
: 5. 4 kV Emergency sus Undervoltage (Degraded Voltage non-LOCA)
SR 3.3.8.1.4 3.
: 4. Bus undervoltage                     2         SR 3.3.8.1.1   2 4116 V and s 4186 V (1 per       SR 3.3.8.1.2 source)       SR 3.3.8.1.4 j
4 kV Emergency Bus Undervoltage (Degraded Voltage High setting) l a.
l l        b. Time Detey                           2         st 3.3.8.1.1   t 57.8 seconds and s 64.2   l (1 per       SR 3.3.8.1.2   seconds                     1 source)       SR 3.3.8.1.4 I
Bus undervoltage 2
l l
SR 3.3.8.1.1 t 3409 V and s 3829 V (1 per SR 3.3.8.1.2 i
l PBAPS UNIT 2                                       3.3-65                         Amendment No.
source)
l II
SR 3.3.8.1.4 b.
Time Delay 2
SR 3.3.8.1.1 t 23.0 seconds and (1 per SR 3.3.8.1.2 s 37.0 seconds source) st 3.3.8.1.4 4 4 kV Emergency Bus Undervoltage (Degraded Voltage LOCA)
. a.
Sus undervoltage 2
SR 3.3.8.1.1 2 3766 y and 5 3836 V (1 per SR 3.3.8.1.2-source)
SR 3.3.8.1.4 l
1 b.
Time Delay 2
SR 3.3.8.1.1 t 9.2 seconds and i
(1 per SR 3.3.8.1.2 s 10.8 seconds source)
SR 3.3.8.1.4 5.
4 kV Emergency sus Undervoltage (Degraded Voltage non-LOCA) 4.
Bus undervoltage 2
SR 3.3.8.1.1 2 4116 V and s 4186 V (1 per SR 3.3.8.1.2 source)
SR 3.3.8.1.4 j
l b.
Time Detey 2
st 3.3.8.1.1 t 57.8 seconds and s 64.2 (1 per SR 3.3.8.1.2 seconds 1
source)
SR 3.3.8.1.4 I
l PBAPS UNIT 2 3.3-65 Amendment No.
I


l LOP Instrumentation B 3.3.8.1 BASES (continued) i APPLICABLE       The LOP instrumentation is required for Engineered Safety         i SAFETY ANALYSES, Features to function in any accident with a loss of offsite       j LCO, and         power. The required channels of LOP instrumentation ensure         i APPLICABILITY     that the ECCS and other assumed systems powered from the           !
LOP Instrumentation B 3.3.8.1 BASES (continued) i APPLICABLE The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite j
DGs, provide plant protection in the event of any of the         i Reference 1 (UFSAR) analyzed accidents in which a loss of         j offsite power is assumed. The first level is loss of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition. These degraded grid relays disconnect the Class 1E buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class 1E equipment from achieving its safety function. The degraded grid relays also prevent the Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss       , ,
LCO, and power. The required channels of LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (UFSAR) analyzed accidents in which a loss of j
of voltage relaying and the degraded grid relaying provides       I protection to the Class 1E distribution systea for all           ;
offsite power is assumed. The first level is loss of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition.
credible conditions of voltage collapse or sustained voltage     !
These degraded grid relays disconnect the Class 1E buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class 1E equipment from achieving its safety function. The degraded grid relays also prevent the Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class 1E distribution systea for all credible conditions of voltage collapse or sustained voltage degradation.
degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.
The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.
The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
The OPERABILITY of the LOP instrthnentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1. Each Function must have a required number of OPERABLE channels per 4 kV emergency bus, with their setpoints within the specified Allowable Values except the bus undervoltage relay which does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value. Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.
The OPERABILITY of the LOP instrthnentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.
                                                                            -(continued)
Each Function must have a required number of OPERABLE channels per 4 kV emergency bus, with their setpoints within the specified Allowable Values except the bus undervoltage relay which does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value.
PBAPS UNIT 2                       B 3.3-188                     Revision No.
Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.
-(continued)
PBAPS UNIT 2 B 3.3-188 Revision No.


LOP Instrumentation B 3.3.8.1 BASES,                                                                             I i
LOP Instrumentation B 3.3.8.1
APPLICABLE         The loss of voltage channel is inoperable if it will not SAFETY ANALYSES, start the diesel on a loss.of power to a 4 kV emergency bus.
: BASES, i
APPLICABLE The loss of voltage channel is inoperable if it will not SAFETY ANALYSES, start the diesel on a loss.of power to a 4 kV emergency bus.
LCO, and
LCO, and
              --APPLICABILITY     The Allowable Values are specified for _each applicable (continued)_   Function in the Table 3.3.8.1-1. The nominal setpoints are selected to ensure that the setpoints do not exceed the
--APPLICABILITY The Allowable Values are specified for _each applicable (continued)_
                                ' Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value, is     .
Function in the Table 3.3.8.1-1.
acceptable. Trip setpoints are those predetermined values of output at which'an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the. limiting values determined by the voltage regulation
The nominal setpoints are selected to ensure that the setpoints do not exceed the
                                - calculation. The setpoints were corrected using IISCP           ;
' Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value, is acceptable. Trip setpoints are those predetermined values of output at which'an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the. limiting values determined by the voltage regulation
methodology to account for relay drift, relay accuracy,           j potential transformer accuracy, measuring and test equipment     u accuracy margin, and includes a calibration leave alone zone. IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values. IISCP then includes relay drift, calibration leave.
- calculation.
alone zones,'and margins. The setpoint assumes a nominal 35/1 potential transformer ratio.                                 !
The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, j
i The specific Applicable Safety Analyses, LCO, and                 j
potential transformer accuracy, measuring and test equipment u
                                , Applicability discussions for Unit 2 LOP instrumentation are     ;
accuracy margin, and includes a calibration leave alone zone.
listed below on a Function by Function' basis.
IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values.
In addition, since some equipment required by Unit 2 is powered from Unit 3 sources, .the Unit 3 LOP instrumentation     ;
IISCP then includes relay drift, calibration leave.
supporting ~ the required sources must also be OPERABLE. The     !
alone zones,'and margins. The setpoint assumes a nominal 35/1 potential transformer ratio.
OPERABILITY requirements for the Unit 3 LOP instrumentation       '
i The specific Applicable Safety Analyses, LCO, and j
is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA) is not required to be OPERABLE, since this Function is related
, Applicability discussions for Unit 2 LOP instrumentation are listed below on a Function by Function' basis.
                                -to a LOCA on Unit 3 only. The Unit 3 instrumentation is listed in Unit 3 Table 3.3.8.1-1.
In addition, since some equipment required by Unit 2 is powered from Unit 3 sources,.the Unit 3 LOP instrumentation supporting ~ the required sources must also be OPERABLE. The OPERABILITY requirements for the Unit 3 LOP instrumentation is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA) is not required to be OPERABLE, since this Function is related
: 1. 4 kV Emeroency Bus Undervoltaae (Loss of Voltaael When both offsite sources are lost, a loss of voltage condition on aL4 kV emergency bus indicates:that.the             j respective emergency bus is unable to supply sufficient
-to a LOCA on Unit 3 only. The Unit 3 instrumentation is listed in Unit 3 Table 3.3.8.1-1.
                                                                                                    ~
: 1. 4 kV Emeroency Bus Undervoltaae (Loss of Voltaael When both offsite sources are lost, a loss of voltage condition on aL4 kV emergency bus indicates:that.the j
respective emergency bus is unable to supply sufficient
~
power for proper operation of the applicable. equipment.
power for proper operation of the applicable. equipment.
Therefore, the power supply to the bus is transferred from offsite power to DG power. This ensures'that adequate power will be available to the required equipment.
Therefore, the power supply to the bus is transferred from offsite power to DG power. This ensures'that adequate power will be available to the required equipment.
                                                                                    -(continued)
-(continued)
PBAPS' UNIT 2                       B 3.3-159                     Revision No.
PBAPS' UNIT 2 B 3.3-159 Revision No.
V                           I
V I


