List of results
- 05000316/LER-1982-047-03, /03L-0:on 820603,insp Revealed That Installation of Valve Control 2-ABV-A Did Not Conform to Design Drawing. Caused by Inadequate Installation During Const.Emergency Mod Initiated + (04:02:37, 27 May 2025)
- 05000296/LER-1981-062, Forwards Updated LER 81-062/03X-1 + (04:02:40, 27 May 2025)
- 05000338/LER-1982-040-03, /03L-0:on 820525,pressure in Nitrogen Reservoir for Pressurizer Power Operated Relief Valve (PORV) PCV-1455C Dropped Below Required Min Pressure.Caused by Leakage in PORV Nitrogen Supply Sys.Sys Will Be Modified + (04:02:43, 27 May 2025)
- 05000316/LER-1982-046-03, /03L-0:on 820520,west Centrifugal Charging Pump Removed from Svc to Repair Leaking 1/2-inch Threaded Seal Water Line Elbow at Inboard Mechanical Seal Hx.Cause of Leak Undetermined.Fitting Removed & Threads Cleaned + (04:02:44, 27 May 2025)
- 05000338/LER-1982-033-03, /03L-0:on 820525,w/unit in Mode 5,fire Door M80-1 Between Rod Control Room & Outside Found Blocked Open W/O Fire Watch.Door Blocked by Air & Electrical Lines.Blocks Removed & Door Closed + (04:02:49, 27 May 2025)
- 05000296/LER-1982-024-03, /03L-0:on 820523,during Startup testing,5% Average Insertion Time for All Control Rods Exceeded & 11 2x2 Arrays Failed to Meet 5% Insertion Time for Fastest 3 Rods.Cause Undetermined + (04:02:51, 27 May 2025)
- IR 05000373/1981030 + (04:02:52, 27 May 2025)
- 05000327/LER-1982-067-03, /03L-0:on 820521,diesel Generator 1B-B Declared Inoperable When 120-volt Control Power Fuses Blew During Replacement of Bulb in Control Board.Caused by Shattered Bulb Glass Shorting Filaments.Fuses & Bulbs Replaced + (04:02:54, 27 May 2025)
- 05000338/LER-1982-035-03, /03L-0:on 820517,2B Fuel Oil Storage Sys for Emergency Diesel Generators Found Below Tech Spec Limits. Caused by Slow Flow Rate from Transfer Line to Day Tank. Filling Rate to 2B Tank Increased + (04:02:57, 27 May 2025)
- TAC:45202 + (04:02:57, 27 May 2025)
- TAC:12672 + (04:03:01, 27 May 2025)
- 05000366/LER-1982-057-03, /03L-0:on 820527,containment Hydrogen Peroxide Analyzer Found Inoperable.Caused by Component Failure. Analyzer Internal Sampling Flow Components Failed to Maintain Correct Flow.Sample Pump Repaired + (04:03:23, 27 May 2025)
- 05000305/LER-1982-015-03, /03L-0:on 820518,while Trying to Borate RCS During Physic Testing,No Boric Acid Flow Obtained Through Blender Due to freeze-up in Boric Acid Tank to Blender Line at Valve CVC-401.Old Heat Tracing Tape Replaced + (04:03:39, 27 May 2025)
- 05000325/LER-1981-093, Updated LER 81-093/01T-2:on 811226,reactor Protection Sys Vessel Low Level Trip instrument,1-B21-LT-NO17D-1,was Indicating Upscale.Caused by Personnel Failure to Recognize & Perform Tech Specs.Personnel Counseled + (04:03:44, 27 May 2025)
- 05000315/LER-1982-040-03, /03L-0:on 820521,operator Discovered Fire Door 367 to Nuclear Sampling Room Would Not Close Properly.Caused by 3 of 4 Screws Missing from Sequencer for Double Doors. Sequencer Securely Fastened to Frame + (04:03:48, 27 May 2025)
- 05000325/LER-1981-095-03, RHR Svc Water Subsystem Pumps B & D Would Not Start Due to Simulated Low Header Pressure Lockout.Caused by Open Circuit Breaker in Motor Coolers Low Suction Pressure Permissive Switch + (04:03:50, 27 May 2025)
- 05000325/LER-1981-095, Forwards Updated LER 81-095/03L-1 + (04:03:53, 27 May 2025)
