Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000346/LER-1981-036-03, /03L-0:on 810616,containment Radiation post- Accident monitor,RE-5030,found Not Running.Caused by Low Flow Due to Bypass Discharge Hose Falling Off During Routine Maint.Hose Reconnected & Monitor Restarted + (05:03:36, 23 December 2024)
- 05000220/LER-1981-024-03, /03L-0:on 810615,containment Oxygen Sampling Isolation Valve 201.2-23 Failed to Meet Acceptance Criteria of N1-1SP-25.6 During Local Leak Rate Testing.Caused by Dirt Under Seat.Valve Bonnet Removed & Body & Seat Cleaned + (05:03:38, 23 December 2024)
- 05000346/LER-1981-014-03, /03X-1:on 810226,decay Heat Valve 64 Would Not Open During Testable ECCS Valves Quarterly Test.Caused by Loose Set Rod Bushing,Allowing Gear Box Set Rod to Move Which Unlocked Limit Switches from Adjusted Position + (05:03:43, 23 December 2024)
- 05000249/LER-1980-048-03, Shutdown Cooling Sys Inboard Isolation Valve Did Not Close During Shutdown,While Testing Group 2 & 3 Isolation Circuitry.Caused by Breaker Door Interlock Out of Adjustment.Interlock Adjusted + (05:03:45, 23 December 2024)
- 05000220/LER-1981-024, Forwards LER 81-024/03L-0 + (05:03:47, 23 December 2024)
- ML20009D617 + (05:03:50, 23 December 2024)
- 05000346/LER-1981-014, Forwards LER 81-014/03X-1 + (05:03:51, 23 December 2024)
- 05000249/LER-1980-048, Forwards Updated LER 80-048/03X-1 + (05:03:56, 23 December 2024)
- ML20009D609 + (05:03:58, 23 December 2024)
- ML20009D605 + (05:04:09, 23 December 2024)
- ML20009D606 + (05:04:09, 23 December 2024)
- ML20009D603 + (05:04:11, 23 December 2024)
- 05000237/LER-1981-006-01, Excessive Leakage Indicated Various Penetrations in Feedwater Check Valves. Caused by Cracked O Ring & Worn Swing Pins.Valves Repaired & Broken Components Replaced + (05:04:13, 23 December 2024)
- ML20009D601 + (05:04:14, 23 December 2024)
- 05000237/LER-1981-006, Forwards Updated LER 81-006/01X-1 + (05:04:16, 23 December 2024)
- 05000346/LER-1981-036, Forwards LER 81-036/03L-0 + (05:04:18, 23 December 2024)
- ML20009D595 + (05:04:19, 23 December 2024)
- 05000318/LER-1981-029-03, /03L-0:on 810609,reactor Protection Sys Channel a Trip Unit for Thermal Margin/Low Pressure Monitor Was Found to Be Faulty.Caused by Bistable Trip Unit ATU7 Not Tripping at Appropriate Signal Levels.Trip Unit Replaced + (05:04:21, 23 December 2024)
- ML20009D592 + (05:04:24, 23 December 2024)
- 05000318/LER-1981-029, Forwards LER 81-029/03L-0 + (05:04:26, 23 December 2024)
- ML20009D587 + (05:04:27, 23 December 2024)
- ML20009D586 + (05:04:28, 23 December 2024)
- ML20009D584 + (05:04:30, 23 December 2024)
- 05000249/LER-1981-015-03, /03L-0:on 810618,switch Actuated at 32.8 Inches During Calibr of Isolation Condenser Steam/Condensate Line High Flow.Caused by Instrument Drift.Switch Reset + (05:04:31, 23 December 2024)
- ML20009D580 + (05:04:32, 23 December 2024)
- 05000249/LER-1981-015, Forwards LER 81-015/03L-0 + (05:04:34, 23 December 2024)
- ML20009D577 + (05:04:35, 23 December 2024)
- 05000331/LER-1981-025-03, /03L-0:on 810616,RHR B Svc Water Pump Did Not Develop Required Discharge Pressure at Rated Flow.Caused by Normal Wear Creating Excessive Clearances Between Impeller & Casing Rings.Impellers Adjusted + (05:04:36, 23 December 2024)
- ML20009D575 + (05:04:38, 23 December 2024)
- ML20009D574 + (05:04:39, 23 December 2024)
- ML20009D572 + (05:04:40, 23 December 2024)
- 05000331/LER-1981-025, Forwards LER 81-025/03L-0 + (05:04:41, 23 December 2024)
- ML20009D569 + (05:04:42, 23 December 2024)
- ML20009D568 + (05:04:43, 23 December 2024)
- ML20009D566 + (05:04:46, 23 December 2024)
- IR 05000293/1981007 + (05:04:47, 23 December 2024)
- ML20009D563 + (05:04:48, 23 December 2024)
- IR 05000254/1981011 + (05:04:54, 23 December 2024)
- 05000306/LER-1981-008-01, /01T-0:on 810611,shaft Vibration on Reactor Coolant Pump 21 & Seal 1 Leakoff Flow Increased Beyond Normal Range.Pump Disassembled.On 810706,circumferential Crack Discovered.Cause Not Determined + (05:04:57, 23 December 2024)
- ML20009D557 + (05:05:00, 23 December 2024)
- 05000306/LER-1981-008, Forwards LER 81-008/01T-0 + (05:05:02, 23 December 2024)
- 05000305/LER-1981-022-03, /03L-0:on 810619,spent Fuel Pool Boron Sampling Not Performed within Allotted Time Frame During Steady State Operation.Caused by Temporary Work Load Increase on Chemistry Staff.Sample Taken & Analyzed + (05:05:05, 23 December 2024)
- ML20009D552 + (05:05:06, 23 December 2024)
- ML20009D551 + (05:05:07, 23 December 2024)
- 05000305/LER-1981-022, Forwards LER 81-022/03L-0 + (05:05:08, 23 December 2024)
- IR 05000312/1981018 + (05:05:10, 23 December 2024)
- 05000331/LER-1981-024-03, /03L-0:on 810616,drywell Equipment Drain Line Valve CV-3729 Did Not Give Fully Closed Indication During Testing.Caused by Seat Leakage in Solenoid Valve SV-3729. Solenoid Valve Replaced + (05:05:12, 23 December 2024)
- ML20009D543 + (05:05:14, 23 December 2024)
- 05000315/LER-1981-022-03, /03L-0:on 810618,during Surveillance,Feedwater Snubber 1-FWS-1 Found to Have Rotated to Position Allowing Air to Enter Fluid Inlet Ports.During Functional Bench Test, Snubber Failed to Lock Up.Caused by Loose Locknut + (05:05:17, 23 December 2024)
- 05000331/LER-1981-024, Forwards LER 81-024/03L-0 + (05:05:20, 23 December 2024)
- 05000315/LER-1981-022, Forwards LER 81-022/03L-0 + (05:05:21, 23 December 2024)