ENS 44744: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
(One intermediate revision by the same user not shown) | |||
Line 3: | Line 3: | ||
| facility = Paducah Gaseous Diffusion Plant | | facility = Paducah Gaseous Diffusion Plant | ||
| Organization = | | Organization = | ||
| license number = | | license number = GDP-1 | ||
| region = 2 | | region = 2 | ||
| state = Kentucky | | state = Kentucky | ||
Line 17: | Line 17: | ||
| event date = 12/28/2008 04:45 CST | | event date = 12/28/2008 04:45 CST | ||
| last update date = 02/06/2009 | | last update date = 02/06/2009 | ||
| title = 24 Hour Report - Actuation | | title = 24 Hour Report - Actuation of Leak Detection System Due to Minor Process Gas Leak | ||
| event text = On 12/28/2008 at 0445 the C-337 unit 5 cell 3 PGLD (process gas leak detection) head located on stage 8 actuated. Operators responded to the alarm and performed sampling in the area. The sample result indicated 3 ppm of HF at the stage 8 compressor. To stop the release the cell was taken off-stream and the pressure was reduced to below atmosphere. Investigation indicated that a UF6 release had occurred. The amount of material released has not been determined. | | event text = On 12/28/2008 at 0445 the C-337 unit 5 cell 3 PGLD (process gas leak detection) head located on stage 8 actuated. Operators responded to the alarm and performed sampling in the area. The sample result indicated 3 ppm of HF at the stage 8 compressor. To stop the release the cell was taken off-stream and the pressure was reduced to below atmosphere. Investigation indicated that a UF6 release had occurred. The amount of material released has not been determined. | ||
The actuated PGLD head is Q safety system component. At the time of the incident the cell was operating in a mode which required the system to be operable. This is being reported based on SAR 6.9 Table 1, J.2 as an Unplanned Actuation of a Q Safety System. | The actuated PGLD head is Q safety system component. At the time of the incident the cell was operating in a mode which required the system to be operable. This is being reported based on SAR 6.9 Table 1, J.2 as an Unplanned Actuation of a Q Safety System. |
Latest revision as of 18:27, 24 November 2018
Where | |
---|---|
Paducah Gaseous Diffusion Plant Paducah, Kentucky (NRC Region 2) | |
License number: | GDP-1 |
Reporting | |
Other Unspec Reqmnt | |
Time - Person (Reporting Time:+3.23 h0.135 days <br />0.0192 weeks <br />0.00442 months <br />) | |
Opened: | Kevin Beasley 13:59 Dec 28, 2008 |
NRC Officer: | Bill Huffman |
Last Updated: | Feb 6, 2009 |
44744 - NRC Website | |