LOP Instrumentation B 3.3.8.1 BASES APPLICABLE       1. 4 kV 'Emeroency Bus Undervoltaae (Loss of Voltaae)
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE
SAFETY ANALYSIS,   (continued)
: 1. 4 kV 'Emeroency Bus Undervoltaae (Loss of Voltaae)
LCO, and APPLICABILITY = The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function per associated emergency bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.   (One channel inputs to each of the four DGs.) Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, "AC Sources-Shutdown," for Applicability Bases for the DGs.
SAFETY ANALYSIS, (continued)
: 2. 3. 4. 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)
LCO, and APPLICABILITY =
The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function per associated emergency bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.
(One channel inputs to each of the four DGs.) Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, "AC Sources-Shutdown," for Applicability Bases for the DGs.
2.
3.
4.
: 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)
A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large-ECCS motors without risking damage to the motors that cou'd disable the ECCS function.
A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large-ECCS motors without risking damage to the motors that cou'd disable the ECCS function.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the~ Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which_causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the~ Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which_causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and D%raded Voltage Low Setting. These relays _ monitor the following voltage levels with the         l following time delays: the Function 2 relay, 2286 - 2706 volts in approximately 2 seca ds when source voltage is reduced abruptly to zero volts (inverse time delay); the Function 3 relay, 3409 - 3829 volts in approximately 30 seconds when source voltage is reduced abruptly to 2940 volts (inverse time delay); the Function 4 relay, 3766 -
Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and D%raded Voltage Low Setting. These relays _ monitor the following voltage levels with the following time delays: the Function 2 relay, 2286 - 2706 volts in approximately 2 seca ds when source voltage is reduced abruptly to zero volts (inverse time delay); the Function 3 relay, 3409 - 3829 volts in approximately 30 seconds when source voltage is reduced abruptly to 2940 volts (inverse time delay); the Function 4 relay, 3766 -
3836 volts in approximately 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds. The Function 2 and 3 relays are inverse time delay relays.         1 These relays operate along a repeatable characteristic         i curve. With relay operation being inverse with time, for (continued)
3836 volts in approximately 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds. The Function 2 and 3 relays are inverse time delay relays.
PBAPS UNIT 2                       B 3.3-190                   Revision No.
1 These relays operate along a repeatable characteristic i
curve. With relay operation being inverse with time, for (continued)
PBAPS UNIT 2 B 3.3-190 Revision No.


c                     '
c LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1',
LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1',
Loss of Power Instrumentation am REQUIRED CHANNELS
Loss of Power Instrumentation am                                                   -
$URVEILLANCE ALLOWABLE FUNCTION PER Bus REQUIREMENTS VALUE 1.
REQUIRED CHANNELS       $URVEILLANCE             ALLOWABLE FUNCTION                 PER Bus       REQUIREMENTS               VALUE
4 kV Emergency Bus Undervoltage (Loss of Voltage) a.
: 1. 4 kV Emergency Bus Undervoltage (Loss of Voltage)
Bus Undervoltage 1
: a. Bus Undervoltage                     1         SR 3.3.5.1.3   NA
SR 3.3.5.1.3 NA
                                                                        $R 3.3.8.1.4
$R 3.3.8.1.4 2.
: 2. 4 kV Emergency Bus undervoltage (Degraded Voltage Low setting) l     a. Bus Undervoltage                     2         SR 3.3.8.1.1   t 2286 y and s 2706 V (1 per       sR 3.3.8.1.2 source)       SR 3.3.8.1.4
4 kV Emergency Bus undervoltage (Degraded Voltage Low setting) l a.
: b. Time Delay                           2         rA 3.3.8.1.1   a 1.5 seconds and (1 per       SR 3.3.8.1.2   5 2.1 seconds source)       sR 3.3.8.1.4
Bus Undervoltage 2
: 3. 4 kV Emergency Bus Undervoltage (Degraded Voltage High setting) l     a. Bus Undervoltage                     2         sR 3.3.8.1.1   a 34D9 Y and 5 3829 Y (1 per       SR 3.3.8.1.2 source)       sR 3.3.8.1.4
SR 3.3.8.1.1 t 2286 y and s 2706 V (1 per sR 3.3.8.1.2 source)
: b. Time Delay                           2         SR 3.3.8.1.1   a 23.0 seconds and (1 per       SR 3.3.8.1.2   s 37.0 seconds source)       $R 3.3.8.1.4
SR 3.3.8.1.4 b.
: 4. 4 kW Emergency Bus undervoltage (Degraded Voltage LOCA)
Time Delay 2
: a. Bus Undervoltage                     2         SR 3.3.8.1.1   2 3766 y and 5 3836 V (1 per       SR 3.3.8.1.2 source)       sR 3.3.8.1.4
rA 3.3.8.1.1 a 1.5 seconds and (1 per SR 3.3.8.1.2 5 2.1 seconds source) sR 3.3.8.1.4 3.
: b. Time Delay                           2         SR 3.3.8.1.1   e 9.2 seconds and             l (1 per       SR 3.3.8.1.2   s 10.8 seconds source)       sR 3.3.8.1.4                                 l
4 kV Emergency Bus Undervoltage (Degraded Voltage High setting) l a.
: 5. 4 kV Emergency Bus Undervoltage (Degraded Voltage non LOCA)
Bus Undervoltage 2
: a. Bus Undervoltage                     2         st 3.3.8.1.1   t 4116 V and 5 4186 Y (1 per       SR 3.3.8.1.2 source)       st 3.3.8.1.4 l     b. Time Delay                           2         sR 3.3.8.1.1   t 57.8 seconds and s 64.2 (1 per       SR 3.3.8.1.2   seconds source)       sR 3.3.8.1.4
sR 3.3.8.1.1 a 34D9 Y and 5 3829 Y (1 per SR 3.3.8.1.2 source) sR 3.3.8.1.4 b.
                                                                                                                      )
Time Delay 2
__              )
SR 3.3.8.1.1 a 23.0 seconds and (1 per SR 3.3.8.1.2 s 37.0 seconds source)
PBAPS UNIT 3                                     3.3-65                         Amendment No.           !
$R 3.3.8.1.4 4.
I l
4 kW Emergency Bus undervoltage (Degraded Voltage LOCA) a.
1
Bus Undervoltage 2
SR 3.3.8.1.1 2 3766 y and 5 3836 V (1 per SR 3.3.8.1.2 source) sR 3.3.8.1.4 b.
Time Delay 2
SR 3.3.8.1.1 e 9.2 seconds and l
(1 per SR 3.3.8.1.2 s 10.8 seconds source) sR 3.3.8.1.4 l
5.
4 kV Emergency Bus Undervoltage (Degraded Voltage non LOCA) a.
Bus Undervoltage 2
st 3.3.8.1.1 t 4116 V and 5 4186 Y (1 per SR 3.3.8.1.2 source) st 3.3.8.1.4 l
b.
Time Delay 2
sR 3.3.8.1.1 t 57.8 seconds and s 64.2 (1 per SR 3.3.8.1.2 seconds source) sR 3.3.8.1.4
)
)
PBAPS UNIT 3 3.3-65 Amendment No.
l 1


