The NRC identified a non-cited violation oThe NRC identified a non-cited violation of 10 CFR 50, Appendix B, Criterion III, Design Control, for the licensees failure to correctly evaluate the heat-up of the Main Steam Valve House (MSVH), which contains the auxilliary feedwater pumps as well as other safety-related mitigating systems. The violation was entered into the licensees corrective action program as Condition Reports 1077007 and 1077684 and the licensee conducted a preliminary calculation and evaluation to determine the actual temperature increase and determined that the equipment located in MSVH remained operable. The performance deficiency was determined to be more than minor because it was associated with the Design Control attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to evaluate worst-case design conditions resulted in a decreased margin for reliability and capability of mitigating systems contained in the MSVH. The inspectors determined the finding to be of very low safety significance (Green) because the finding was a deficiency affecting the qualification of a mitigating structure, system, or component (SSC), and the SSC maintained its operability or functionality. This finding was not assigned a cross-cutting aspect because the underlying cause was a legacy issue and not indicative of current performance.and not indicative of current performance.  +
23:59:59, 30 September 2017  +
05000280  +  and 05000281  +
23:59:59, 30 September 2017  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
03:20:14, 17 November 2017  +
23:59:59, 30 September 2017  +
Failure to Evaluate Design Maximum Ambient Temperature Effect on Main Steam Valve House  +