- ML18025A933 + (ML18025A933)
- 05000296/LER-1980-018-03, /03L-0:on 800519,reactor Low Pressure Switch PS-3-74B SW 1,found Out of Tolerance.Caused by Instrument Setpoint Drift.Barton 288 Pressure Switch Inspected,Recalibr & Functionally Tested for Repeatability + (ML18025A934)
- 05000296/LER-1980-019, Forwards LER 80-019/03L-0 + (ML18025A935)
- ML18025A936 + (ML18025A936)
- 05000296/LER-1980-019-03, /03L-0:on 800527,during Normal Operation, Discovered Drywell Sump Flow Transmitter FT-77-16 Had Output Signal Shift.Cause Unknown.Transmitter Replaced & Instrument Loop Calibr + (ML18025A937)
- ML18025A938 + (ML18025A938)
- 05000260/LER-1980-025, Forwards LER 80-025/01T-0 + (ML18025A939)
- ML18025A940 + (ML18025A940)
- 05000260/LER-1980-025-01, /01T-0:on 800617,during Normal Operation Discovered That Spare Dresser Industries Safety Valve Had Guide W/Cracks.Caused During Initial Pouring of Casting & Subsequent Cooling.Addl Valves Will Be Inspected for Cracks + (ML18025A941)
- 05000260/LER-1980-023, Forwards LER 80-023/03L-0 + (ML18025A942)
- ML18025A943 + (ML18025A943)
- 05000260/LER-1980-023-03, /03L-0:on 800607,during Normal operation,2A Reactor Recirculation Motor Generator Set Tripped Due to Generator Stator Temp High Relay Actuation.Probable Cause Was Loose Wire Caused by Vibration + (ML18025A944)
- 05000260/LER-1980-022, Forwards LER 80-022/03L-0 + (ML18025A945)
- ML18025A946 + (ML18025A946)
- 05000260/LER-1980-022-03, /03L-0:on 800602,while Performing S.I. 4.1.A-14, Turbine First Stage Pressure Permissive Pressure Switches PS-1-81 a & B & PS-1-91 a & B Setpoints Exceeded Tech Spec Limits.Caused by Switch Drifting + (ML18025A947)
- 05000296/LER-1980-023, Forwards LER 80-023/01T-0 + (ML18025A948)
- ML18025A949 + (ML18025A949)
- 05000296/LER-1980-023-01, /01T-0:on 800617,during Normal Operation,Spare Dresser Industries Safety Valve Was Discovered W/Cracks in Guide.Caused by Initial Pouring of Casting & Cooling.Spare Valves Will Be Inspected for Cracks + (ML18025A950)
- IR 05000260/1980025 + (ML18025A951)
- ML18025A951 + (ML18025A951)
- 05000296/LER-1980-020, Forwards LER 80-020/03L-0 + (ML18025A952)
- ML18025A953 + (ML18025A953)
- 05000296/LER-1980-020-03, /03L-0:on 800609,during Normal operations,3B Diesel Generator Auxiliary Oil Pump Motor Tripped Twice. Caused by Failure of Hoover Model 6203z Sealed Bearings. Motor Replaced.Bearings Replaced Every Two Yrs + (ML18025A954)
- 05000296/LER-1980-021, Forwards LER 80-021/03L-0 + (ML18025A955)
- ML18025A956 + (ML18025A956)
- ML18025A957 + (ML18025A957)
- 05000296/LER-1980-021-03, /03L-0:on 800609,during Normal Operation,Reactor Core Isolation Cooling Turbine Tripped on Overspeed Due to Loss of Speed Control.Caused by Failure of Voltage Suppressor CR-1,type S-240,in Egm Box + (ML18025A958)
- IR 05000296/1980024 + (ML18025A959)
- ML18025A959 + (ML18025A959)
- ML18025A960 + (ML18025A960)
- ML18025A961 + (ML18025A961)
- ML18025A962 + (ML18025A962)
- ML18025A963 + (ML18025A963)
- 05000296/LER-1980-022, Forwards LER 80-022/03L-0 + (ML18025A964)
- ML18025A965 + (ML18025A965)
- 05000296/LER-1980-022-03, /03L-0:on 800616,while Performing SI 4.1.A-14, Turbine first-stage Pressure Permissive & Pressure Switches PS-1-91 a & B Exceeded Limits.Caused by Setpoint Drift. Switches Recalibr + (ML18025A966)
- ML18025A972 + (ML18025A972)
- ML18025A973 + (ML18025A973)
- ML18025A974 + (ML18025A974)
- ML18025A975 + (ML18025A975)
- ML18025A976 + (ML18025A976)
- ML18025A977 + (ML18025A977)
- ML18025A978 + (ML18025A978)
- ML18025A979 + (ML18025A979)
- ML18025A980 + (ML18025A980)
- ML18025A981 + (ML18025A981)
- ML18025A982 + (ML18025A982)
- ML18025A983 + (ML18025A983)
- ML18025A984 + (ML18025A984)
- ML18025A985 + (ML18025A985)
- PNO-II-80-119, on 800628,76 Control Rods Failed to Fully Insert During Routine Shutdown.Manual Scrams Failed to Effect Repair.Auto Scram Caused Full Insertion.Cause Being Investigated.Confirmation of Action Ltr Issued + (ML18025A986)