    ,                                                                LOP Instrumentation B 3.3.8.1 BASES (continued)
LOP Instrumentation B 3.3.8.1 BASES (continued)
APPLICABLE       The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite LCO, and         power. The required channels of LOP instrumentation ensure APPLICABILITY     that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (VFSAR) analyzed accidents in which a loss of offsite power is assumed. The first level is los. of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite powar source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low           !
APPLICABLE The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite LCO, and power.
voltage condition. These degraded grid relays disconnect         i the Class IE buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class IE equipment from achieving its safety function. The degraded grid relays also prevent the       l Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class IE distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.
The required channels of LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (VFSAR) analyzed accidents in which a loss of offsite power is assumed. The first level is los. of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite powar source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition.
These degraded grid relays disconnect the Class IE buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class IE equipment from achieving its safety function. The degraded grid relays also prevent the l
Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class IE distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.
The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.                                                           ,
The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.
The LOP instrumentation satisfies Criterion 3 of the NRC         ;
The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.
Policy Statement.
The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.
The OPERABILITY of the LOP instrumentation is dependent upon     l the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1. Each Function must have a required number of OPERABLE channels per 4 kV emergency bus, with their setpoints within the specified Allowable Values except the bus undervoltage relay which does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value. Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.
Each Function must have a required number of OPERABLE channels per 4 kV emergency bus, with their setpoints within the specified Allowable Values except the bus undervoltage relay which does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value.
                                                                              -(continued)
Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.
PBAPS UNIT 3                       8 3.3-188                     Revision No.
-(continued)
PBAPS UNIT 3 8 3.3-188 Revision No.
t
t


LOP Instrumentation B 3.3.8.1 BASES APPLICABLE       The loss of voltage channel is inoperable if it will not SAFETY ANALYSES, start the diesel on a loss of power to a 4 kV emergency bus.
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE The loss of voltage channel is inoperable if it will not SAFETY ANALYSES, start the diesel on a loss of power to a 4 kV emergency bus.
LCO, and APPLICABILITY   The Allowable Values are specified for each applicable (continued)   Function in the Table 3.3.8.1-1. The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value, is acceptable. Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the limiting values determined by the voltage regulation calculation. The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, potential transformer accuracy, measuring and test equipment accuracy margin, and includes a calibration leave alone zone. IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values. IISCP then includes relay drift, calibration leave     )
LCO, and APPLICABILITY The Allowable Values are specified for each applicable (continued)
alone zones, and margins. The setpoint assumes a nominal       1 35/1-potential transformer ratio.
Function in the Table 3.3.8.1-1.
The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 3 LOP instrumentation are   i listed below on a Function by function basis.                   I In addition, since some equipment required by Unit 3 is powered from Unit 2 sources, the Unit 2 LOP instrumentation     l supporting the required sources must also be OPERABLE. The     j OPERABILITY requirements for the Unit 2 LOP instrumentation     )
The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value, is acceptable. Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the limiting values determined by the voltage regulation calculation. The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, potential transformer accuracy, measuring and test equipment accuracy margin, and includes a calibration leave alone zone.
is the same as described in this section, except Function 4     )
IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values.
(4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA) is     4 not required to be OPERABLE, since this Function is related to a LOCA on Unit 2 only. The Unit 2 instrumentation is         .
IISCP then includes relay drift, calibration leave
listed in Unit 2 Table 3.3.8.1-1.                               !
)
alone zones, and margins. The setpoint assumes a nominal 35/1-potential transformer ratio.
The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 3 LOP instrumentation are i
listed below on a Function by function basis.
In addition, since some equipment required by Unit 3 is powered from Unit 2 sources, the Unit 2 LOP instrumentation supporting the required sources must also be OPERABLE. The j
OPERABILITY requirements for the Unit 2 LOP instrumentation
)
is the same as described in this section, except Function 4
)
(4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA) is 4
not required to be OPERABLE, since this Function is related to a LOCA on Unit 2 only. The Unit 2 instrumentation is listed in Unit 2 Table 3.3.8.1-1.
: 1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltagg1 When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient power for proper operation of the applicable equipment.
: 1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltagg1 When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient power for proper operation of the applicable equipment.
Therefore, the power supply to the bus is transferred from offsite power to DG power. This ensures that adequate power will be available to the required equipment.
Therefore, the power supply to the bus is transferred from offsite power to DG power. This ensures that adequate power will be available to the required equipment.
                                                                              .(continued)
.(continued)
PBAPS-UNIT'3                       8 3.3-189                     Revision No.
PBAPS-UNIT'3 8 3.3-189 Revision No.
  't
't


