Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20064F245 + (01:52:05, 17 December 2024)
- ML20064F244 + (01:52:06, 17 December 2024)
- ML20064F243 + (01:52:07, 17 December 2024)
- 05000338/LER-1978-110-03, /03l-0 on 781024:following a Reactor Trip,The Containment Bulk Avg Temp Exceeded 105 Degrees F Tech Spec Limit Due to Steam Loss to Chilled Water Sys Vacuum Refrigeration Unit + (01:52:08, 17 December 2024)
- 05000334/LER-1982-058-03, /03L-0:on 821122,while Performing Power Range Neutron Flux Channel N-NI 42 Quarterly calibr,1.84 Rate Trip Time Constant Discovered.Caused by Instrument Drift. Time Constant Adjusted to 2.24 + (01:52:10, 17 December 2024)
- 05000333/LER-1982-058-04, /04T-0:on 821217,defected Mn-54 Level in Mollusk Samples Exceeded 10 Times Control Location Sample Level. Possibly Caused by High Bioaccumulation Factor,Resulting in Accumulation of Trace Quantities in Mollusks + (01:52:13, 17 December 2024)
- 05000338/LER-1978-100, Forwards LER 78-100/01X-0, 78-110/03L-0 & 78-113/03L-0 + (01:52:15, 17 December 2024)
- 05000334/LER-1982-058, Forwards LER 82-058/03L-0 + (01:52:16, 17 December 2024)
- ML20064F222 + (01:52:17, 17 December 2024)
- 05000338/LER-1978-120-01, /01T-0 on 781121:inspec of Station Battery Racks Revealed That Racks Had Been Improperly Assembled & Installed During Constr.Deficiencies Will Be Corrected + (01:52:20, 17 December 2024)
- 05000364/LER-1982-051, Forwards LER 82-051/03L-0 + (01:52:21, 17 December 2024)
- ML20064F209 + (01:52:21, 17 December 2024)
- 05000338/LER-1978-122-01, /01T-0 on 781113:during Steady State Oper,It Was Discovered That Only One Seal or Barrier Exists for Spare Pipe Penetrations in Conflict W/Fsar Due to Oversight of Design Personnel.Engineering Is Analyzing It for Solution + (01:52:23, 17 December 2024)
- ML20064F203 + (01:52:24, 17 December 2024)
- ML20064F201 + (01:52:25, 17 December 2024)
- ML20064F199 + (01:52:25, 17 December 2024)
- 05000267/LER-1978-033-03, /03L-0 on 781027:during Routing Surveillance of Steam Pipe Rupture Detection Sys,One of Three Bistables for High Temperature Under Pcrv Did Not Trip,Due to Corroded Cable Terminal Board at Junction Box + (01:52:27, 17 December 2024)
- ML20064F197 + (01:52:28, 17 December 2024)
- ML20064F187 + (01:52:28, 17 December 2024)
- 05000338/LER-1978-120, Forwards LER 78-120/01T-0 & LER 78-122/01T-0 + (01:52:29, 17 December 2024)
- 05000333/LER-1982-058, Forwards LER 82-058/04T-0 + (01:52:30, 17 December 2024)
- ML20064F182 + (01:52:32, 17 December 2024)
- A02589, Forwards Addl Info Re safety-related ECCS Tank Outages, Provided Verbally on 821220 in Response to NUREG-0737, Item II.K.3.17 + (01:52:33, 17 December 2024)
- 05000387/LER-1982-065, Forwards LER 82-065/03L-0 + (01:52:36, 17 December 2024)
- 05000267/LER-1978-033, Forwards LER 78-033/03L-0 + (01:52:38, 17 December 2024)
- 05000336/LER-1978-029-03, /03L-0 on 781025:during Oper,Surveillance Test on Channel a Reactor Protec Sys Core Protec Calculator Reveated Sys Ground Traced to Signal for Pressurizer Pressure W/In Containment Boundary.Source Not Known at This Time + (01:52:39, 17 December 2024)
