TAC:12657
From kanterella
Jump to navigation
Jump to search
Request for: Open | |
Initiation
Questions Answers Results
Other: 05000282/LER-1984-010-01, :on 841029,steam Generator Tube Leakage Occurred.Probably Caused by Intergranular Attack in Tubesheet Crevice Region.Leaking Tubes Plugged.Several Tubes Will Be Removed for Analysis, 05000306/LER-1980-003, Forwards LER 80-003/01T-0, 05000306/LER-1980-003-01, /01T-0:on 800109,while Conducting Eddy Current Examination of Steam Generator,Row 1 Column Hot Leg Tube Found Defective.Caused by Wearing of Tube Lane Blocking Device Against Tube.Device Modified to Prevent Movement, ML19257B905, ML19323G175, ML19323G177, ML19323G178, ML20083E895, ML20093C128, ML20137Y839 | |
| From | |
MONTHYEARML19257B9051980-01-10010 January 1980
[table view]RO 80-03:during Eddy Current Insp of Steam Generator 21, Defect Discovered in One Tube.Caused by Movement of One Tube Lane Blocking Devices Against Outside Surface of Tube, 17 Inches Above Tubesheet.Tube Will Be Plugged ML19291C1991980-01-15015 January 1980 Supplemental Info to RO 80-3.One Tube Defective on Steam Generator Hot Leg 21.One Tube Defective & Ten Tubes Degraded on Cold Leg 21.Hot Leg 22 to Be Inspected.Four Tubes Defective & 42 Degraded on Cold Leg 22.Cause Unknown 05000306/LER-1980-003-01, /01T-0:on 800109,while Conducting Eddy Current Examination of Steam Generator,Row 1 Column Hot Leg Tube Found Defective.Caused by Wearing of Tube Lane Blocking Device Against Tube.Device Modified to Prevent Movement1980-01-23023 January 1980 /01T-0:on 800109,while Conducting Eddy Current Examination of Steam Generator,Row 1 Column Hot Leg Tube Found Defective.Caused by Wearing of Tube Lane Blocking Device Against Tube.Device Modified to Prevent Movement 05000306/LER-1980-003, Forwards LER 80-003/01T-01980-01-23023 January 1980 Forwards LER 80-003/01T-0 ML19323G1781980-02-29029 February 1980 Steam Generator Chemistry Study ML19323G1771980-03-10010 March 1980 Exam of Prairie Island 2 Inconel Alloy 600 Steam Generator Tube. Portions Withheld (Ref 10CFR2.790) ML19323G1751980-04-25025 April 1980 Nondestructive Exam of Prairie Island 2 Steam Generator Tubing ML19318C3481980-06-27027 June 1980 Submits Application to Withhold Westinghouse Research Rept 80-5D9-PRARI-R1, Examination at Prairie Island 2 Inconel Alloy 600 Steam Generator Tube, (Ref 10CFR2.790).Affidavit Supporting Request Encl ML19318C3441980-06-27027 June 1980 Forwards Westinghouse Rept 80-509-PRAIR-R1, Examination at Prairie Island 2 Inconel Alloy 600 Steam Generator Tube, Resulting from 800212 Meeting Re Jan 1980 Insp.Rept Withheld (Ref 10CFR2.790).Util Encl ML20083E8951983-12-19019 December 1983 Repts Steam Generator Tube Plugging Following Recent Outages.Info Will Be Expanded Upon in Inservice Insp Rept & Updated FSAR Will Be Modified ML20093C1281984-10-0101 October 1984 Provides Status of Steam Generator Tube Plugging Effort. During Recent Inservice Insp of Unit 2,33 Tubes Plugged in Steam Generators 21 & 22.Further Info Will Be Submitted in Inservice Insp Rept 05000282/LER-1984-010-01, :on 841029,steam Generator Tube Leakage Occurred.Probably Caused by Intergranular Attack in Tubesheet Crevice Region.Leaking Tubes Plugged.Several Tubes Will Be Removed for Analysis1984-11-28028 November 1984
ML20137Y8391985-10-0202 October 1985 Submits Steam Generator Tube Plugging Info,Per Tech Spec 4.12.E.1.Results of Inservice insp:19 Tubes Plugged, Including 7 Tubes in Steam Generator 21 & 12 Tubes in Steam Generator 22 (1.6% & 3.2%,respectively) 1980-04-25 | |
Retrieved from "https://kanterella.com/w/index.php?title=TAC:12657&oldid=5493356"