h i     '
h i
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE       1. 4 kV Emercency Bus Undervoltaae (Loss of Voltagg),
LOP Instrumentation B 3.3.8.1 BASES APPLICABLE
SAFETY ANALYSIS,   (continued)
: 1. 4 kV Emercency Bus Undervoltaae (Loss of Voltagg),
LCO, and APPLICABILITY   The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function per associated emergency bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.   (One channel inputs to each of the four DGs.) Refer to LCO 3.8.1, "AC- Sources -Operating," and 3.8.2, "AC Sources-Shutdown," for Applicability Bases for the DGs.
SAFETY ANALYSIS, (continued)
: 2. 3. 4. 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)
LCO, and APPLICABILITY The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function per associated emergency bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE.
This ensures no single instrument failure can preclude the start of three of four DGs.
(One channel inputs to each of the four DGs.) Refer to LCO 3.8.1, "AC-Sources -Operating," and 3.8.2, "AC Sources-Shutdown," for Applicability Bases for the DGs.
2.
3.
4.
: 5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)
A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large ECCS motors without risking damage to the motors that could disable the ECCS function.
A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large ECCS motors without risking damage to the motors that could disable the ECCS function.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.
Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the following voltage levels with the following time delays: the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source voltage is reduced abruptly to zero volts (inverse time delay); the Function 3 relay, 3409 - 3829 volts in approximately 30 seconds when source voltage is reduced abruptly to 2940 volts (inverse time delay); the Function 4 relay, 3766 -
Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the following voltage levels with the following time delays:
the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source voltage is reduced abruptly to zero volts (inverse time delay); the Function 3 relay, 3409 - 3829 volts in approximately 30 seconds when source voltage is reduced abruptly to 2940 volts (inverse time delay); the Function 4 relay, 3766 -
3836 volts in approximately 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds. The Function 2 and 3 relays are inverse time delay relays.
3836 volts in approximately 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds. The Function 2 and 3 relays are inverse time delay relays.
These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for
These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for
                                                                            -(continued)
-(continued)
PBAPS UNIT 3                       8 3.3-190                   Revision No.
PBAPS UNIT 3 8 3.3-190 Revision No.
  -}}
-}}

Latest revision as of 19:58, 10 December 2024

Proposed Final Tech Specs Pages for License Change Application ECR 96-01511 Re Rev to Loss of Power Setpoints for 4 Kv Emergency Buses
ML20195B827
Person / Time
Site: Peach Bottom  
Issue date: 05/25/1999
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20195B822 List:
References
NUDOCS 9906030115
Download: ML20195B827 (18)


Text

7

}c l

l ATTACHMENT 1 PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 LICENSE CHANGE APPLICATION ECR 96-01511 ~

" Interim" Pages j

i Unit 2 Unit 3 3.3 3.3-65 8 3.3-188-B 3.3-188 B 3.3-189 8 3.3-189 i

B 3.3-190 B 3.3-190 9906030115 990525

~

PDR ADOCK 05000277 P

PDR L

LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)

Loss of Power Instrumentation REQUIRED CHANNELS SURVE!LLANCE ALLOWABLE FUNCTION PER BUS REQUIREMENTS VALUE 1.

4 kV Emergency sus Undervoltage (Loss of Voltage) a.

Bus undervoltage 1

SR 3.3.8.1.3 NA SR 3.3.8.1.4 2.

4 kV Emergency Bus Undervoltage (Degraded Voltage Low Setting) l~

a.

Bus Undervoltage 2

SR 3.3.8.1.1 t 2286 V and s 2706 V (1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 t 1.5 seconds and (1 per SR 3.3.8.1.2 s 2.1 seconds source)

- SR 3.3.8.1.4 3.

4 kV Emergency Bus Undervoltage (Degraded Voltage High Setting) l a.

Bus Undervoltage 2

SR 3.3.8.1.1 2 3409 Y and 5 3829 V (1 per SR 3.3.8.1.2 tource)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 4 23.0 seconds and (1 per SR. 3.3.8.1.2 s 37.0 seconds source)

SR 3.3.8.1.4

-4 4 kV Emergency Bus undervoltage (Degraded Voltage LOCA)

. a.' Bus Undervoltage 2

SR 3.3.8.1.1 2 3766 V and 5 3836 V (a)

(1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 t 9.2 seconds and (1 per SR 3.3.8.1.2 5 10.8 seconds (a) source)

SR 3.3.8.1.4 5.

4 kV Emergency Bus Undervoltage (Degraded Voltage non-LOCA) a.

Bus Undervoltage-2 SR 3.3.8.1.1 2 4116 Y and s 4186 V (a)

(1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.5.1.1 a 57.8 seconds and 5 64.2 (1 per SR 3.3.8.1.2 seconds (a) source)

SR 3.3.8.1.4 (a) Prior.to the laplementation of modification 96 01511, the Allowable Values of the Functions below are:

4.s a 3691 V and 5 3713 V, with internal time delay set t 0.9 seconds and 51.1 seconds, 4.b t 8.4 seconds and s 9.6 seconds, 5.a a 4065 y and s 4089 V, with internal time delay' set t 0.9 seconds and 51.1 seconds,

~ ~ '

5.b t 57.0 seconds and s 63.0 seconds.

l PBAPS UNIT 2 3.3-65 Amendment No.

. ~.

LOP Instrumentation B 3.3.8.1 BASES (continued)

' APPLICABLE The LOP instrumentation is required for Engineered Safety

~ SAFETY ANALYSES, - Features to function in any accident with a loss of offsite LC0, and power. The required channels of. LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the i

Reference 1 (UFSAR) analyzed accidents in which a loss of offsite power is assumed. The first level is loss of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition. These degraded grid relays disconnect i

the Class IE buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class 1E equipment from achieving its safety function. The degraded grid relays also prevent the Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class IE distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that

' the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.

Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.

l The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite i

power.

The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.

