The inspectors identified a Green, NCV of The inspectors identified a Green, NCV of 10 CFR 50, Appendix B, Criterion XVI, Corrective Actions, for Dominion\'s failure to promptly identify and correct the source of a reactor coolant system (RCS) pressure boundary leak from July 3, 2009, through July 13, 2009. Dominion subsequently repaired the leak and returned to 100 percent power. The inspectors determined that Dominion\'s failure to promptly identify and correct the cause of pressure boundary leakage is a performance deficiency that was reasonably within Dominion\'s ability to foresee and correct and should have been prevented. This issue is more than minor because the issue is similar to NRC Inspection Manual Chapter (IMC) 0612, Appendix E, and minor example 2.g. The inspectors determined that the issue affected the Initiating Events Cornerstone objective to limit the likelihood of those events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. The inspectors concluded that this condition, assuming the worst case degradation, would not have affected other mitigating systems resulting in a total loss of their safety function. Accordingly, the finding was determined to be of very low safety significance (Green) using IMC 609, Attachment 0609.004, Phase 1 Screening Worksheet. The inspectors determined that this issue had a crosscutting aspect in the Problem Identification and Resolution cross-cutting area, Corrective Action Program component, because Dominion did not identify the pressure boundary leakage completely, accurately, and in a timely manner commensurate with its safety significance. (P.1 (a))te with its safety significance. (P.1 (a))  +
23:59:59, 30 September 2010  +
05000336  +  and 05000423  +
23:59:59, 30 September 2010  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:40:11, 21 February 2018  +
23:59:59, 30 September 2010  +
Failure to Promptly Identify and Correct the Source of a Unit 2 RCS Pressure Boundary Leak  +