The inspectors identified a non-cited violThe inspectors identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XI, Test Controls, for the licensees failure to ensure that the stations in-service testing program for main steam isolation valves (MSIVs) incorporated the requirements and acceptance limits contained in applicable design documents. Specifically, the licensees in-service procedures did not direct testing of the valves be performed at the minimum required pressure and this resulted in the licensees failure to identify two degraded MSIVs during in-service testing. The licensee entered this issue into the corrective action program as Condition Report CR-2018-003229.rogram as Condition Report CR-2018-003229.  +
23:59:59, 30 June 2018  +
05000445  +  and 05000446  +
23:59:59, 30 June 2018  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:35:30, 10 September 2018  +
23:59:59, 30 June 2018  +
Failure to Incorporate Design Information Into System Test Procedures  +