Browse wiki

Jump to navigation Jump to search
The inspectors identified a finding of verThe inspectors identified a finding of very low safety significance and associated Non-Cited Violation (NCV) of 10 CFR Part 50, Appendix B, Criterion III, Design Control , for failure to adequately evaluate the capability of motor control starter contactors to operate during design basis degraded voltage conditions. Specifically, the licensee did not analyze all circuit elements of resistance and failed to incorporate the latest results of calculated plant bus voltages. The performance deficiency was determined to be more than minor because it was associated with the Mitigating System Cornerstone attribute of equipment performance and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as of very low safety significance (Green) because the finding involved a design or qualification deficiency that did not result in a loss of operability. Specifically, the licensee performed an operability evaluation taking into account all resistances in the circuit, the latest load flow analysis and test data and concluded there was sufficient voltage available. This finding has a cross-cutting aspect in the area of Resources for failure to ensure complete, accurate, and up-to-date design documentation, procedures, work packages and correct labeling of components.ckages and correct labeling of components.  +
23:59:59, 31 December 2011  +
05000440  +
23:59:59, 31 December 2011  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
19:05:59, 30 September 2017  +
23:59:59, 31 December 2011  +
Inadequate Control Circuit Voltage Calculation for Safety- Related Motor Starter Contactors  +