- 05000245/LER-1981-013, Forwards LER 81-013/03L-0 + (ML20009F410)
- 05000245/LER-1981-013-03, /03L-0:on 810612,flow Rates Found to Be Lower than Expected While Using Standby Gas Treatment Sys to Ventilate Primary Containment.Caused by HEPA Filter Fouling.Filters Replaced & Sys Returned to Svc + (ML20009F412)
- ML20009F413 + (ML20009F413)
- ML20009F415 + (ML20009F415)
- ML20009F416 + (ML20009F416)
- ML20009F417 + (ML20009F417)
- 05000366/LER-1981-057, Forwards LER 81-057/01T-0 + (ML20009F418)
- ML20009F419 + (ML20009F419)
- ML20009F420 + (ML20009F420)
- 05000366/LER-1981-057-01, /01T-0:on 810623,valve 2P41-F315B Found Closed. Caused by Inadvertent Operation Due to Possible Bumping of Control Switch.Valve Opened & Protective Cover Installed + (ML20009F421)
- ML20009F422 + (ML20009F422)
- 05000321/LER-1981-048, Forwards LER 81-048/03L-0 + (ML20009F423)
- ML20009F424 + (ML20009F424)
- ML20009F425 + (ML20009F425)
- ML20009F427 + (ML20009F427)
- TXX-3371, Addresses Concerns Expressed During Site Visit Re Separation Between Class IE & non-Class IE Circuits at Transfer Switches for Hot Shutdown Panel.Adequate Separation Will Be Provided in Examining Isolation Cords/Interposing Relays + (ML20009F428)
- 05000321/LER-1981-048-03, /03L-0:on 810702,HPCI Isolated on High Steam Line Flow.Caused by Switch Failure Due to Loss of Internal Damping.Switch Replaced,Recalibr & Returned to Svc.Hpci Proven Operable + (ML20009F429)
- ML20009F430 + (ML20009F430)
- ML20009F431 + (ML20009F431)
- ML20009F432 + (ML20009F432)
- 05000369/LER-1981-031, Forwards LER 81-031/03L-0 + (ML20009F433)
- ML20009F434 + (ML20009F434)
- 05000369/LER-1981-031-03, /03L-0:on 810313,noble Gas Activity Monitor EMF-33 for Condenser Evacuation Sys Not Functioning.Caused by Excessive Moisture in Sample Lines.Grab Samples Taken as Required.Mod to Equipment in Progress + (ML20009F437)
- 05000321/LER-1981-055, Forwards LER 81-055/03L-0 + (ML20009F439)
- ML20009F440 + (ML20009F440)
- ML20009F442 + (ML20009F442)
- ML20009F444 + (ML20009F444)
- 05000321/LER-1981-055-03, /03L-0:on 810327,snubbers 1B21-FDH-19, 1B21-FDH-22A,1B21-SS23 & 1E11-RHRH-234 Were Low of Fluid. Probably Caused by Seal Leakage.Snubbers Replaced + (ML20009F445)
- 05000369/LER-1981-102-03, /03L-0:on 810621,peak Shock Annunciation 20.2 Hz Red Light Was Actuated.Caused by Wire from Contact Switch in Triaxial response-spectrum Recorder Pinched Between Contact Block & Mounting Frame,Resulting in Short.Wire Cleared + (ML20009F446)
- ML20009F447 + (ML20009F447)
- L-81-208, Final Deficiency Rept Re Unauthorized Field Welded Attachments on Containment Vessel Shell,Initially Reported on 810416.Special Repair Procedure Issued to Correct/Remove Weld Deficiencies + (ML20009F448)
- ML20009F449 + (ML20009F449)
- 05000321/LER-1981-072, Forwards LER 81-072/03L-0 + (ML20009F450)
- ML20009F451 + (ML20009F451)
- 05000321/LER-1981-078, Forwards LER 81-078/03L-0 + (ML20009F452)
- ML20009F453 + (ML20009F453)
- 05000321/LER-1981-072-03, /03L-0:on 810707,instrument Root Valve B21-F500 for Low Condenser Vacuum Switches Had Been Isolated Causing Instruments to Trip.Cause Unknown.Valve Returned to Correct Position.Root Valves Locked Open + (ML20009F454)
- 05000321/LER-1981-078-03, /03L-0:on 810712,torus Water Temp Found Above Allowable Temp Level.Caused by Testing of Reactor Core Isolation Cooling & HPCI Turbines.Temp Was Reduced to Allowable Level + (ML20009F455)
- 05000321/LER-1981-054, Forwards LER 81-054/03L-0 + (ML20009F457)
- 05000366/LER-1981-069, Forwards LER 81-069/03L-0 + (ML20009F458)
- ML20009F459 + (ML20009F459)
- 05000366/LER-1981-069-03, /03L-0:on 810630,average Power Range Monitor Surveillance Not Performed within Required Time Limit. Caused by Personnel Error.Surveillance Performed + (ML20009F460)
- 05000339/LER-1981-048, Forwards LER 81-048/03L-0 + (ML20009F461)
- ML20009F462 + (ML20009F462)
- ML20009F463 + (ML20009F463)
- ML20009F464 + (ML20009F464)
- ML20009F465 + (ML20009F465)
- ML20009F466 + (ML20009F466)
- ML20009F467 + (ML20009F467)
- ML20009F468 + (ML20009F468)