- 05000338/LER-1982-054-03, /03L-0:on 820716,valve Guide Discovered Missing from Loop a Cold Leg Reactor Coolant Loop Stop Valve MOV-1591.Cause Unknown.Missing Part Found in Reactor Vessel on 820803.Valve Guide Will Be Removed + (ML20062M877)
- ML20062M880 + (ML20062M880)
- ML20062M881 + (ML20062M881)
- AECM-81-452, Forwards Summary of Environ Protection Program Respecting Const of Grand Gulf Nuclear Stations Units 1 & 2 for Six Months Ending Oct 31 1981 + (ML20062M883)
- 05000373/LER-1982-075, Forwards LER 82-075/03L-0 + (ML20062M885)
- 05000328/LER-1981-141, Forwards LER 81-141/03L-0 + (ML20062M886)
- 05000361/LER-1982-053-03, /03L-0:on 820719,condensate Storage Tank T-121 Water Level Fell Below Tech Spec Limit on Seven Occasions. Caused by Inadequate Makeup Water Control to Tank.Tech Spec Change Initiated to Install Automatic Level Control + (ML20062M889)
- ML20062M892 + (ML20062M892)
- ML20062M897 + (ML20062M897)
- 05000251/LER-1981-014, Forwards LER 81-014/02T-0 + (ML20062M901)
- ML20062M903 + (ML20062M903)
- ML20062M905 + (ML20062M905)
- 05000328/LER-1981-141-03, /03L-0:on 811112,auxiliary Feedwater Pump a Pressure Control Valve 2-PCV-3-122 Could Not Be Operated from Main Control Room.Caused by Inoperable Servo Valve Due to Clogged Passages from Contaminated Hydraulic Fluid + (ML20062M908)
- ML20062M911 + (ML20062M911)
- ML20062M912 + (ML20062M912)
- BECO-94-003, Responds to NRC Request for Addl Info on Proposed TS Change Re Spent Fuel Storage Capacity Expansion + (ML20062M916)
- 05000373/LER-1982-075-03, /03L-0:on 820726,air Hose to Automatic Dispatch Sys Valve 1B21-FO13V Ruptured So That in Compressors Could Not Maintain Sys Pressure.Probably Caused by Hose Age, Exceeding Min Bend Radius & Exposure to High Temp + (ML20062M917)
- ML20062M919 + (ML20062M919)
- ML20062M922 + (ML20062M922)
- 05000251/LER-1981-014-02, /02T-0:on 811123,defective Area of Large Aggregate W/Inadequate Fines Found in Containment Liner Plate Concrete Cover.Caused by Inadequate Cementation of Original Pour as Result of Defective Concrete Batch + (ML20062M924)
- 05000369/LER-1982-060, Forwards LER 82-060/03L-0 + (ML20062M927)
- 05000361/LER-1982-057-03, /03L-0:on 820720,condensate Storage Tank T-121 Water Level Fell Below Tech Spec Limit on Four Occasions. Caused by Inadequate Makeup Water Control to Tank.Tech Spec Change Initiated to Install Automatic Level Control + (ML20062M931)
- ML20062M937 + (ML20062M937)
- 05000361/LER-1982-042, Forwards LER 82-042/01T-0.Detailed Event Analysis Submitted + (ML20062M939)
- 05000324/LER-1982-086, Forwards LER 82-086/03L-0 + (ML20062M947)
- ML20062M951 + (ML20062M951)
- 05000327/LER-1981-139, Forwards LER 81-139/03L-0 + (ML20062M952)
- 05000327/LER-1981-139-03, /03L-0:on 811112,control Rod Indication Sys Declared Inoperable Due to Being Out of Calibr.Caused by Dirty Potentiometer.Indicator Recalibr & Returned to Svc + (ML20062M956)
- ML20062M958 + (ML20062M958)
- 05000361/LER-1982-068-03, /03L-0:on 820728,condensate Storage Tank T-121 Water Level Fell Below Tech Spec Limit on Two Occasions. Caused by Inadequate Makeup Water Control to Tank.Tech Spec Change Initiated to Install Automatic Level Control + (ML20062M960)
- 05000369/LER-1982-060-03, /03L-0:on 820701,06 & 13,fire Detection Sys Trouble Alarms Could Not Be Cleared & Efa Zones 63 & 64 Declared Inoperable.Caused by Corrosion Due to Water Leakage Into Data Gathering Panel 1.Failed Components Replaced + (ML20062M962)
- 05000259/LER-1981-071, Forwards LER 81-071/03L-0 + (ML20062M963)
- 05000259/LER-1981-072, Forwards LER 81-072/03L-0 + (ML20062M966)
- ML20062M967 + (ML20062M967)
- 05000259/LER-1981-071-03, /03L-0:on 811111,1-LIS-3-203B Switch 2 Operated at 31.4 Inches of Water.Caused by Instrument Drift.Barton Model 288 Switch Recalibr + (ML20062M972)
- 05000324/LER-1982-086-03, /03L-0:on 820715,during Refueling Outage,Source Range Monitors C & D Indicated Erratic Upscale Count Rate. Caused by Guide Tube Sealing Gland Leak Allowing Moisture Intrusion Into Detector Cable Connectors.Leak Repaired + (ML20062M974)
- ML20062M978 + (ML20062M978)
- ML20062M980 + (ML20062M980)
- 05000321/LER-1981-124, Forwards LER 81-124/03L-0 + (ML20062M981)
- 05000361/LER-1982-071-03, /03L-0:on 820727,condensate Storage Tank T-121 Water Level Fell Below Tech Spec Limit on One Occasion. Caused by Inadequate Makeup Water Control to Tank.Tech Spec Change Initiated to Install Automatic Level Control + (ML20062M982)
- ML20062M988 + (ML20062M988)
- 05000361/LER-1982-042-01, /01T-0:on 820729,during Mode 3,stroke Time for Valves 2HV4706 & 2HV4713 Exceeded Tech Spec Allowable Response Times.Caused by Improper Limit Switch.Setting Corrected & Acceptance Criteria Added + (ML20062M989)
- 05000321/LER-1981-124-03, /03L-0:on 811121,torus Delta Pressure Transmitter 1T48-N008 Drain Valve Closed.Cause Attributed to Procedure Inaccuracy.Procedure Revised + (ML20062M991)
- ML20062M994 + (ML20062M994)
- 05000259/LER-1981-072-03, /03L-0:on 811112,while Performing SI 4.2.B-55, Pressure Transmitter 1-PT-74-65 Found Out of Tolerance. Caused by Instrument Drift.Ge Model 551 Pressure Transmitter Recalibr,Functionally Tested & Returned to Svc + (ML20062M995)
- ML20062M997 + (ML20062M997)
- ML20062M999 + (ML20062M999)
- ML20062N000 + (ML20062N000)
- ML20062N002 + (ML20062N002)
- ML20062N004 + (ML20062N004)
- 05000313/LER-1982-017, Forwards LER 82-017/03L-0 + (ML20062N008)