Browse wiki
Jump to navigation
Jump to search
Green. The team identified a Green finding … Green. The team identified a Green finding for the failure to meet the surveillance standards of IEEE 308-1971, Criteria for Class 1E Electric Systems for Nuclear Power Generating Stations, Section 5.2.3, Preferred Power Supply. Specifically, from 2001 to December 2, 2016, the licensee failed to monitor the operation of the voltage regulator/load tap changer functions on startup transformers 1, 2, and 3. In response to this issue, the licensee provided reasonable assurance that the voltage regulator/load tap changer was operating properly based on review of plant computer voltage plot data following an Arkansas Nuclear One, Unit 1 trip that occurred on December 14, 2015. This finding was entered into the licensees corrective action program as Condition Reports CR-ANO-C-2016-4777, CR-ANO-C-2016-4879, and CR-ANO-C-2016-5015. The team determined that the failure to monitor startup transformers 1, 2, and 3 voltage regulator/load tap changers to the extent that they are shown to be ready to perform their intended function, in accordance with IEEE Standard 308-1971, was a performance deficiency. The finding was determined to be more than minor because it was associated with the equipment performance attribute of the Mitigating Systems Cornerstone and affected the cornerstone objective of ensuring the availability, reliability, and capability of mitigating systems to respond to initiating events to prevent undesirable consequences. Specifically, the failure to monitor the adequacy of the voltage supplied from startup transformers 1, 2, and 3 voltage regulator/load tap changer did not ensure that offsite power would be available to perform its necessary functions to provide power to the safety-related mitigation equipment. In accordance with Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power, dated June 19, 2012, Exhibit 2, Mitigating Systems Screening Questions, the issue screened as having very low safety significance (Green) because it was a design or qualification deficiency that did not represent a loss of operability or functionality; did not represent an actual loss of safety function of the system or train; did not result in the loss of one or more trains of non-technical specification equipment; and did not screen as potentially risk-significant due to seismic, flooding, or severe weather. This finding did not have a cross-cutting aspect because the performance deficiency did not reflect current licensee performance. not reflect current licensee performance.
23:59:59, 31 December 2016 +
23:59:59, 31 December 2016 +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +, 05000313/FIN-2016008-03 +...
IEEE 308-1971 + and IEEE 308 +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
12:56:28, 25 September 2017 +
23:59:59, 31 December 2016 +