The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.

Each Function must have-a required number of OPERABLE channels per 4 kV emergency bus with their setpoints within the j

specified Allowable Values except the bus undervoltage relay which does not have an Allowable.Value. A degraded voltage l

channel is inoperable if its actual trip setpoint is not

' within its required Allowable Value.

Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.

(Note-Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage

[

and timer trip setpoint Allowable Vaulues for the indicated l

Sontinued)

I' PBAPS UNIT 2 B 3.3-188 Revision No.

a i

c.

LOP Instrumentation B 3.3.8.1 BASES APPLICABLE functions remain at the previously approved values on a SAFETY ANALYSES, relay by relay basis.) The loss of voltage channel is LCO and inoperable if it will not start the diesel on a loss of APPL.ICABILITY power to a 4 kV emergency bus.

(continued)

The Allowable Values are specified for each applicable-Function in the Table 3.3.8.1-1.

The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. O with a trip setpoint within the Allowable Value,peration is acceptable. Trip setpoints are those predetermined values of output at which an action should take place.

The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state.

The Allowable Values were set equal to the limiting values determined by the voltage regulation calculation.

The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy potentialtransformeraccuracy,measuringandtestequIpment accuracy margin, and includes a calibration leave alone zone.

IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values.

IISCP then includes relay drift, calibration leave alone zones, and margins.

Note: Table 3.3.8.1-1 contains a note that prior to the imple(mentation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The set assumes a nominal 35/1 potential transformer ratio. point The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 2 LOP instrumentation are listed below on a function by Function basis.

In addition, since some equi powered from Unit 3 sources,pment required by Unit 2 is the Unit 3 LOP in'strumentation supporting the required sources must also be OPERABLE.

The OPERABILITY requirements for the Unit 3 LOP instrumentation is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA)ted is not required to be OPERABLE since this Function is rela to a LOCA on Unit 3 only. theUnit3instrumentationis listed in Unit 3 Table 3.3.8.1-1.

1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)

When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient power for Therefore, proper operation of the applicable equipment.

the power suppl offsite power to DG power.y to the bus is transferred fromThis ensures that will be available to the required equipment.

-(continued)

PBAPS UNIT 2 B 3.3-189 Revision No.

4 LOP Instrumentation

~

B 3.3.8.1 BASES APPLICABLE

1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)

SAFETY ANALYSIS, (continued)

LCC. and 1

APFLICABILITY The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function )er associated emeregncy bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.

(One channel inputs to each of the four DGs.

Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, }AC Sources-Shutdown," for Applicability Bases for the DGs.

2.

3.

4.

5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)

A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large ECCS motors without risking damage to the motors that could disabia the ECCS function.

Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus.

This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.

Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded "oltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the followiny voltage levels with the following time delays:

the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source volta e is reduced abruptly tb _ero volts (lts in c) proximate y 30 inverse time delay ; the Function 3 relay, 3409 - 3829 vo seconds when source volta e is reduced aaruptly to 2940 volts (lts in approximate y 10 seconds; and the Function 5 inverse time delay ; the Function 4 relay, 3766 -

3836 vo relay, 4116 - 4186 volts in approximately 60 seconds.

(Note: Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The Function 2 and 3 relays are inverse time delay relays. These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for Tc.ontinued)

PBAPS UNIT 2 B 3.3-190 Revision No.

~

LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)

Loss of Power Instrtmentation REQUIRED CHANNELS SURVEILLANCE ALLOW 48LE FUNCTION PER SUS REQUIREMENTS VALUE 1.

4 kV Emergency Bus undervoltage (Loss of Voltage) a.

Bus Undervoltage 1

SR 3.3.8.1.3 NA SR 3.3.8.1.4 2.

4 kV Dergency Bus Undervoltage (Degraded Voltage Low Setting) l a.

Bus Undervoltage 2

3R 3.3.8.1.1 t 2286 V and s 2706 V (1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 t 1.5 seconds and (1 per SR 3.3.8.1.2 s 2.1 seconds source)

SR 3.3.8.1.4 3.

4 kV Emergency Bus Undervoltage (Degraded Voltage High Setting) l a.

Bus Undervoltage 2

SR 3.3.8.1.1 2 3409 V and 5 3829 Y (1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 t 23.0 seconds and (1 per SR 3.3.5.1.2 s 37.0 seconds source)

SR 3.3.8.1.4 4.

4 kV Emergency Bus Undervoltage (Degraded Voltage LOCA) a.

Sus Undervoltage 2

SR 3.3.8.1.1 e 3766 V and 5 3836 V (a)

(1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 t 9.2 seconds and (1 per SR 3.3.8.1.2 s 10.8 seconds (a) source)

SR 3.3.8.1.4 5.

4 kV Emergency Bus Undervoltage (Degraded Voltage ren-LOCA) a.

Bus undervoltage 2

SR 3.3.8.1.1 2 4116 V and s 4186 V (a)

(1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 a 57.8 seconds and 5 64.2 (1 per SR 3.3.8.1.2 seconds (a) source)

SR 3.3.8.1.4 (a) Prior to the inplementation of modification 96-01511, the Allowable values of the Ftsictions below aret 4.a a 3691 y and 5 3713 V, with internal time delay set t 0.9 seconds and 51.1 seconds, 4.b t 8.4 seconds and s 9.6 seconds, 5.s a 4065 V and s 4089 V, with internal time dels,.et t 0.9 seconds and s 1.1 seconds, 5.b t 57.0 seconds and s 63.0 seconds.

PBAPS UNIT 3 3.3-65 Amendment No.

'i

~

LOP Instrumentation B 3.3.8.1 BASES (continued)

APPLICABLE The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite LCO, and power. The required channels of LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (UFSAR) analyzed accidents in which a loss of i

offsite power is assumed. The first level is loss of l

voltage.

This loss of voltage level detects and disconnects the Class 1E buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid i

voltage relays which are set to detect a sustained low voltage condition. These degraded grid relays disconnect the Class 1E buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class IE equipment from achieving its safety function.

The degraded grid relays also prevent the Class 1E equipment from sustaining damage from prolonged operation at reduced voltage.

The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class 1E distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperaturc remains below the limits of 10 CFR 50.46.

Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.

The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.

The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.

The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.

Each Function must have a required number of OPERABLE channels per 4 kV emergency bus with their set)oints within the s)ecified Allowable Values except the aus undervoltage relay w11ch does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value.

Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.