- 05000336/LER-1978-029, Forwards LER 78-029/03L-0 + (01:52:41, 17 December 2024)
- ML20064F155 + (01:52:42, 17 December 2024)
- 05000387/LER-1982-058-03, /03L-0:on 821122,during Startup Testing Program, full-in Position Lost on Rod 46-23 Causing Rod Withdrawal Block Preventing Rod Movement.Cause Unknown.Condition Would Not Repeat When Technicians Arrived to Work on Rod + (01:52:44, 17 December 2024)
- ML20064F142 + (01:52:45, 17 December 2024)
- RBG-40322, Responds to Violation Noted in Insp Rept 50-458/94-05 Re Failure to Maintain Uninterruptible Power Security Sys. Caused by Inadequate Evaluation.Temporary Compensatory Instructions for UPS Sys Security Operations Bulletin Loss + (01:52:45, 17 December 2024)
- 05000267/LER-1978-016-03, /03X-1 on 780510:while Oper at 40% Pwr,Moisture Concentrations in Pcrv Exceeded Limits of 4.2.11.Moisture Was Introduced During Previous Loop 1 Shutdown & Collected in Pcrv Insulation + (01:52:47, 17 December 2024)
- 05000267/LER-1978-016, Forwards LER 78-016/03X-1 + (01:52:48, 17 December 2024)
- 05000259/LER-1982-097-03, /03L-0:on 821203,review Revealed Several Isolation Valves Tested Less Frequently than Required by Tech Spec.Caused by Misinterpretation of NRC Guidelines When Implementing Asme,Section Xi.Instructions Revised + (01:52:50, 17 December 2024)
- ML20064F129 + (01:52:55, 17 December 2024)
- ML20064F131 + (01:52:55, 17 December 2024)
- 05000387/LER-1982-058, Forwards LER 82-058/03L-0 + (01:52:56, 17 December 2024)
- ML20064F126 + (01:52:57, 17 December 2024)
- 05000348/LER-1978-082-03, /03L-0 on 781025:B Train Penetration Room Filtration Sys Inoperable.Caused by Low Spring Tension on Filter Support Assembly + (01:52:58, 17 December 2024)
- 05000348/LER-1978-082, Forwards LER 78-082/03L-0 + (01:53:00, 17 December 2024)
- ML20064F120 + (01:53:01, 17 December 2024)
- 1CAN128210, Forwards Acoustic Emision Insp of Reactor Coolant Pump Motor Flywheel, Per 820914 Request + (01:53:03, 17 December 2024)
- ML20064F113 + (01:53:04, 17 December 2024)
- 05000277/LER-1982-039-03, /03L-0:on 821126,HPCI Flow Controller Read Approx 80% Instead of 100%.Caused by Faulty Amplifier Card in Flow Controller.Flow Controller Replaced & HPCI Sys Tested & Returned to Svc + (01:53:06, 17 December 2024)
- 05000278/LER-1978-021-01, /01T-0 on 781106:while at Pwr Feedwater Control Sys Failure Resulted in Reactor Low Level Transient & Scram HPCI Initiated But Delivered Unstable Flow & Soon Tripped on Overspeed.Cause Was HPCI Governor Being Out of Calibr + (01:53:08, 17 December 2024)
- 05000278/LER-1978-021, Forwards LER 78-021/01T-0 + (01:53:09, 17 December 2024)
- ML20064F104 + (01:53:10, 17 December 2024)
- 05000368/LER-1978-010-01, /01T-0 on 781102:during Post-Core Hot Functional Test,Prior to Initial Criticality Mode 3 Oper,Lift Setpoints of Main Steam Line Code Safety Valves Were Nonconservative. Caused by Incorrect Identification of Simmer Point + (01:53:12, 17 December 2024)
- 05000259/LER-1982-097, Forwards LER 82-097/03L-0 + (01:53:13, 17 December 2024)
- 05000368/LER-1978-010, Forwards LER 78-010/01T-0 + (01:53:14, 17 December 2024)
- TAC:M87189 + (01:53:15, 17 December 2024)