Browse wiki

Jump to navigation Jump to search
The team identified a non-cited violation The team identified a non-cited violation of 10 CFR 50.63, Loss of all alternating current power, for failure to ensure Regulatory Guide 1.155, Station Blackout commitments were implemented in calculations for restoring off-site power. The licensee entered this deficiency into their corrective action program for resolution. The licensees failure to maintain calculations to assure adequate voltage for the remote closing of switchyard breakers during a station blackout event is a performance deficiency. The team determined that the finding is more than minor because it adversely affected the design control attribute of the mitigating reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding is of very low safety significance (Green) using the SDP because it did not represent a loss of system or safety function. A cross-cutting aspect was not identified because the finding does not represent current performance.ng does not represent current performance.  +
23:59:59, 30 September 2010  +
05000302  +
23:59:59, 30 September 2010  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
21:44:53, 8 October 2017  +
23:59:59, 30 September 2010  +
Failure to Incorporate Requirements of Recovering from a Station Blackout into Calculations  +