(Note:

Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Vaulues for the indicated (continued)

PBAPS UNIT 3 B 3.3-188 Revision No.

LOP Instrumentation B 3.3.8.1 BASES APPLICABLE functions remain at the previously approved values on a SAFETY ANALYSES, relay by relay basis.) The loss of voltage channel is LCO, and inoperable if it will not start the diesel on a loss of APPLICABILITY power to a 4 kV emergency bus.

(continued)

The Allowable Values are specified for each applicable Function in the Table 3.3.8.1-1.

The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value is acceptable.

Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, lues were set equalthe pro output changes state. The Allowable Va to the limiting values determined by the voltage regulation calculation.

The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, potential transformer accuracy, measuring and test equipment and includes a calibration leave alone accuracy margin {hodology utilizes the square root of the sum zone.

IISCP me of the squares ta combine random non-directional accuracy values.

11SCP then includes relay drift, calibration leave alone zones, and margins.

Table 3.3.8.1-1 contains a note that prior to the imple(Note:

mentation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain at the previously approved values on a relay by relay basis.) The set assumes a nominal 35/1 potential transformer ratio. point i

i The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 3 LOP instrumentation are l

listed below on a Function by Function basis.

i In addition, since some equipment required by Unit 3 is powered from Unit 2 sources, the Unit 2 LOP instrumentation j

sunorting the required sources must also be OPERABLE. The OP RABILITY requirements for the Unit 2 LOP instrumentation i

is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA)ted is not required to be OPERABLE since this Function is rela to a LOCA on Unit 2 only. theUnit2instrumentationis listed in Unit 2 Table 3.3.8.1-1.

1. 4 kV Emeraency Bus Undervoittae (Loss of Voltaae)

When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient i

power for proper operation of the a)plicable equipment.

q Therefore, the power supply to the aus is transferred from offsite power to DG power. This ensures that adequate power will be available to the required equipment.

~(continued)

PBAPS UNIT 3 B 3.3-189 Revision No.

LOP Instrumentation B 3.3.8.1 BASES I

APPLICABLE

1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltaae)

-SAFETY ANALYSIS, (cont < nued)

LCO, and APPLICABILITY The single channel of 4 kV Emergency Bus Und Loss Function per associated emergency bus is on required to circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.

(One channel inputs to each of the four DGs.

Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, )AC Sources-Shutdown," for Applicability Bases for the DGs.

2.

3.

4.

5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaael A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be ins'ifficient for starting large ECCS motors without risking damage to the motors that could disable the ECCS function.

Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.

Four Functions are provided to monitor degraded voltage at four different levels. These-Functions are the Degraded i

Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the following voltage levels with the-following time delays:

the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source volta e is i

inverse time delay ; the reduced abruptly to zero volts (lts in approximate y 30 Function 3 relay, 3409 - 3829 vo seconds when source volta e is reduced abruptly to 2940 inverse time delay ; the Function 4 relay, 3766 -

volts (lts in approximate y 10 seconds; and the Function 5 3836 vo i

relay, 4116 - 4186 volts in approximately 60 seconds.

(Note: Table 3.3.8.1-1 contains a note that prior to the implementation of modification 96-01511, the relay voltage and timer trip setpoint Allowable Values for the indicated functions remain-at the previously approved values on a relay by relay basis.) The Function 2 and 3 relays are inverse time delay relays.

These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for

'YEontinued)

PBAPS UNIT 3 B 3.3-190 Revision No.

l

7.

l ATTACHMENT 2 -

PEACH BOTTOM ATOMIC POWER STATION UNITS 2 AND 3 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 LICENSE CHANGE APPLICATION ECR 96-01511

" Final" Pages Unit 2 Unit 3 3.3-65 3.3-65 B 3.3-188 B 3.3-188 8 3.3-189 B 3.3-189 B 3.3-190 B 3.3-190

' sky..

LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1)

Loss of Power Instrumentation REQUIRED CHANNELS SURVE!LLANCE ALLOWABLE FUNCTION PER BUS REQUIREMENTS VALUE 1.

4 kV Emergency Bus Undervoltage (Loss of Voltage) a.

Sus Undervoltage 1

SR 3.3.8.1.3 NA st 3.3.8.1.4 2.

4 kV Emergency Bus Undervoltage (Degraded Voltage Low setting) l a.

Bus undervottage 2

SR 3.3.8.1.1 a 2286 V and 5 2706 V (1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

sa 3.3.8.1.1 t 1.5 seconds and (1 per SR 3.3.8.1.2 s 2.1 seconds source)

SR 3.3.8.1.4 3.

4 kV Emergency Bus Undervoltage (Degraded Voltage High setting) l a.

Bus undervoltage 2

SR 3.3.8.1.1 t 3409 V and s 3829 V (1 per SR 3.3.8.1.2 i

source)

SR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 t 23.0 seconds and (1 per SR 3.3.8.1.2 s 37.0 seconds source) st 3.3.8.1.4 4 4 kV Emergency Bus Undervoltage (Degraded Voltage LOCA)

. a.

Sus undervoltage 2

SR 3.3.8.1.1 2 3766 y and 5 3836 V (1 per SR 3.3.8.1.2-source)

SR 3.3.8.1.4 l

1 b.

Time Delay 2

SR 3.3.8.1.1 t 9.2 seconds and i

(1 per SR 3.3.8.1.2 s 10.8 seconds source)

SR 3.3.8.1.4 5.

4 kV Emergency sus Undervoltage (Degraded Voltage non-LOCA) 4.

Bus undervoltage 2

SR 3.3.8.1.1 2 4116 V and s 4186 V (1 per SR 3.3.8.1.2 source)

SR 3.3.8.1.4 j

l b.

Time Detey 2

st 3.3.8.1.1 t 57.8 seconds and s 64.2 (1 per SR 3.3.8.1.2 seconds 1

source)

SR 3.3.8.1.4 I

l PBAPS UNIT 2 3.3-65 Amendment No.

I

LOP Instrumentation B 3.3.8.1 BASES (continued) i APPLICABLE The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite j

LCO, and power. The required channels of LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (UFSAR) analyzed accidents in which a loss of j

offsite power is assumed. The first level is loss of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite power source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition.

These degraded grid relays disconnect the Class 1E buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class 1E equipment from achieving its safety function. The degraded grid relays also prevent the Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class 1E distribution systea for all credible conditions of voltage collapse or sustained voltage degradation.

The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.

Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.

