- 05000316/LER-1979-043-03, /03X-1:on 791102,during Surveillance Insp,Ice Condenser Divider Barrier Seal Found to Have Cracks in Rubber.Caused by Excessive Compression During Installation. Seal Ring Replaced in Manner Limiting Compression + (20:18:43, 7 January 2025)
- ML17326A429 + (20:18:45, 7 January 2025)
- ML17326A426 + (20:18:45, 7 January 2025)
- 05000316/LER-1979-047-03, /03L-0:on 791124,during Grid Degraded Voltage Relay Calibr,Relay 27-1-201-AB Dropped Out at Nonconservative Value.Caused by Zener Diode Failure.Diode Replaced & Relay Recalibr + (20:18:47, 7 January 2025)
- 05000316/LER-1979-046-03, /03L-0:on 791119,during Refueling,Source Range Neutron Flux Monitor N-31 Failed.Caused by Excessive Moisture in Detector Wells.Detectors Replaced & Dried + (20:18:49, 7 January 2025)
- ML17326A422 + (20:18:51, 7 January 2025)
- ML17326A421 + (20:18:52, 7 January 2025)
- ML17326A415 + (20:18:54, 7 January 2025)
- ML17326A412 + (20:18:56, 7 January 2025)
- ML17326A411 + (20:18:57, 7 January 2025)
- ML17326A410 + (20:18:58, 7 January 2025)
- 05000316/LER-1979-045-03, /03L-0:on 791113,penetration Provided Access from Containment to Auxiliary Bldg Atmosphere Contrary to Tech Specs.Caused by Repair of Bonnet Removed from Hand Valve.Valve Work Suspended + (20:19:00, 7 January 2025)
- ML17326A407 + (20:19:01, 7 January 2025)
- 05000316/LER-1979-045, Forwards LER 79-045/03L-0 + (20:19:02, 7 January 2025)
- 05000315/LER-1979-062-03, /03L-0:on 791111,inoperable Steam Flow Channel 1 Taken Out of Trip Condition During Investigation of Channel Spec Reading.Caused by Incorrect Panel Indicator Labeling. Channel Placed in Trip Mode & Labeling Corrected + (20:19:05, 7 January 2025)
- 05000315/LER-1979-061-03, /03L-0:on 791111,during Startup,Steam Generator 4 Steam Flow Channel 1 Indicated 21% Lower than Redundant Channel.Caused by Oil Leak from Bellows to Transmitter Body Causing Drift Out of Spec.Transmitter Replaced + (20:19:07, 7 January 2025)
- ML17326A399 + (20:19:08, 7 January 2025)
- 05000315/LER-1979-060-03, /03L-0:on 791116,intermediate Deck Door to Ice Condenser Found Frozen Shut.Caused by Plugged Air Handling Unit Drain Line & Frozen Drainage Overflow.Ice Removed & Drain Line Cleared.Mod Initiated + (20:19:10, 7 January 2025)
- 05000315/LER-1979-059-03, /03L-0:on 791108,during Test,Containment Air Particulate Detector Isolation Valve ECR-31 Would Not Close. Caused by Leaking Asco Solenoid Air Supply Valve & Vent Port Tube Restriction.Valve Cleaned & Tube Removed + (20:19:12, 7 January 2025)
- ML17326A395 + (20:19:15, 7 January 2025)
- ML17326A393 + (20:19:16, 7 January 2025)
- 05000316/LER-1979-044-03, /03L-0:on 791025,during Transfer of Fuel, Surveillance Requirement for Potential Impact Energy of Crane Load Was Not Completed.Caused by Misunderstanding of New Tech Spec.Refueling Procedure Change Initiated + (20:19:20, 7 January 2025)
- BW170109, Registration of Use of Cask to Store Spent Fuel + (20:19:23, 7 January 2025)
- ML17326A390 + (20:19:25, 7 January 2025)
