- ML20087K103 + (19:11:55, 13 December 2024)
- ML20087K099 + (19:11:56, 13 December 2024)
- ML20087K102 + (19:11:56, 13 December 2024)
- ML20087K093 + (19:11:57, 13 December 2024)
- ML20087K076 + (19:11:58, 13 December 2024)
- ML20087K081 + (19:11:58, 13 December 2024)
- ML20087K072 + (19:11:59, 13 December 2024)
- 05000285/LER-1976-013-03, /03L:on 760413,positive Axial Power Distribution Limit Setpoint Out of Spec in Nonconservative Direction on Channel A.Caused by Random Noise Signals.Minor Circuit Mod Implemented to Prevent Reoccurrence + (19:12:01, 13 December 2024)
- 05000285/LER-1976-014-01, /01T:on 760414,valve HCV-383-4 Failed to Close by Control Switch.Caused by GE Type 7700,Size 1 Combination Breaker/Reversing Starter Failure to Operate Due to Binding Contact.Contact Lubricated & Adjusted + (19:12:04, 13 December 2024)
- 05000285/LER-1976-015-03, /03L:on 760408 & 20,inadvertent Noble Gas Releases to Auxiliary Bldg Occurred Due to Valve leak-by on Chemical & Vol Control Sys.Caused by Leakage by Standby Ion Exchanger CH-8A Isolation Valves + (19:12:06, 13 December 2024)
- 05000285/LER-1976-016-03, /03L:on 760427,primary Air Start Motor for Diesel Generator 2 Failed to Disengage.Caused by Incorrect Airgap Setting.Airgap Properly Set & Generator Successfully Started W/Proper Disengagement + (19:12:09, 13 December 2024)
- 05000285/LER-1976-017-01, /01L:on 760518,no Flow Condition Discovered on Steam Generator Blowdown Radiation Monitors RM-054A & B. Caused by Closed Valve HCV-2508.Valve Immediately Reopened + (19:12:11, 13 December 2024)
- ML20087K058 + (19:12:12, 13 December 2024)
- 05000285/LER-1976-018-03, /03L:on 760514,possible Violation of Release Rate for Containment Purge 76A-11 Discovered.Caused by Inaccurate High Reading by Sensitive Spectrometer Sys.Violation Did Not Occur + (19:12:14, 13 December 2024)
- 05000285/LER-1976-019-01, /01T:on 760528,two Main Steam Safety Valves Relieved Due to Setpoint Drift.Caused by Environ Temp Conditions.Valves Reset & Setpoint Returned to Plus or Minus 1% of Nominal Setpoint Value + (19:12:17, 13 December 2024)
- 05000285/LER-1976-019, Suppl 1 to LER 76-19/03L:on 761001,five of 10 Valve Setpoints Drifted from Tech Spec Tolerance of Plus or Minus 1%.Caused by Change in Environ Condition.Valves Will Be Inspected During Refueling Outage + (19:12:18, 13 December 2024)
- 05000285/LER-1976-020-01, /01T:on 760604,util Notified of Error in Strikin II Computer Code Which Could Result in Reduction of 0.7 Kw/Ft in Allowable Peak Linear Heat Rate.Caused by Representing Guide Tubes as Solid Rods + (19:12:20, 13 December 2024)
- 05000285/LER-1976-021-03, /03L:on 760629,timer Relays for SI-3A,AC-3B & Si-3B Failed to Time Out at Set Times.Caused by Mechanical Binding of Time Relay Model HA-41A6-L-08.Timer Relays Tested Twice Weekly Until Replacements Received + (19:12:22, 13 December 2024)
- 05000285/LER-1976-021, Suppl 1 to LER 76-21/03L:on 760802,timer Relays for SI-3A, AC-3B & SI-3B Failed to Time Out at Set Times.Caused by Binding Operating Mechanisms.Timers Tested Twice Weekly to Verify Operability Until Replacements Received + (19:12:23, 13 December 2024)
- ML20087K026 + (19:12:24, 13 December 2024)
- ML20087K025 + (19:12:26, 13 December 2024)
- 05000285/LER-1976-022-01, /01T:on 760710,river delta-temp Limit of 20F Exceeded.Caused by Failure of Condenser Backwash Valve MOV-A-D4 to Open Electrically After Backwashing Condenser. Backwash Valve Repaired + (19:12:31, 13 December 2024)