The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.

The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.

The OPERABILITY of the LOP instrthnentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.

Each Function must have a required number of OPERABLE channels per 4 kV emergency bus, with their setpoints within the specified Allowable Values except the bus undervoltage relay which does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value.

Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.

-(continued)

PBAPS UNIT 2 B 3.3-188 Revision No.

LOP Instrumentation B 3.3.8.1

BASES, i

APPLICABLE The loss of voltage channel is inoperable if it will not SAFETY ANALYSES, start the diesel on a loss.of power to a 4 kV emergency bus.

LCO, and

--APPLICABILITY The Allowable Values are specified for _each applicable (continued)_

Function in the Table 3.3.8.1-1.

The nominal setpoints are selected to ensure that the setpoints do not exceed the

' Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value, is acceptable. Trip setpoints are those predetermined values of output at which'an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the. limiting values determined by the voltage regulation

- calculation.

The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, j

potential transformer accuracy, measuring and test equipment u

accuracy margin, and includes a calibration leave alone zone.

IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values.

IISCP then includes relay drift, calibration leave.

alone zones,'and margins. The setpoint assumes a nominal 35/1 potential transformer ratio.

i The specific Applicable Safety Analyses, LCO, and j

, Applicability discussions for Unit 2 LOP instrumentation are listed below on a Function by Function' basis.

In addition, since some equipment required by Unit 2 is powered from Unit 3 sources,.the Unit 3 LOP instrumentation supporting ~ the required sources must also be OPERABLE. The OPERABILITY requirements for the Unit 3 LOP instrumentation is the same as described in this section, except Function 4 (4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA) is not required to be OPERABLE, since this Function is related

-to a LOCA on Unit 3 only. The Unit 3 instrumentation is listed in Unit 3 Table 3.3.8.1-1.

1. 4 kV Emeroency Bus Undervoltaae (Loss of Voltaael When both offsite sources are lost, a loss of voltage condition on aL4 kV emergency bus indicates:that.the j

respective emergency bus is unable to supply sufficient

~

power for proper operation of the applicable. equipment.

Therefore, the power supply to the bus is transferred from offsite power to DG power. This ensures'that adequate power will be available to the required equipment.

-(continued)

PBAPS' UNIT 2 B 3.3-159 Revision No.

V I

LOP Instrumentation B 3.3.8.1 BASES APPLICABLE

1. 4 kV 'Emeroency Bus Undervoltaae (Loss of Voltaae)

SAFETY ANALYSIS, (continued)

LCO, and APPLICABILITY =

The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function per associated emergency bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE. This ensures no single instrument failure can preclude the start of three of four DGs.

(One channel inputs to each of the four DGs.) Refer to LCO 3.8.1, "AC Sources-Operating," and 3.8.2, "AC Sources-Shutdown," for Applicability Bases for the DGs.

2.

3.

4.

5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)

A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large-ECCS motors without risking damage to the motors that cou'd disable the ECCS function.

Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the~ Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which_causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.

Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and D%raded Voltage Low Setting. These relays _ monitor the following voltage levels with the following time delays: the Function 2 relay, 2286 - 2706 volts in approximately 2 seca ds when source voltage is reduced abruptly to zero volts (inverse time delay); the Function 3 relay, 3409 - 3829 volts in approximately 30 seconds when source voltage is reduced abruptly to 2940 volts (inverse time delay); the Function 4 relay, 3766 -

3836 volts in approximately 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds. The Function 2 and 3 relays are inverse time delay relays.

1 These relays operate along a repeatable characteristic i

curve. With relay operation being inverse with time, for (continued)

PBAPS UNIT 2 B 3.3-190 Revision No.

c LOP Instrumentation 3.3.8.1 Table 3.3.8.1 1 (page 1 of 1',

Loss of Power Instrumentation am REQUIRED CHANNELS

$URVEILLANCE ALLOWABLE FUNCTION PER Bus REQUIREMENTS VALUE 1.

4 kV Emergency Bus Undervoltage (Loss of Voltage) a.

Bus Undervoltage 1

SR 3.3.5.1.3 NA

$R 3.3.8.1.4 2.

4 kV Emergency Bus undervoltage (Degraded Voltage Low setting) l a.

Bus Undervoltage 2

SR 3.3.8.1.1 t 2286 y and s 2706 V (1 per sR 3.3.8.1.2 source)

SR 3.3.8.1.4 b.

Time Delay 2

rA 3.3.8.1.1 a 1.5 seconds and (1 per SR 3.3.8.1.2 5 2.1 seconds source) sR 3.3.8.1.4 3.

4 kV Emergency Bus Undervoltage (Degraded Voltage High setting) l a.

Bus Undervoltage 2

sR 3.3.8.1.1 a 34D9 Y and 5 3829 Y (1 per SR 3.3.8.1.2 source) sR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 a 23.0 seconds and (1 per SR 3.3.8.1.2 s 37.0 seconds source)

$R 3.3.8.1.4 4.

4 kW Emergency Bus undervoltage (Degraded Voltage LOCA) a.

Bus Undervoltage 2

SR 3.3.8.1.1 2 3766 y and 5 3836 V (1 per SR 3.3.8.1.2 source) sR 3.3.8.1.4 b.

Time Delay 2

SR 3.3.8.1.1 e 9.2 seconds and l

(1 per SR 3.3.8.1.2 s 10.8 seconds source) sR 3.3.8.1.4 l

5.

4 kV Emergency Bus Undervoltage (Degraded Voltage non LOCA) a.

Bus Undervoltage 2

st 3.3.8.1.1 t 4116 V and 5 4186 Y (1 per SR 3.3.8.1.2 source) st 3.3.8.1.4 l

b.

Time Delay 2

sR 3.3.8.1.1 t 57.8 seconds and s 64.2 (1 per SR 3.3.8.1.2 seconds source) sR 3.3.8.1.4

)

)

PBAPS UNIT 3 3.3-65 Amendment No.

l 1

LOP Instrumentation B 3.3.8.1 BASES (continued)

APPLICABLE The LOP instrumentation is required for Engineered Safety SAFETY ANALYSES, Features to function in any accident with a loss of offsite LCO, and power.

The required channels of LOP instrumentation ensure APPLICABILITY that the ECCS and other assumed systems powered from the DGs, provide plant protection in the event of any of the Reference 1 (VFSAR) analyzed accidents in which a loss of offsite power is assumed. The first level is los. of voltage. This loss of voltage level detects and disconnects the Class IE buses from the offsite powar source upon a total loss of voltage. The second level of undervoltage protection is provided by the four levels of degraded grid voltage relays which are set to detect a sustained low voltage condition.