- 05000338/LER-1982-039-03, /03L-0:on 820517,steam Flow Channel IV Flow Indicator FI-1485 for Steam Generator 1B Discovered Reading Offscale Low.Cause Not Determined.Channel Placed in Trip Condition,Transmitter Calibr & Instrument Loop Checked + (04:03:59, 27 May 2025)
- 05000366/LER-1982-052-03, /03L-0:on 820525,during Startup from Refueling & Performance of Safety Relief Valve Operability Tests, Solenoids of Valves 2B21-F013A & E Interchanged.Caused by Personnel Error.Personnel Reinstructed + (04:04:02, 27 May 2025)
- 05000328/LER-1982-064-03, /03L-0:on 820523,lower Containment Airlock Door Failed Air Leak Rate Test.Caused by Air Leakage Through Door Handwheel Shaft Packing.Packing Tightened & Door Retested. Design Change Request Submitted + (04:04:11, 27 May 2025)
- 05000339/LER-1982-026-03, /03L-0:on 820520,RCS Suction to RHR Sys Pumps Lost on Three Occasions.Caused by Erroneous RCS Level Indications While Draining Rcs.Charging Pump Started to Refill Sys + (04:04:16, 27 May 2025)
- 05000339/LER-1982-024-03, /03X-0:on 820518,w/RCS Water Solid,Power Operated Relief valve,PCV-2456,lifted Twice When Loop C Cold Leg Stop valve,MOV-2595,opened & Reactor Coolant pump,2-RC-P-1C Started.Caused by Thermal Expansion of Reactor Coolant + (04:04:30, 27 May 2025)
- 05000250/LER-1982-005-03, /03L-0:on 820519,during Routine Startup,Augmented Surveillance of Hot Channel Factors Not Initiated When Threshold Power (98%) Was Passed.Caused by Procedural Error.Procedure Change Initiated + (04:04:33, 27 May 2025)
- 05000267/LER-1982-019-03, /03L-0:on 820518,during Feedwater Flow Surveillance Test,Circulator 1A Speed Program Switch & Two Feedwater Flow Switches Were Out of Calibr.Caused by Instrument Drift.Switches Recalibr + (04:05:13, 27 May 2025)
- 05000334/LER-1982-014, Forwards LER 82-014/01T-0 + (04:05:17, 27 May 2025)
- 05000318/LER-1982-024-03, /03L-0:on 820514,ESF Actuation Sys Channel C Pressurizer Pressure Failed Low,Resulting in Removal of Channel Zf & Subcooled Margin Monitor 22 from Svc.Caused by Fault in Ac/Dc Converter Isolator 2-PY-102C + (04:05:47, 27 May 2025)
- 05000219/LER-1982-029, Forwards LER 82-029/01T-0.Detailed Event Analysis Encl + (04:05:48, 27 May 2025)
- 05000311/LER-1982-044-03, /03L-0:on 820518,operator Discovered Leakage Rate of 130-ft Elevation Containment Air Lock Exceeded Tech Spec Limits.Caused by Improperly Positioned Inner Door Seal. Inner Door Seal Properly Positioned + (04:05:54, 27 May 2025)
- 05000334/LER-1982-018-03, /03L-0:on 820512,RHR Pump RH-P-1B Failed to Start. Caused by Interruption of RHR Flow,Due to Procedural & Personnel Errors.Circuit Breaker Racking Mechanism Problem Delayed Restoring Flow.Procedure Revised & Operator Trained + (04:05:54, 27 May 2025)
- ML20054H181 + (04:06:03, 27 May 2025)
- 05000315/LER-1982-039-01, /01T-0:on 820601,during Monthly Insp of Eccs,Boron Injection Tank Isolation Valve Cycled W/Recirculation Valve Open.Caused by Personnel Error.Procedure Revised & Appropriate Administrative Action Taken + (04:06:20, 27 May 2025)
- 05000318/LER-1980-011-01, Diesel Generator 21 Failed to Achieve 10-s Rated Speed,Rendering Low Pressure Safety Injection Pump 22 Inoperable.Caused by Slow Response of Diesel Generator Governor.Governor Replaced + (04:06:26, 27 May 2025)
- 05000318/LER-1980-011, Forwards Updated LER 80-011/01X-1 + (04:06:29, 27 May 2025)
- 05000272/LER-1982-032-03, /03L-0:on 820515,boric Acid Flow in Transfer Pumps 11 & 12 Decreased Below Tech Spec Limit Rendering Pumps Inoperable.Caused by Increase in Impeller to Volute Clearance Due to Normal Wear.Clearance Adjusted + (04:06:44, 27 May 2025)