- ML20087K022 + (19:12:32, 13 December 2024)
- ML20087K019 + (19:12:33, 13 December 2024)
- 05000285/LER-1976-023-01, /01T:on 760726,safety Injection Refueling Water Storage Tank Boron Concentration Reduced to 1,825 Ppm. Caused by Valve CH-152 leak-by.Valve Tightened + (19:12:34, 13 December 2024)
- 05000285/LER-1976-024-01, /01L:on 760801,waste Liquid Release Conducted W/Waste Liquid Process Radiation Monitor Inoperable.Caused by Operator Failure to Return Monitor to Operate Position. Operator Orally Reprimanded + (19:12:36, 13 December 2024)
- ML20087K013 + (19:12:37, 13 December 2024)
- ML20087K010 + (19:12:38, 13 December 2024)
- 05000285/LER-1976-025-03, /03L:on 760815,4,160 Volt Breaker T1B-3B Tripped on Instantaneous Overcurrent Relaying,Deenergizing 4,160/480 Volt Transformer T1B-3B & 480 Volt Bus 1B3B.Caused by Internally Faulted Transformer + (19:12:40, 13 December 2024)
- DCL-84-110, Forwards Nekton,Inc Paper, Post-Miocene Compressional Tectonics Along Central State of CA Margin. Conclusion of Paper Will Reviewed + (19:12:41, 13 December 2024)
- ML20087K004 + (19:12:44, 13 December 2024)
- ML20087K001 + (19:12:45, 13 December 2024)
- ML20087K003 + (19:12:45, 13 December 2024)
- ML20087K000 + (19:12:46, 13 December 2024)
- ML20087J997 + (19:12:48, 13 December 2024)
- ML20087J999 + (19:12:48, 13 December 2024)
- NG-95-2583, Monthly Operating Rept for July 1995 for Duane Arnold Energy Ctr + (19:12:49, 13 December 2024)
- ML20087J991 + (19:12:50, 13 December 2024)
- 05000285/LER-1976-026-03, /03L:on 760815,dc Bus 2 Ground Alarm Annunciated in Control Room & Smoke Observed Coming from Diesel Generator 2 Governor Motor Encl.Caused by RPM Governor Motor Armature Internally Faulted + (19:12:52, 13 December 2024)
- ML20087J987 + (19:12:56, 13 December 2024)
- ML20087J985 + (19:12:57, 13 December 2024)
- 05000285/LER-1976-027-03, /03L:on 760815,primary Air Start Motor for Diesel Generator 2 (DG) Failed to Disengage After DG-2 Successfully Started.Caused by Drift of Airgap Setting for Magnetic Pickup Unit.Preventive Maint Program Revised + (19:12:58, 13 December 2024)
- ST-HL-AE-5146, Forwards Response to GL 92-01,Rev 1,Suppl 1, Reactor Vessel Structural Integrity. Reactor Pressure Vessels at Util Built by C-E + (19:12:59, 13 December 2024)
- 05000285/LER-1976-029-03, /03L:on 760831,reactor Coolant Sampled & Analyses Indicated I-131 Equivalent 2.075 Uci Per Gram.Caused by Power Transient.Numercial Limit Exceeded But All Conditions of Tech Spec Fulfilled + (19:13:01, 13 December 2024)
- 05000285/LER-1976-030, Summary of 760902 Telcon on LER 76-30/01L Re Steam Generator Blowdown Radiation Monitor Setpoints Out of Spec.Caused by Use of Unofficial & Incorrect Document as Part of 760804 Surveillance Test + (19:13:02, 13 December 2024)
- BSEP-95-0384, Monthly Operating Repts for July 1995 for BSEP Units 1 & 2 + (19:13:03, 13 December 2024)
- 05000285/LER-1976-030-01, /01T:on 760901,discovered High Alarm Setpoint on Steam Generator Blowdown Monitors RM-054A & RM-054B Set at 600,000 Counts Per Minute.Caused by Use of Unofficial Copy of Process Monitor Setpoints + (19:13:05, 13 December 2024)
- ML20087J953 + (19:13:06, 13 December 2024)
- ML20087J933 + (19:13:07, 13 December 2024)
- ML20087J930 + (19:13:07, 13 December 2024)
- ML20087J910 + (19:13:08, 13 December 2024)