These degraded grid relays disconnect the Class IE buses from the offsite power source if the degraded voltage condition exists for a time interval which could prevent the Class IE equipment from achieving its safety function. The degraded grid relays also prevent the l

Class IE equipment from sustaining damage from prolonged operation at reduced voltage. The combination of the loss of voltage relaying and the degraded grid relaying provides protection to the Class IE distribution system for all credible conditions of voltage collapse or sustained voltage degradation. The initiation of the DGs on loss of offsite power, and subsequent initiation of the ECCS, ensure that the fuel peak cladding temperature remains below the limits of 10 CFR 50.46.

Accident analyses credit the loading of the DG based on the loss of offsite power during a loss of coolant accident.

The diesel starting and loading times have been included in the delay time associated with each safety system component requiring DG supplied power following a loss of offsite power.

The LOP instrumentation satisfies Criterion 3 of the NRC Policy Statement.

The OPERABILITY of the LOP instrumentation is dependent upon the OPERABILITY of the individual instrumentation relay channel Functions specified in Table 3.3.8.1-1.

Each Function must have a required number of OPERABLE channels per 4 kV emergency bus, with their setpoints within the specified Allowable Values except the bus undervoltage relay which does not have an Allowable Value. A degraded voltage channel is inoperable if its actual trip setpoint is not within its required Allowable Value.

Setpoints are calibrated consistent with the Improved Instrument Setpoint Control Program (IISCP) methodology assumptions.

-(continued)

PBAPS UNIT 3 8 3.3-188 Revision No.

t

LOP Instrumentation B 3.3.8.1 BASES APPLICABLE The loss of voltage channel is inoperable if it will not SAFETY ANALYSES, start the diesel on a loss of power to a 4 kV emergency bus.

LCO, and APPLICABILITY The Allowable Values are specified for each applicable (continued)

Function in the Table 3.3.8.1-1.

The nominal setpoints are selected to ensure that the setpoints do not exceed the Allowable Value between CHANNEL CALIBRATIONS. Operation with a trip setpoint within the Allowable Value, is acceptable. Trip setpoints are those predetermined values of output at which an action should take place. The setpoints are compared to the actual process parameter (e.g., voltage), and when the measured output value of the process parameter exceeds the setpoint, the protective relay output changes state. The Allowable Values were set equal to the limiting values determined by the voltage regulation calculation. The setpoints were corrected using IISCP methodology to account for relay drift, relay accuracy, potential transformer accuracy, measuring and test equipment accuracy margin, and includes a calibration leave alone zone.

IISCP methodology utilizes the square root of the sum of the squares to combine random non-directional accuracy values.

IISCP then includes relay drift, calibration leave

)

alone zones, and margins. The setpoint assumes a nominal 35/1-potential transformer ratio.

The specific Applicable Safety Analyses, LCO, and Applicability discussions for Unit 3 LOP instrumentation are i

listed below on a Function by function basis.

In addition, since some equipment required by Unit 3 is powered from Unit 2 sources, the Unit 2 LOP instrumentation supporting the required sources must also be OPERABLE. The j

OPERABILITY requirements for the Unit 2 LOP instrumentation

)

is the same as described in this section, except Function 4

)

(4 kV Emergency Bus Undervoltage, Degraded Voltage LOCA) is 4

not required to be OPERABLE, since this Function is related to a LOCA on Unit 2 only. The Unit 2 instrumentation is listed in Unit 2 Table 3.3.8.1-1.

1. 4 kV Emeraency Bus Undervoltaae (Loss of Voltagg1 When both offsite sources are lost, a loss of voltage condition on a 4 kV emergency bus indicates that the respective emergency bus is unable to supply sufficient power for proper operation of the applicable equipment.

Therefore, the power supply to the bus is transferred from offsite power to DG power. This ensures that adequate power will be available to the required equipment.

.(continued)

PBAPS-UNIT'3 8 3.3-189 Revision No.

't

h i

LOP Instrumentation B 3.3.8.1 BASES APPLICABLE

1. 4 kV Emercency Bus Undervoltaae (Loss of Voltagg),

SAFETY ANALYSIS, (continued)

LCO, and APPLICABILITY The single channel of 4 kV Emergency Bus Undervoltage (Loss of Voltage) Function per associated emergency bus is only required to be OPERABLE when the associated DG and offsite circuit are required to be OPERABLE.

This ensures no single instrument failure can preclude the start of three of four DGs.

(One channel inputs to each of the four DGs.) Refer to LCO 3.8.1, "AC-Sources -Operating," and 3.8.2, "AC Sources-Shutdown," for Applicability Bases for the DGs.

2.

3.

4.

5. 4 kV Emeraency Bus Undervoltaae (Dearaded Voltaae)

A degraded voltage condition on a 4 kV emergency bus indicates that, while offsite power may not be completely lost to the respective emergency bus, available power may be insufficient for starting large ECCS motors without risking damage to the motors that could disable the ECCS function.

Therefore, power to the bus is transferred from offsite power to onsite DG power when there is insufficient offsite power to the bus. This transfer will occur only if the voltage of the preferred and alternate power sources drop below the Degraded Voltage Function Allowable Values (degraded voltage with a time delay) and the source breakers trip which causes the bus undervoltage relay to initiate the DG. This ensures that adequate power will be available to the required equipment.

Four Functions are provided to monitor degraded voltage at four different levels. These Functions are the Degraded Voltage Non-LOCA, Degraded Voltage LOCA, Degraded Voltage High Setting, and Degraded Voltage Low Setting. These relays monitor the following voltage levels with the following time delays:

the Function 2 relay, 2286 - 2706 volts in approximately 2 seconds when source voltage is reduced abruptly to zero volts (inverse time delay); the Function 3 relay, 3409 - 3829 volts in approximately 30 seconds when source voltage is reduced abruptly to 2940 volts (inverse time delay); the Function 4 relay, 3766 -

3836 volts in approximately 10 seconds; and the Function 5 relay, 4116 - 4186 volts in approximately 60 seconds. The Function 2 and 3 relays are inverse time delay relays.

These relays operate along a repeatable characteristic curve. With relay operation being inverse with time, for

-(continued)

PBAPS UNIT 3 8 3.3-190 Revision No.

-