Browse wiki

Jump to navigation Jump to search
The inspectors identified a Green,non-citeThe inspectors identified a Green,non-cited violation of 10CFR 50, Appendix B, Criterion XVI, Corrective Action, associated with the licensees failure to take corrective action for the identified cause of a significant condition adverse to quality. Specifically, a feedwater bypass control valve vibrated open resulting in a turbine trip and initiation of auxiliary feedwater. The licensee determined that the cause was an inadequate procedure for performing maintenance on the feedwater bypass control valves, but failed to correct the inadequate procedure after identifying it as the cause of a control valve failure and a turbine trip. This finding was entered into the licensees corrective action program as Condition Report CR-2018-000959.rogram as Condition Report CR-2018-000959.  +
23:59:59, 31 March 2018  +
05000445  +  and 05000446  +
23:59:59, 31 March 2018  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
22:35:01, 10 September 2018  +
23:59:59, 31 March 2018  +
Failure to Correct a Significant Condition Adverse to Quality  +