Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20069B092 + (ML20069B092)
- 05000321/LER-1983-015, Forwards LER 83-015/03L-0 + (ML20069B094)
- 05000321/LER-1981-117, Forwards LER 81-117/03L-0 + (ML20069B095)
- 05000321/LER-1983-015-03, /03L-0:on 830204,reactor Water Cleanup Sys Differential Instrument Ft&C Procedure Not Performed in Sept 1982.Caused by Personnel Error During Entry of Listed Surveillance.Mod Instituted + (ML20069B100)
- AECM-81-413, Forwards Description of Sys Interaction Programs,Per Unresolved Safety Issues A-17 + (ML20069B101)
- 05000321/LER-1981-117-03, /03L-0:on 811116,while Performing HNP-1-3975,test of Control Room & Standby Gas Treatment Filter Trains,Train a Declared Inoperable Due to Burned Out Transformer in Heater Control Box.Caused by Indicating Wire Short Circuit + (ML20069B103)
- ML20069B108 + (ML20069B108)
- 05000321/LER-1981-130, Forwards LER 81-130/03L-0 + (ML20069B112)
- ML20069B113 + (ML20069B113)
- 05000321/LER-1981-130-03, /03L-0:on 811130,during Normal Power Operation,Rhr Heat Exchanger 1E11-B001B Was Taken Out for Insp of RHR Svc Water Side.Rhr Svc Water Isolated from RHR Heat Exchanger B for Maint.Subsystem Determined Inoperable on 811203 + (ML20069B115)
- 05000328/LER-1981-143, Forwards LER 81-143/03L-0 + (ML20069B123)
- 05000328/LER-1981-143-03, /03L-0:on 811115,w/shutdown Banks Withdrawn, Reactor Tripped on lo-lo Steam Generator Level Due to Failure of 2-LCV-3-171.Caused by Dirty Solenoid.Solenoid Cleaned & Cover Replaced + (ML20069B128)
- 05000296/LER-1981-067, Forwards LER 81-067/03L-0 + (ML20069B136)
- 05000324/LER-1981-126, Forwards LER 81-126/03L-0 + (ML20069B142)
- 05000302/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20069B151)
- ML20069B154 + (ML20069B154)
- 05000296/LER-1981-067-03, /03L-0:on 811116,continuous Air Monitor 3-RM-90-249 Failed to Sample Turbine Room Roof Exhaust W/ Fans in Operation.Caused by Worn Std V-belt for Schwitzer Model 325 Vacuum Pump.Belt Replaced & Monitor Tested + (ML20069B156)
- ML20069B157 + (ML20069B157)
- ML20069B159 + (ML20069B159)
- ML20069B161 + (ML20069B161)
- 05000324/LER-1981-126-03, /03L-0:on 811119,during Routine Surveillance, Control Room Chart recorder/indicator,2-CAC-AR-1263,model Mark Ii,Discovered Showing Downscale Trend in Drywell Oxygen Concentration.Caused by Failure to Perform Required Maint + (ML20069B163)
- 05000321/LER-1981-126, Forwards LER 81-126/03L-0 + (ML20069B167)
- 05000321/LER-1981-126-03, /03L-0:on 811123,A71-K1C Reactor low-low Level Relay Found Inoperable.Caused by Component Failure Due to Insulation Breakdown in Coil.Relay Replaced + (ML20069B171)
- 05000302/LER-1983-006-03, /03L-0:on 830203,during Control Rod Exercise Surveillance,Absolute Position Indication for Rod 6,group 2 Failed to Indicate +/-2% Motion Per Tech Spec Requirements. Caused by Failed Reed Switch.Tube Replaced + (ML20069B176)
- ML20069B180 + (ML20069B180)
- ML20069B182 + (ML20069B182)
- ML20069B183 + (ML20069B183)
- 05000364/LER-1981-047-03, /03L-0:on 811109,indicator PI3371B of Steam Generator 2B Pressure Instrumentation Loop to Hot Shutdown Panel Failed Low.Caused by Loop Power Supply Card Failure. Card Replaced + (ML20069B185)
- 05000324/LER-1983-025, Forwards LER 83-025/03L-0 + (ML20069B189)
- 05000296/LER-1981-068, Forwards LER 81-068/03L-0 + (ML20069B192)
- 05000324/LER-1981-127, Forwards LER 81-127/03L-0 + (ML20069B197)
- ML20069B198 + (ML20069B198)
- ML20069B202 + (ML20069B202)
- 05000324/LER-1983-025-03, /03L-0:on 830216,closed Position Indication for Drywell to Suppression Pool Vacuum Breaker X18C Could Not Be Achieved.Caused by Problem W/Vacuum Breaker Closed Position Limit Switch LB-240-794.Problem Will Be Investigated + (ML20069B204)
- 05000364/LER-1981-049-03, /03L-0:on 811109,B2G Sequencer on Diesel Generator 2B Failed to Meet Time Requirements for Picking Up Step 5 While Performing Operability Test.Caused by Setpoint Drift of Agastat Timer.Timer Adjusted + (ML20069B205)
- 05000261/LER-1981-031-01, /01T-0:on 811201,pressurizer Power Operated Relief Valve Block Valves Were Determined Not to Meet Design Specs. Valve Motor Operators Failed to Shut Valves Completely Following 811130 Transient.Block Valves Closed Manually + (ML20069B217)
- W3P83-0547, Forwards Proposed Rev to FSAR Committing to Set of Low Power Natural Circulation Tests in Satisfaction of Operator Training Requirements of NUREG-0737,Item I.G.1 + (ML20069B220)
- AECM-81-494, Second Interim Deficiency Rept Re Lower Flow Rate in ESF Electrical Switchgear Room Cooling Sys,Initially Reported 810303.Measurement of Flow Rates at Various Locations Continuing.Next Rept by 820131 + (ML20069B228)
- ML20069B229 + (ML20069B229)
- 05000369/LER-1981-179, Forwards LER 81-179/03L-0.Detailed Event Analysis Encl + (ML20069B230)
- ML20069B241 + (ML20069B241)
- ML20069B242 + (ML20069B242)
- 05000324/LER-1981-127-03, /03L-0:on 811121,printing Mechanism of Primary Containment Atmospheric Monitoring Recorder 2-CAC-AR-1259 Drove Hard Downscale When Exhibiting Indication of Hydrogen Concentration in Drywell.Caused by Instrument Drift + (ML20069B244)
- 05000316/LER-1981-065, Forwards LER 81-065/04L-0 + (ML20069B251)
- 05000369/LER-1981-179-03, /03L-0:on 811111,during Performance of Below Bank Rod Test,Reactor Was Manually Tripped Due to Loss of Cooling Water to Reactor Coolant Pump Motor Coolers.Caused by Failed Fuse in Power Supply of Solenoid Valve to IRN-253A + (ML20069B254)
- ML20069B258 + (ML20069B258)
- 05000316/LER-1981-065-04, /04L-0:on 811127,extreme High delta-P Across Traveling Screens Was Discovered.Circulation Water Pump 24 Was Shut Down Causing Condenser delta-T to Rise Above Tech Spec Limits.Caused by Cladophora Accumulating on Screens + (ML20069B264)
- ML20069B274 + (ML20069B274)
- ML20069B275 + (ML20069B275)
- ML20069B281 + (ML20069B281)
- ML20069B284 + (ML20069B284)