- 2CAN111702, License Amendment Request - Updating the Reactor Coolant System Pressure-Temperature Limits + (20:19:27, 7 January 2025)
- AEP-NRC-2017-58, Core Operating Limits Report + (20:19:29, 7 January 2025)
- ML17326A383 + (20:19:30, 7 January 2025)
- ML17326A382 + (20:19:31, 7 January 2025)
- 05000316/LER-1979-042-03, /03L-0:on 791101,while in Mode 6,w/one Diesel Generator Out of svc,1kV Inverter Blew Fuse.Caused by Loose Bus Feed Cable Short Circuiting Inverter While Contractor Personnel Worked on Inoperable Generator + (20:19:34, 7 January 2025)
- ML17326A375 + (20:19:35, 7 January 2025)
- ML17326A374 + (20:19:37, 7 January 2025)
- 05000315/LER-1979-058-01, /01T-0:on 791115,flow Path from Unit 2 motor- Driven Afp Steam Generators 1 & 4 Was Inoperable.Caused by Power Supply to Motor Operated Valves FMO-212 & FMO-242 Being Removed for Routine Insp.Power Restored + (20:19:41, 7 January 2025)
- 05000316/LER-1979-040-03, /03L-0:on 791101,during Refueling Operations, Reactor Vessel Head Unbolted W/One Source Range Neutron Flux Monitor Inoperable.Caused by Deficient Refueling Procedure. Procedure to Be Revised + (20:19:44, 7 January 2025)
- ML17326A368 + (20:19:46, 7 January 2025)
- ML17326A367 + (20:19:47, 7 January 2025)
- ML17326A366 + (20:19:48, 7 January 2025)
- ML17326A365 + (20:19:49, 7 January 2025)
- 05000316/LER-1979-037-03, /03L-0:on 791019,emergency Leakoff Valve QMO-225 Found Open.Caused by Const Worker Accidentally Operating Breaker W/Foot.All Const Electricians Advised to Use Caution + (20:19:50, 7 January 2025)
- ML17326A352 + (20:19:52, 7 January 2025)
- ML17326A353 + (20:19:52, 7 January 2025)
- ML17326A350 + (20:19:53, 7 January 2025)
- 05000315/LER-1979-055-03, /03L-0:on 791013,while Performing 18 Month Visual Insp,Several Fire Penetration Barriers Identified as Nonfunctional.Investigation & Corrective Action Continuing Rept Will Be Submitted + (20:19:55, 7 January 2025)
- ML17326A348 + (20:19:57, 7 January 2025)
- ML17326A346 + (20:20:00, 7 January 2025)
- 05000316/LER-1979-036-03, /03L-0:on 791011,computer Disc Containing Constants for Delta Flux Program Accidently Written Over, Causing Inoperable Axial Flux Difference Alarm.Caused by Disc Area for New Program Being Next to Area for Constants + (20:20:02, 7 January 2025)
- 05000315/LER-1979-054-03, /03L-0:on 791013,all Bistable Trip Points Out of Spec.Caused by T-hot Resistance Drift 7-8% Below Normal. Replacement for Resistance to Voltage Converter Calibr to Spec & Loop Set for Proper Trip Setpoints + (20:20:04, 7 January 2025)
- 05000315/LER-1979-054, Forwards LER 79-054/03L-0 + (20:20:06, 7 January 2025)
- 05000315/LER-1979-053-03, /03L-0:on 791012,loop 3 Channel 4 Steam Generator Level Failed.Caused by Faulty Containment Cable Penetration. Penetration Feedthrough Switched to Spare Penetration & New Feedthrough Checked for Operability + (20:20:08, 7 January 2025)
- 05000315/LER-1979-053, Forwards LER 79-053/03L-0 + (20:20:10, 7 January 2025)
- ML17326A333 + (20:20:12, 7 January 2025)
- ML17326A328 + (20:20:13, 7 January 2025)