| facility = Paducah Gaseous Diffusion Plant
| facility = Paducah Gaseous Diffusion Plant
| Organization =  
| Organization =  
| license number = Gdp-1
| license number = GDP-1
| region = 2
| region = 2
| state = Kentucky
| state = Kentucky
Line 17: Line 17:
| event date = 12/28/2008 04:45 CST
| event date = 12/28/2008 04:45 CST
| last update date = 02/06/2009
| last update date = 02/06/2009
| title = 24 Hour Report - Actuation Of Leak Detection System Due To Minor Process Gas Leak
| title = 24 Hour Report - Actuation of Leak Detection System Due to Minor Process Gas Leak
| event text = On 12/28/2008 at 0445 the C-337 unit 5 cell 3 PGLD (process gas leak detection) head located on stage 8 actuated.  Operators responded to the alarm and performed sampling in the area.  The sample result indicated 3 ppm of HF at the stage 8 compressor.  To stop the release the cell was taken off-stream and the pressure was reduced to below atmosphere. Investigation indicated that a UF6 release had occurred.  The amount of material released has not been determined.
| event text = On 12/28/2008 at 0445 the C-337 unit 5 cell 3 PGLD (process gas leak detection) head located on stage 8 actuated.  Operators responded to the alarm and performed sampling in the area.  The sample result indicated 3 ppm of HF at the stage 8 compressor.  To stop the release the cell was taken off-stream and the pressure was reduced to below atmosphere. Investigation indicated that a UF6 release had occurred.  The amount of material released has not been determined.
The actuated PGLD head is Q safety system component.  At the time of the incident the cell was operating in a mode which required the system to be operable.  This is being reported based on SAR 6.9 Table 1, J.2 as an Unplanned Actuation of a Q Safety System.
The actuated PGLD head is Q safety system component.  At the time of the incident the cell was operating in a mode which required the system to be operable.  This is being reported based on SAR 6.9 Table 1, J.2 as an Unplanned Actuation of a Q Safety System.

Latest revision as of 18:27, 24 November 2018

ENS 44744 +/- *RETRACTED*
Where
Paducah Gaseous Diffusion Plant
Paducah, Kentucky (NRC Region 2)
License number: GDP-1
Reporting
Other Unspec Reqmnt
Time - Person (Reporting Time:+3.23 h0.135 days <br />0.0192 weeks <br />0.00442 months <br />)
Opened: Kevin Beasley
13:59 Dec 28, 2008
NRC Officer: Bill Huffman
Last Updated: Feb 6, 2009
44744 - NRC Website