- ML17266A395 + (14:16:10, 8 January 2025)
- 05000335/LER-1980-067-01, Discovered That Some Reactor Trip Breakers Would Not Trip on Undervoltage.Caused by Redundant UV & Shunt Trip Devices Not Tripping or Tripping Sluggishly.Device Armature Realigned + (14:16:11, 8 January 2025)
- 05000335/LER-1980-012-03, Diesel Generator B Failed to Reach Rated Speed During Operational Check.Caused by Sticking Injector Linkages.All Critical Linkage Bearings Received Adequate Lubrication + (14:16:12, 8 January 2025)
- 05000335/LER-1980-069-03, /03L-0:on 801226,10% Steam Bypass Valve (PCV-8805) Failed Open Causing Reactor Power to Increase.Caused by Failure of Voltage to Current Converter in Steam Bypass Controller Cabinet.Valve Isolated + (14:16:14, 8 January 2025)
- 05000335/LER-1980-066-03, /03L-0:on 801201,B Component Cooling Water Heat Exchanger Was Isolated to Repair Leak in Icw Discharge Piping.Caused by Normal Wear & Corrosive Attack at Elbow. Leak Repaired + (14:16:15, 8 January 2025)
- 05000335/LER-1980-062-03, /03L-0:on 801218,leak Test Surveillance on Containment Personnel Air Lock Interspace Was Missed While Automatic Tester Was Out for Repair.Caused by Personnel Error.Automatic Tester Repaired + (14:16:16, 8 January 2025)
- 05000335/LER-1980-068-03, /03L-0:on 801203,containment Radiation Channel MD Failed High.Cause Not Stated.Detector Will Be Replaced During Next Outage + (14:16:18, 8 January 2025)
- 05000335/LER-1980-065-03, /03L-0:on 801121,containment Fire Protection Zone 14A Went Into Invalid Alarm State.Caused by One Detector Shorting Out Due to Condensation.Detector Removed + (14:16:19, 8 January 2025)
- ML17266A383 + (14:16:21, 8 January 2025)
- ML17266A382 + (14:16:21, 8 January 2025)
- ML17266A380 + (14:16:22, 8 January 2025)
- ML17266A381 + (14:16:22, 8 January 2025)
- 05000335/LER-1980-063-03, /03T-0:on 801107,drifting Pressure Indication for C Pressurizer Pressure Channel Was Noted & Channel Bypassed. Caused by Faulty Pressure Signal Transmitter on Pressure Sensing Instrument.Transmitter Replaced & Channel Recali + (14:16:23, 8 January 2025)
- 05000335/LER-1980-064-03, /03L-0:on 801030,during Normal Operation,Turbine Control Sys Malfunction Caused Unexpected Load Decrease Resulting in Reactor Cold Leg Temp Briefly Exceeding Tech Spec Limit.No Cause Determined.Feedback re-established + (14:16:25, 8 January 2025)
- ML17266A377 + (14:16:26, 8 January 2025)
- ML17266A376 + (14:16:27, 8 January 2025)
- TAC:43912 + (14:16:27, 8 January 2025)
- 05000335/LER-1980-038-03, /03L-0:on 800813,during Normal Operation,Cedm 7 Failed,Dropping Dual Control Element Assembly to Full Insertion.Caused by Failed Timing Module.Module Was Replaced.Cedm 7 Was Operationally Tested & Returned to Svc + (14:16:29, 8 January 2025)
- 05000335/LER-1980-037-03, /03L-0:on 800812,during Normal Full Power Operation,Containment Radiation Channed MD Failed Low. Caused by Failure of Two Capacitors in -6.8 Volt Power Supply.Capacitors Replaced + (14:16:30, 8 January 2025)
- 05000335/LER-1980-039-03, /03L-0:on 800814,dose Equivalent Iodine Exceeded Tech Spec 3.4.8a Limit.Caused by Dropped Control Element assembly.I-131 Level Decreased to Nominal Levels After 96-h + (14:16:31, 8 January 2025)
- 05000335/LER-1980-043-03, /03L-0:on 800821,during Normal Operation,Cedm 39 Failed,Dropping CEA to Full Insertion.Cause of Failure Undetermined.Power Supply Unit Replaced.Cedm 39 Returned to Normal Operations + (14:16:33, 8 January 2025)
