- 05000331/LER-1982-080-03, River Water Supply Sys Traveling Screen Wash Pump 1P-112B Found W/Discharge Head Below Tech Spec Requirement for Traveling Screen 1F-36B. Caused by Unaligned Pump & Motor.Pump/Motor Realigned (← links)
- 05000331/LER-1983-004-03, /03L-0:on 830208,during Surveillance Testing,Rcic motor-operated full-flow Test Valve MOV-2515 Would Not Properly Control Flow.Caused by Loose Valve Stem anti- Rotation Collar Due to Worn,Loose Set Screws (← links)
- 05000331/LER-1983-006-03, /03L-0:on 830211,during Normal Operation,Power Lost to MSIV D Leakage Control Sys.Caused by Blown Fuse Due to Random Failure of High Alarm Relay B21 K2D.Fuse Replaced. Replacement of Relay Under Consideration (← links)
- 05000331/LER-1983-007-03, /03L-0:on 830212,during Shutdown Surveillance Testing,W/Reactor Pressure at 400 Psig,Instrument Line in Excess Flow Check Valve XFV-4643A Would Not Check Closed & XFV-4637 & XFV-4458B Gave Open & Closed Signals When Tested (← links)