- 05000333/LER-1982-023-03, /03L-0:on 820514,during Normal Operation,While Conducting Surveillance,Containment Isolation Valve 10 MOV 38A Found Inoperable.Caused by Motor Failure.Motor Replaced + (04:07:56, 27 May 2025)
- 05000311/LER-1982-046-03, /03L-0:on 820527,during Routine Surveillance,Less than Required Svc Water Flow to Containment Coil Unit 23 Discovered.Caused by Oysters Plugging Valve Tube Bundle 23SW57.Oysters Removed & Svc Water Flow Returned to Normal + (04:08:07, 27 May 2025)
- 05000313/LER-1982-011-03, /03L-0:on 820514,discovered That on 820502 Reactor Heated Above 280 F W/O Proving Emergency Feedwater Sys Operable Through Successful Completion of Required Automatic Actuation Surveillance Tests + (04:08:15, 27 May 2025)
- 05000272/LER-1982-036-03, /03L-0:on 820526,control Room Emergency Air Conditioner 12 Failed to Operate.Caused by Tripped Load Ctr Supply Breaker 1C16Y de-energizing Fan Power Supply.No Cause Determined.Breaker Closed & Fan Returned to Svc + (04:08:31, 27 May 2025)
- 05000328/LER-1982-063-03, /03L-0:on 820518,during Surveillance Instruction 106,several Ice Bed Flow Passages Found Blocked W/Excessive Frost & Ice in Bay 8 of Ice Condensor.Caused by Blockage of Air Handling Unit 9A by Sandblasting Pellets + (04:09:08, 27 May 2025)
- 05000280/LER-1982-029-03, /03L-0:on 820518,during Periodic Test 2-PT-39B-2 Snubbers 2-RC-HSS-162 & 163 Found to Have Empty Remote Reservoir.Caused by Damaged O Ring on Common Valve Block. O Ring Replaced + (04:09:09, 27 May 2025)
- 05000280/LER-1982-062-03, /03L-0:on 820520,PT-27 Revealed Low Ampere Readings for Circuit 7A in Panels 8 & 9,contrary to Tech Spec.Caused by Damaged Tapes.Tapes Replaced + (04:09:11, 27 May 2025)
- 05000271/LER-1982-010-03, /03L-0:on 820513 & 27,RHR Svc Water Breaker Tripped Free When Pump Started.Caused by Worn Prop.Ge Model 416 250-8HB Breaker Prop Replaced.Breaker Tested Satisfactorily & Returned to Svc + (04:09:18, 27 May 2025)
- 05000325/LER-1982-052-03, /03L-0:on 820524,surveillance Revealed That Primary Containment Atmosphere Oxygen analyzer,1-CAC-AT-125 9-2 Would Not Indicate Expected Drywell Oxygen Concentrations.Caused by Calibr Shift on Zero End + (04:09:23, 27 May 2025)
- 05000272/LER-1982-037-03, /03L-0:on 820526,svc Water Flow to Containment Fan Coil Unit 12 Found Below Tech Spec Requirements.Caused by Flow Control Valve 12SW223 Stuck in Closed Position.Valve Repaired + (04:09:25, 27 May 2025)
- IR 05000219/1982002 + (04:09:36, 27 May 2025)
- 05000271/LER-1982-009-03, /03L-0:on 820513,during Normal Operation,Reactor Pressure Indicator PI 2-3-55D Indicated Lower than Redundant Indicators.Caused by Degraded 24-volt Dc Power Supply.Power Supply Replaced + (04:09:40, 27 May 2025)
- 05000272/LER-1981-035, Forwards LER 81-035/03X-1.Detailed Event Analysis Encl + (04:09:48, 27 May 2025)
- 05000325/LER-1982-059-03, /03L-0:on 820522,surveillance Revealed That Fully Withdrawn Control Rod 38-39 Had Intermittent RTGB Position 48 Indication While full-out RTGB Indication Was Operable. Caused by Defective Rod Position Reed Switch + (04:09:54, 27 May 2025)
- 05000250/LER-1982-004-03, /03L-0:on 820517,during Routine Reactor Startup, Augmented Surveillance of Hot Channel Factors Not Maintained as Required.Caused by Computer Taken Out of Svc During Surveillance Sequence.Personnel Reinstructed + (04:10:02, 27 May 2025)
- TAC:48523 + (04:10:09, 27 May 2025)
- IR 05000271/1982001 + (04:10:12, 27 May 2025)