- 05000335/LER-1980-061-03, /03L-0:on 801027,dc Electric Buses Were Switched Into Configuration Such That One Dc Bus Provided Control Power for Both Component Cooling Water Loops.Caused by Electrical Maint Activity + (14:16:34, 8 January 2025)
- ML17266A370 + (14:16:36, 8 January 2025)
- 05000335/LER-1980-058-03, /03L-0:on 801019,target A-16 Alarmed (Diesel Generator 1B Failure to Start).Caused by Open Feeder Breaker to PP-112.Feeder Breaker Closed + (14:16:37, 8 January 2025)
- 05000335/LER-1980-057-03, /03L-0:on 801008,3-inch Rip Noted in Fire Hose & Equivalent Capacity Hose Not Routed to Unprotected Area within 1-h.Caused by Procedural Deficiency.Procedure Modified + (14:16:39, 8 January 2025)
- 05000335/LER-1979-014-09, Diesel Generator Vendor Notified Util of Potential Failure of Crankshaft Coupling for Cooling Fans on Diesel Generators.Cause Unstated. Couplings Replaced W/Couplings of Improved Design + (14:16:40, 8 January 2025)
- 05000335/LER-1980-046-03, While at 100% Power, Control Element Assembly 33 Dropped to Fully Inserted Position.Caused by Failed 15-volt Dc Power Supply in Coil Power Programmer.Power Supply Replaced + (14:16:42, 8 January 2025)
- 05000335/LER-1980-059-03, /03L-0:on 801024,primary Ddps Computer Failed, Causing Loss of Control Element Assembly Position Indication.Caused by Program Software Error.Position Info Manually Reloaded Into Backup Computer + (14:16:43, 8 January 2025)
- L-80-381, Application to Amend License DPR-67 by Upgrading Rated Power from 2,560 MW to 2,700 Mw.Forwards Proposed Tech Spec Changes & Supporting Matl + (14:16:44, 8 January 2025)
- ML17266A364 + (14:16:44, 8 January 2025)
- L-80-365, Final Deficiency Rept Originally Reported on 800325 Re Defective Hydramotor Actuators for Dampers & Louvers.Caused by Mfg from Incorrect Matl.Dampers Reworked & Retested. Dampers & Louvers to Be Tested in Preoperational Program + (14:16:46, 8 January 2025)
- ML17266A361 + (14:16:46, 8 January 2025)
- 05000335/LER-1980-060-03, /03L-0:on 800929,design Review of Unit 2 Determined Tie Line Between Condensate Storage Tank & Unit 1 Auxiliary Feedwater Did Not Meet Intent of Design.Caused by Design Error.Tie Line to Be Modified + (14:16:51, 8 January 2025)
- L-80-338, Forwards Financial Info Requested by NRC Re Transfer of Ownership Interest to City of Orlando & Orlando Utils Commission.Cash Flow Statement & Bond Info Encl + (14:16:54, 8 January 2025)
- ML17266A355 + (14:16:56, 8 January 2025)
- ML17266A356 + (14:16:56, 8 January 2025)
- L-81-369, Forwards Responses to NRC Requests for Addl Info Re Facility.Responses Will Be Incorporated in Future FSAR Amend.Ten Oversize Drawings Encl.Aperture Cards Are Available in PDR + (14:16:57, 8 January 2025)
- ML17266A354 + (14:16:57, 8 January 2025)
- ML17266A352 + (14:16:59, 8 January 2025)
- ML17266A351 + (14:16:59, 8 January 2025)
- ML17266A349 + (14:17:00, 8 January 2025)
- ML17266A348 + (14:17:00, 8 January 2025)
- ML17266A350 + (14:17:00, 8 January 2025)
- ML17266A347 + (14:17:01, 8 January 2025)
- ML17266A346 + (14:17:01, 8 January 2025)
- ML17266A345 + (14:17:02, 8 January 2025)
- ML17266A344 + (14:17:02, 8 January 2025)
- ML17266A342 + (14:17:03, 8 January 2025)
- ML17266A343 + (14:17:03, 8 January 2025)
- ML17266A339 + (14:17:04, 8 January 2025)
- ML17266A340 + (14:17:04, 8 January 2025)