- 05000324/LER-1980-062, Updated LER 80-062/01T-1:on 800907,during Unit 2 Reactor Core Isolation Cooling Flow Rate Test,Reactor Core Isolation Cooling Turbine Tripped on High Turbine Exhaust Pressure. Caused by Personnel Error + (ML19347A893)
- 05000325/LER-1980-069, Forwards LER 80-069/03L-0 + (ML19347A894)
- ML19347A895 + (ML19347A895)
- ML19347A897 + (ML19347A897)
- ML19347A898 + (ML19347A898)
- ML19347A899 + (ML19347A899)
- ML19347A901 + (ML19347A901)
- 05000325/LER-1980-069-03, /03L-0:on 800827,during Normal Surveillance,Rhr Flow Indicator on Remote Shutdown Panel Demonstrated Erratic Indications W/Sys Shutdown.Caused by Mechanical Failure of Meter Movement.Movement Calibr & Returned to Svc + (ML19347A902)
- 05000348/LER-1980-052, Forwards LER 80-052/03L-0 + (ML19347A903)
- ML19347A904 + (ML19347A904)
- 05000348/LER-1980-052-03, /03L-0:on 800829,electronic Switching Sys B1H Sequencer Failed to Meet Time Requirement for Steps 2 & 3. Caused by Setpoint Drift.Agastat Timers Satisfactorily Reset + (ML19347A905)
- 05000259/LER-1980-069, Forwards LER 80-069/03L-0 + (ML19347A906)
- ML19347A907 + (ML19347A907)
- ML19347A909 + (ML19347A909)
- 05000259/LER-1980-069-03, /03L-0:on 800902,while Performing SI 4.2.A-17, Channel B of Refueling Zone Isolation Static Pressure Permissive & Static Pressure Logic Sys Damper O-PDC64-8 Failed to Close.Contacts Adjusted + (ML19347A911)
- 05000219/LER-1980-039, Forwards LER 80-039/03L-0 + (ML19347A912)
- ML19347A913 + (ML19347A913)
- 05000348/LER-1980-051, Forwards LER 80-051/03L-0 + (ML19347A914)
- ML19347A915 + (ML19347A915)
- 05000366/LER-1980-128-03, /03L-0:on 800905,reactor High Pressure Instruments 2B21-N023C & D Actuated Above Tech Specs.Caused by Setpoint Drift.Switches Recalibr & Tested Successfully + (ML19347A916)
- 05000348/LER-1980-051-03, /03L-0:on 800826,diesel Generator 1C Failed to Reach Speed within Specified Limits.Apparent Cause Was Leaking Check Valve in Fuel Oil Sys.Valve Replaced & Diesel Generator Returned to Svc + (ML19347A917)
- 05000219/LER-1980-039-03, /03L-0:on 800829,during Low Pressure Main Steam Line Functional Test & calibr,RE23B & 23D Pressure Switches Actuated at Valve Above Tech Spec Limits.Caused by Instrument Repeatability.Switches Reset to Desired Limit + (ML19347A918)
- ML19347A919 + (ML19347A919)
- ML19347A921 + (ML19347A921)
- 05000285/LER-1980-021, Forwards LER 80-021/03L-0 + (ML19347A922)
- ML19347A923 + (ML19347A923)
- ML19347A924 + (ML19347A924)
- ML19347A925 + (ML19347A925)
- ML19347A926 + (ML19347A926)
- ML19347A928 + (ML19347A928)
- 05000368/LER-1980-063, Forwards LER 80-063/03L-0 + (ML19347A929)
- ML19347A930 + (ML19347A930)
- 05000285/LER-1980-021-03, /03L-0:on 800910,transformer T4 of DG-1 Failed. Transformer Feeds Diesel Oil Immersion Heater & Alarm Relays.Caused by Moveable Armature Located on Immersion Heater Contractor.Armature Repaired + (ML19347A931)
- ML19347A932 + (ML19347A932)
- 05000296/LER-1980-035, Forwards LER 80-035/03L-0 + (ML19347A933)
- ML19347A934 + (ML19347A934)
- ML19347A935 + (ML19347A935)
- 05000368/LER-1980-063-03, /03L-0:on 800822,after Unit Trip at 90%,power a Condensate Storage Tank Level Fell Below Tech Spec Min. Caused by Emergency Feedwater Sys.Suction Taken from Tank After Unit Trip.Procedures Revised to Prevent Reoccurrence + (ML19347A936)
- ML19347A938 + (ML19347A938)
- 05000296/LER-1980-035-03, /03L-0:on 800901, a Reactor Recirculation Pump Tripped.Caused Undetermined.Unit Load Reduced to 700 Mw & Pump Restarted in 6-h + (ML19347A939)
- ML19347A940 + (ML19347A940)
- 05000267/LER-1980-047, Forwards LER 80-047/03L-0 + (ML19347A941)
- ML19347A942 + (ML19347A942)
- 05000325/LER-1980-070, Forwards LER 80-070/03L-0 + (ML19347A945)
- ML19347A946 + (ML19347A946)
- ML19347A947 + (ML19347A947)
- 05000259/LER-1980-068, Forwards LER 80-068/01T-0 + (ML19347A948)
- ML19347A949 + (ML19347A949)
- 05000219/LER-1980-038, Forwards LER 80-038/03L-0 + (ML19347A951)
- ML19347A952 + (ML19347A952)
- ML19347A953 + (ML19347A953)