The following is a summary from the DiabloThe following is a summary from the Diablo Canyon Part 21 Report submitted:</br>On May 18, 2020, Pacific Gas and Electric (PG&E) completed its evaluation of a deviation concerning commercial-grade thermocouples dedicated at Diablo Canyon Power Plant. The original defect was discovered on April 10, 2020 during bench testing where two separate thermocouples exhibited leakage during static pressure testing. The two thermocouples were tested as part of a spare safety-related pump motor refurbishment. Upon subsequent review, it was identified that a pressure boundary test had not been required as part of the dedication process, but should have for its safety-related application. These components were not installed in the plant and there was no risk to the health and safety of the public. Thermocouples from the same batch have been quarantined to prevent installation, and it has been confirmed that none of the suspect batch of thermocouples have been installed in the plant. The thermocouple replacement part evaluation has been revised to include a pressure boundary test as part of the commercial-grade dedication prior to acceptance.</br>Thermocouple Make and Model: March Bellofram 3060-2-JJ-2-13.00-0-1-000</br>The NRC Resident Inspectors have been notified.</br>This report only affects Diablo Canyon Power Plant.</br>The person informing the Nuclear Regulatory Commission:</br>Kenneth Cortese</br>Quality Verification Director</br>Diablo Canyon Power Plant</br>Pacific Gas and Electric</br>805-440-367wer Plant Pacific Gas and Electric 805-440-367  +
18:57:00, 18 May 2020  +
54,721  +
14:07:00, 20 May 2020  +
18:57:00, 18 May 2020  +
The following is a summary from the DiabloThe following is a summary from the Diablo Canyon Part 21 Report submitted:</br>On May 18, 2020, Pacific Gas and Electric (PG&E) completed its evaluation of a deviation concerning commercial-grade thermocouples dedicated at Diablo Canyon Power Plant. The original defect was discovered on April 10, 2020 during bench testing where two separate thermocouples exhibited leakage during static pressure testing. The two thermocouples were tested as part of a spare safety-related pump motor refurbishment. Upon subsequent review, it was identified that a pressure boundary test had not been required as part of the dedication process, but should have for its safety-related application. These components were not installed in the plant and there was no risk to the health and safety of the public. Thermocouples from the same batch have been quarantined to prevent installation, and it has been confirmed that none of the suspect batch of thermocouples have been installed in the plant. The thermocouple replacement part evaluation has been revised to include a pressure boundary test as part of the commercial-grade dedication prior to acceptance.</br>Thermocouple Make and Model: March Bellofram 3060-2-JJ-2-13.00-0-1-000</br>The NRC Resident Inspectors have been notified.</br>This report only affects Diablo Canyon Power Plant.</br>The person informing the Nuclear Regulatory Commission:</br>Kenneth Cortese</br>Quality Verification Director</br>Diablo Canyon Power Plant</br>Pacific Gas and Electric</br>805-440-367wer Plant Pacific Gas and Electric 805-440-367  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:00:00, 20 May 2020  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
16:37:46, 15 January 2021  +
14:07:00, 20 May 2020  +
1.799 d (43.17 hours, 0.257 weeks, 0.0591 months)  +
18:57:00, 18 May 2020  +
Part 21 Report - Inadequate Dedication of Replacement Thermocouples  +