Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML18025A879 + (ML18025A879)
- IR 05000259/1980006 + (ML18025A881)
- ML18025A882 + (ML18025A882)
- ML18025A883 + (ML18025A883)
- IR 05000259/1980009 + (ML18025A885)
- ML18025A887 + (ML18025A887)
- 05000260/LER-1980-020, Forwards LER 80-020/03L-0 + (ML18025A889)
- ML18025A890 + (ML18025A890)
- 05000260/LER-1980-020-03, /03L-0:on 800421,high Pressure Switch PS-3-22D Found Exceeding Setpoint During Normal Operation.Caused by Setpoint Drift.Barksdale BST-A12SS Switch Inspected,Calibr & Functionally Tested + (ML18025A891)
- ML18025A899 + (ML18025A899)
- ML18025A900 + (ML18025A900)
- ML18025A901 + (ML18025A901)
- 05000296/LER-1980-017, Forwards LER 80-017/03L-0 + (ML18025A902)
- ML18025A903 + (ML18025A903)
- 05000296/LER-1980-017-03, /03L-0:on 800404,after Running SI 4.11.c.3 & .4, Last Page of SI Was Missing.Last Page Had Not Been Performed 3 of Last 4 Months,So One Fire Protection Zone Not Tested Monthly.Caused by Misplacement.Page Replaced + (ML18025A904)
- 05000296/LER-1980-012, Forwards LER 80-012/03L-0 + (ML18025A905)
- ML18025A906 + (ML18025A906)
- 05000296/LER-1980-012-03, /03L-0:on 800509,while Performing SI 4.2.A-3,LIS- 3-56a Switch 2 & LIS-3-56b Switch 2 Failed to Operate.Caused by Stuck Switch Contacts.Switch Contacts Cleaned & Checked for Proper Setpoint + (ML18025A907)
- 05000260/LER-1980-021, Forwards LER 80-021/03L-0 + (ML18025A908)
- ML18025A909 + (ML18025A909)
- 05000260/LER-1980-021-03, /03L-0:on 800506,during Routine Shutdown, Particulate Channel 2-RR-90-249 Was Erratic & Declared Inoperable.Caused by Failure of Recorder Amplifier.Amplifier Replaced.Failure Attributed to Normal Aging + (ML18025A910)
- ML18025A911 + (ML18025A911)
- ML18025A912 + (ML18025A912)
- 05000296/LER-1980-015, Forwards LER 80-015/03L-0 + (ML18025A913)
- ML18025A914 + (ML18025A914)
- ML18025A915 + (ML18025A915)
- 05000296/LER-1980-015-03, /03L-0:on 800512,3B RHR Pump Cooling Water Flow Determined Inadequate Per TS 3.5.B.1(2) & 3.5.BB.5.Caused by Apparent Restriction in Cooling Water Piping.Exchanger Removed & Flushed + (ML18025A916)
- 05000296/LER-1980-014, Forwards LER 80-014/03L-0 + (ML18025A917)
- ML18025A919 + (ML18025A919)
- 05000296/LER-1980-014-03, /03L-0:on 800512,during Normal Operation,Reactor Core Isolation Cooling Tripped on Overspeed Due to Loss of Speed Control.Caused by Diode in Egm Box Failure Due to End of Life.Egm Box Replaced & Calibr + (ML18025A920)
- 05000296/LER-1980-016, Forwards LER 80-016/03L-0 + (ML18025A921)
- ML18025A922 + (ML18025A922)
- 05000296/LER-1980-016-03, /03L-0:on 800513,following Completion of Flow Test on Diesel Generator Heat Exchanger 3D,cooling Water Found Inadequate Per Tech Spec 3.5.B.2.Apparently Caused by Restriction in Cooling Water Piping.Water Lines Flushed + (ML18025A923)
- 05000296/LER-1980-013, Forwards LER 80-013/03L-0 + (ML18025A926)
- ML18025A928 + (ML18025A928)
- 05000296/LER-1980-013-03, /03L-0:on 800517,LIS-3-56B Switch 2 Failed to Operate.Cause Attributed to Stuck Switch Contacts.Leaf Switches Inside Level Indicating Switch Replaced & Checked for Proper Setpoint & Repeatability + (ML18025A930)
- 05000296/LER-1980-018, Forwards LER 80-018/03L-0 + (ML18025A931)
- ML18025A932 + (ML18025A932)
- ML18025A933 + (ML18025A933)
- 05000296/LER-1980-018-03, /03L-0:on 800519,reactor Low Pressure Switch PS-3-74B SW 1,found Out of Tolerance.Caused by Instrument Setpoint Drift.Barton 288 Pressure Switch Inspected,Recalibr & Functionally Tested for Repeatability + (ML18025A934)
- 05000296/LER-1980-019, Forwards LER 80-019/03L-0 + (ML18025A935)
- ML18025A936 + (ML18025A936)
- 05000296/LER-1980-019-03, /03L-0:on 800527,during Normal Operation, Discovered Drywell Sump Flow Transmitter FT-77-16 Had Output Signal Shift.Cause Unknown.Transmitter Replaced & Instrument Loop Calibr + (ML18025A937)
- ML18025A938 + (ML18025A938)
- 05000260/LER-1980-025, Forwards LER 80-025/01T-0 + (ML18025A939)
- ML18025A940 + (ML18025A940)
- 05000260/LER-1980-025-01, /01T-0:on 800617,during Normal Operation Discovered That Spare Dresser Industries Safety Valve Had Guide W/Cracks.Caused During Initial Pouring of Casting & Subsequent Cooling.Addl Valves Will Be Inspected for Cracks + (ML18025A941)
- 05000260/LER-1980-023, Forwards LER 80-023/03L-0 + (ML18025A942)
- ML18025A943 + (ML18025A943)
- 05000260/LER-1980-023-03, /03L-0:on 800607,during Normal operation,2A Reactor Recirculation Motor Generator Set Tripped Due to Generator Stator Temp High Relay Actuation.Probable Cause Was Loose Wire Caused by Vibration + (ML18025A944)
- 05000260/LER-1980-022, Forwards LER 80-022/03L-0 + (ML18025A945)