- 05000260/LER-1985-017-03, :on 851120,during Handling of Spent Local Power Range Monitor in Fuel Pool,Instrument Tube Came Too Close to Water Surface,Setting Off Alarms.Radiological Caution Statements Added to Procedure + (ML20138Q555)
- ML20138Q556 + (ML20138Q556)
- ML20138Q557 + (ML20138Q557)
- ML20138Q558 + (ML20138Q558)
- 3F1285-17, Forwards Response to 851105 Request for Addl Info & Seven Training Dept Procedures Re Licensed Operator Requalification & Replacement Operator Training Programs + (ML20138Q560)
- B15686, Requests Removal of Portion of Util in Response to Insp Repts 50-245/95-34,50-336/95-34 & 50-423/95-34 + (ML20138Q561)
- 05000327/LER-1985-040, :on 851009,trains Became Inoperable Due to Air Injection Into Suction of Pumps During Swap Over from Train B to a Rhr.Caused by Procedure Inadequacy.Pumps Shutoff & Vented.Rcs Level Increased.Valves Verified + (ML20138Q562)
- ML20138Q563 + (ML20138Q563)
- ML20138Q564 + (ML20138Q564)
- ML20138Q565 + (ML20138Q565)
- ML20138Q567 + (ML20138Q567)
- 05000302/LER-1985-020, :on 851009,both MSIVs from Steam Generator B Automatically Closed Due to Spurious Emergency Feedwater Initiation & Control Actuation.Caused by Low Steam Generator Level Indication.Trip Module Replaced + (ML20138Q569)
- ML20138Q571 + (ML20138Q571)
- ML20138Q574 + (ML20138Q574)
- ML20138Q576 + (ML20138Q576)
- ML20138Q580 + (ML20138Q580)
- ML20138Q583 + (ML20138Q583)
- ML20138Q584 + (ML20138Q584)
- 05000327/LER-1985-039-01, :on 851010,containment Ventilation Isolation Occurred.Caused by Instrument Mechanic Mistakenly Running Test on Incorrect Radiation Monitor.Mechanic Counseled. Disciplinary Action Will Be Taken + (ML20138Q585)
- ML20138Q586 + (ML20138Q586)
- ML20138Q588 + (ML20138Q588)
- 05000338/LER-1985-022, :on 851205,firearm Discovered & Confiscated by Security Personnel in Access Area.Employee Retained, Searched,Questioned & Escorted Offsite.Firearm in Duffle Bag by Accident,Based on Polygraph Test + (ML20138Q590)
- ML20138Q591 + (ML20138Q591)
- ML20138Q592 + (ML20138Q592)
- ML20138Q593 + (ML20138Q593)
- ML20138Q595 + (ML20138Q595)
- 05000219/LER-1985-022, :on 851120,main Generator Tripped,Causing Turbine Trip & Full Reactor Scram.After Scram Reset,Msiv Closure Scram Occurred.Generator Trip Due to Phase B Differential Current Relay Trip.Unit Replaced + (ML20138Q596)
- ML20138Q598 + (ML20138Q598)
- ML20138Q600 + (ML20138Q600)
- 05000336/LER-1985-015, :on 851008,no Sample Flow from Radmonitor Discovered.Caused by Low Flow Switch FIS8262 Stuck in Nonalarming Position,Closed Suction Valve 2-EB-89 & Failure of Operator to Verify Proper Radmonitor Flow + (ML20138Q601)
- 05000289/LER-1997-002, :on 970129,potential Inability of Startup Feedwater Block Valves to Fully Close Following Main Steam Line Break Occurred Due to MOV Program Weakness.Increased Torque Switch Settings on Valve Operators + (ML20138Q602)
- 05000528/LER-1985-058, :on 851003,reactor Trip Occurred Due to Low DNBR on Core Protection Calculators.Caused by Switchyard Breakers Opening Due to Malfunction in Multiplexer.Breakers Hardwired.Coolant Pump Procedures Revised + (ML20138Q603)
- NSD-NRC-97-4974, Forwards non-proprietary Copies of WCAP-14808, Notrump Final Validation Rept for AP600, Revs 0 & 1.TRs Address Aspects of AP600 Design Certification Application + (ML20138Q604)
- ML20138Q605 + (ML20138Q605)
- ML20138Q606 + (ML20138Q606)
- ML20138Q607 + (ML20138Q607)
- ML20138Q608 + (ML20138Q608)
- 05000458/LER-1985-039, :on 851117,in Operational Condition 2 at 30 Mwt,Rwcu Sys Isolated Due to Unstable High Differential Flow Readings.Caused by Water Flashing at Blowdown Flow Element G33 FEN011.Loop Recalibr + (ML20138Q610)
- ML20138Q611 + (ML20138Q611)
- 05000219/LER-1985-021, :on 851119,during Performance of APRM Surveillance Test & Calibr Procedure,Aprm Flow Converter Trip Setpoint Exceeded Tech Spec Acceptance Criteria.Caused by Setpoint Drift.Setpoint Reset + (ML20138Q612)
- RBG-22603, Informs That Util Will Comply W/Nrc Sept 1985 Policy Statement Re Shift Technical Advisors on Shift Prior to Startup After First Refueling Outage.When Shift Technical Advisor Utilized,Fifth Operator Will Be Assigned to Shift + (ML20138Q614)
- ML20138Q616 + (ML20138Q616)
- ML20138Q618 + (ML20138Q618)
- ML20138Q619 + (ML20138Q619)
- 05000298/LER-1985-018, :on 851123,ESF Challenged Due to Trip of RWCU Sys Space Temp Switches.Caused by RWCU Mechanical Pump Seal Failure,Resulting in Steam Leak.Procedure Revised + (ML20138Q625)
- ST-HL-AE-1386, Forwards Response to Draft SER or FSAR Items Q410.04,40.38, 211.21,211.38,440.78,10.27,311.03,222.8,440.44,Q430.120 & D.0.7-3 Concerning Motor Operator Valves & Diesel Generator Loading Table.Related Correspondence + (ML20138Q628)
- ML20138Q629 + (ML20138Q629)
- IR 05000245/1985015 + (ML20138Q630)
- 05000220/LER-1985-018, :on 851010,low Air Pressure Start Test of Tech Spec Section 4.6.7.b.4 Failed.Caused by Need to Energize or Manually Bypass Solenoids on Governor Sys.Mods to Governor Sys & Sys Manual Start Performed + (ML20138Q632)
- ML20138Q633 + (ML20138Q633)
- 05000312/LER-1985-021, :on 851119,emergency Diesel Generator a Automatically Started When Bus 4A Normal Supply Breaker Tripped on Overvoltage Condition.Caused by Technicians Disconnecting Ground Wiring + (ML20138Q636)