- 05000333/LER-1979-101, Forwards LER 79-101/03L-0 + (ML19262A890)
- ML19262A891 + (ML19262A891)
- ML19262A892 + (ML19262A892)
- 05000333/LER-1979-101-03, /03L-0:on 791108,during Operations Surveillance Test F-ST-76L,six Penetrations Discovered Not Sealed During Plant Const.Cause Not Stated.Penetrations Sealed w/3-h Rated Matl & Performed Fire Watch + (ML19262A894)
- ML19262A895 + (ML19262A895)
- IR 05000546/1979019 + (ML19262A896)
- 05000029/LER-1979-029, Forwards LER 79-029/03L-0 + (ML19262A897)
- 05000029/LER-1979-029-03, /03L-0:on 791106,during Testing of post-accident Hydrogen Venting sys,HV-SOV-1 & 2 Failed to Seat Properly. Caused by Oil & Dirt Buildup on Valve Internals.Valves Cleaned,Inspected & Returned to Svc + (ML19262A901)
- 05000029/LER-1979-030, Forwards LER 79-030/03L-0 + (ML19262A902)
- 05000029/LER-1979-030-03, /03L-0:on 791109,during Safety Injection Accumulator Time Delay Verification Procedure OP-4630,TDC4 Setpoint Discovered to Be Beyond Tech Spec Limit.Cause Under Investigation.Temporarily Replaced Time Delay Relay + (ML19262A905)
- ML19262A906 + (ML19262A906)
- ML19262A908 + (ML19262A908)
- ML19262A909 + (ML19262A909)
- ML19262A911 + (ML19262A911)
- ML19262A912 + (ML19262A912)
- ML19262A913 + (ML19262A913)
- ML19262A914 + (ML19262A914)
- 05000293/LER-1979-043, Forwards LER 79-043/03L-0 + (ML19262A915)
- ML19262A916 + (ML19262A916)
- 05000293/LER-1979-043-03, /03L-0:on 791108,drywell Unidentified Leakage Rate Exceeded Tech Specs.Caused by Leakage Passing Inboard Isolation Valve MO-2301-4 on HPCI Sys.Valve Backseated & Leakage Reduced to Less than That Requiring Shutdown + (ML19262A917)
- ML19262A918 + (ML19262A918)
- 05000219/LER-1979-042, Forwards LER 79-042/03L-0 + (ML19262A919)
- ML19262A920 + (ML19262A920)
- ML19262A921 + (ML19262A921)
- 05000219/LER-1979-042-03, /03L-0:on 791106,valve ERV Nr 108A Opened During Operation for No Reason.After Calibr,Valve Malfunctioned within 1-h.Caused by Component Failure.Pressure Switch Replaced + (ML19262A922)
- ML19262A923 + (ML19262A923)
- ML19262A924 + (ML19262A924)
- 05000321/LER-1979-091, Forwards LER 79-091/03L-0 + (ML19262A925)
- ML19262A926 + (ML19262A926)
- 05000321/LER-1979-091-03, /03L-0:on 791106,insurance Investigation Revealed Required Penetration Seal Not Installed in 2-inch Penetration in Control/Svc Bldg Firewall.Caused by Misinterpreted Drawings.Seal Installed + (ML19262A927)
- 05000312/LER-1979-003, Forwards LER 79-003/04T-0 + (ML19262A928)
- 05000312/LER-1979-003-04, /04T-0:on 791120,plant Effluent Sample Exceeded Tech Spec Limit of 0.2 Mg/L Chlorine.Caused by Excessive Flow in Plant Sewage Sys + (ML19262A930)
- 05000333/LER-1979-100, Forwards LER 79-100/03L-0 + (ML19262A931)
- ML19262A932 + (ML19262A932)
- 05000333/LER-1979-100-03, /03L-0:on 791108,during Normal Operation to Complete Corrective Maint,Hpci Sys Unintentionally Made Inoperable.Caused by Need to Replace Leaking Gasket Associated W/Sys Hydraulic Control Valve Seat Drain + (ML19262A933)
- 05000302/LER-1979-105, Forwards LER 79-105/03L-0 + (ML19262A934)
- ML19262A935 + (ML19262A935)
- 05000302/LER-1979-105-03, /03L-0:on 791101,during Sampling of Rcs,Chemical Addition Isolation Valve CAV-2 Would Not Close.Cause Unknown.Valve Body of CAV-2 Lubricated,Satisfactorily Tested & Returned to Svc on 791102 + (ML19262A936)
- ML19262A937 + (ML19262A937)
- ML19262A938 + (ML19262A938)
- 05000348/LER-1979-050-03, /03L-0:on 791107,trip Bistables for Pressurizer Pressure Transmitter PT455 Not Tripped Before Pressurizer Level Transmitter 459 Root Valves Closed.Caused by Personnel Error.Matter to Be Discussed W/Operations Personnel + (ML19262A939)
- 05000348/LER-1979-051-03, /03L-0:on 791103,during Surveillance Test on Turbine Driven Auxiliary Feedwater Pump,Pump Tripped on Overspeed.Caused by Misadjustment of Manual Speed Due to Leak of Position Markings.Manual Control Adjusted + (ML19262A940)
- 05000348/LER-1979-052-03, /03L-0:on 791106,refueling Water Storage Tank Declared Inoperable When Water Vol Fell Below Tech Specs. Caused by Drift Problems on Level Transmitters.Transmitters Undergoing Repairs + (ML19262A941)
- 05000348/LER-1979-054-01, /01T-0:on 791119,notified by Westinghouse That Possibility Exists That Current Negative Rate Trip Setpoints May Not Provide Reactor Trip During Single or Multiple Rod Drop Events.Caused by Designer Calculation Errors + (ML19262A942)