Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML11287A189 + (ML11287A189)
- ML11287A192 + (ML11287A192)
- ML11287A194 + (ML11287A194)
- ML11287A195 + (ML11287A195)
- ML11287A207 + (ML11287A207)
- ML11287A211 + (ML11287A211)
- ML11287A227 + (ML11287A227)
- ML11287A251 + (ML11287A251)
- ML11287A252 + (ML11287A252)
- ML11287A253 + (ML11287A253)
- ML11287A254 + (ML11287A254)
- ML11287A255 + (ML11287A255)
- ML11287A256 + (ML11287A256)
- ML11287A310 + (ML11287A310)
- ML11287A313 + (ML11287A313)
- ML11287A322 + (ML11287A322)
- ML112880138 + (ML112880138)
- ML112880139 + (ML112880139)
- ML112900077 + (ML112900077)
- ML112900087 + (ML112900087)
- ML112900101 + (ML112900101)
- L-11-335, Supplemental Information for License Amendment Request Regarding Offsite Electric Power System Acceptability Until December 12. 2011 + (ML112900202)
- L-11-287, 10 CFR 50.55a Request VR-1, Revision 1, Align Valve Testing Frequencies to NUREG-1482 Provision + (ML112900204)
- NG-11-0383, Registration of Independent Spent Fuel Storage Installation Casks + (ML112900206)
- 05000263/LER-1980-007-01, /01T-0:on 800303,during Refuel Shutdown,Cable Routing for HPCI & Automatic Depressurization Sys Cables Identified Lack of Physical Separation Between Automatic Depressurization Sys Cables & Ones for Div of HPCI Sensors + (ML112900662)
- ML112900663 + (ML112900663)
- 05000263/LER-1980-013-01, /01T-0:on 800309,during Refueling Operations,Rod Withdrawn Block Not Received When Refueling Bridge Traversed Core.Caused by Actuating Arm Out of Adjustment.Components Readjusted & Interlocks Tested Prior to Refueling + (ML112900665)
- ML112900666 + (ML112900666)
- 05000263/LER-1980-011-01, /01T-0:on 800306,during Refueling Outage,Repairs to Outboard MSIV Stop Valve Revealed Flow Path Between Secondary Containment & Turbine Bldg When MSIV Poppet Was Pulled.Caused by Lack of Preventive Procedure Controls + (ML112900668)
- ML112900669 + (ML112900669)
- 05000263/LER-1980-006-03, /03L-0:on 800226,during Refueling Outage,Seven of Main Steam Line Area Temp Switches Found to Trip Above Required Level.Caused by Setpoint Drift.Switches Recalibr + (ML112900678)
- ML112900679 + (ML112900679)
- 05000263/LER-1980-015-01, /01T-0:on 800317,during Refueling Outage & Insp Required by IE Bulletin 79-01B,unqualified Splices Found in Power Cables for Inboard MSIV Solenoid Valves.Cause Not Stated.Splices Replaced W/Qualified Matls + (ML112900680)
- ML112900681 + (ML112900681)
- 05000263/LER-1980-016-01, /01T-0:on 800327,during Refueling,Supports for SRV Pneumatic Supply Sys Would Not Meet Seismic Class I Requirements.Caused by Inadequate Design & Installation of Sys.Sys Was Upgraded to Satisfy Requirements + (ML112900685)
- ML112900686 + (ML112900686)
- 05000263/LER-1980-017-01, /01T-0:on 800328,Bechtel Power Corp Notified Util That Control Rod Driveline Hydraulic Piping Frame Supports Would Not Meet OBE Stress Limits.Caused by Eds Computer Code Error.Supports Modified + (ML112900707)
- ML112900708 + (ML112900708)
- 05000263/LER-1980-018-03, /03L-0:on 800411,during Routine Operator Insp, Attachment Weld of Ripple to Level Switch Float Chamber Assembly on Moisture Separator Level Switch LS-1188 Found Cracked.Caused by Improper Weld Procedure + (ML112900722)
- ML112900723 + (ML112900723)
- 05000263/LER-1980-020-03, /03L-0:on 800427,during post-maint Startup of Reactor Recirculation Sys,Inaccessible Recirculation Valve Motor Failed.Cause Not Stated.Motor Is Limitorque Type SMB-2 W/Magnetic Brake + (ML112900745)
- ML112900746 + (ML112900746)
- ML112900749 + (ML112900749)
- 05000263/LER-1980-021-03, /03L-0:on 800515,during Normal Startup,Reactor Core Isolation Cooling Control Power Fuse Opened.Caused by Shorted Relay Coil in Circuit Due to Ac Relay Inadvertently Installed by Maint Personnel.Relay Replaced + (ML112900751)
- ML112900752 + (ML112900752)
- 05000263/LER-1980-022-03, /03L-0:on 800529,primary Containment Oxygen Concentration Exceeded 5% by Weight Tech Spec Limit.Caused by Open Svc Air Isolation Valve to Drywell.Procedures Have Been Revised to Assure Proper Valve Positioning + (ML112900754)
- ML112900755 + (ML112900755)
- 05000263/LER-1980-023-03, /03L-0:on 800601,air Ejector Offgas Radiation Monitors Dropped to About 20% Normal for About 40 Minutes. Caused by Mechanical Vacuum Pump Offgas Sample Valve Being Incorrectly Opened.Valve Now Wired Shut + (ML112900760)
- ML112900761 + (ML112900761)
- 05000263/LER-1979-020-03, /03L-0:on 791030,reactor Core Isolation Cooling Isolation Temp Switch Found to Trip Above Allowable Setpoint.Caused by Setpoint Drift.Switch Replaced + (ML112900790)
- 05000263/LER-1979-009-03, /03L-0 on 790404:steam Leak Found in 90 Degree Elbow in 1-inch Core Isolation Cooling Steam Supply Drain Pot Condenser Line.Caused by Erosion Due to High Velocity Steam from Leaking Valve.Hole Patched.Repairs Planned + (ML112900836)