The inspectors identified a finding of verThe inspectors identified a finding of very low safety significance and associated non-cited violation of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, because the licensee failed to establish routine testing procedure that demonstrated room temperatures would be maintained. Specifically, on March 29, 2012, the inspectors identified that the licensee failed to establish routine testing procedure that demonstrated the air flows for emergency diesel generators G-01 and G-02 ventilation systems would perform adequately to ensure that the room temperatures would be maintained. The licensee entered this issue into its corrective action program, and corrective actions included performance of air flow measurements on the fan units, creation of a preventive maintenance requirement for taking periodic flow measurements, and assessment of the identified issue through a condition evaluation. The finding was determined to be more than minor in accordance with Inspection Manual Chapter 0612, Appendix B, Issue Screening, dated December 24, 2009. The inspectors determined that this finding was more than minor because it was associated with the Mitigating Systems Cornerstone attribute for design control. Specifically, it adversely affected the Mitigating System Cornerstone objective to ensure the reliability of systems that respond to initiating events to prevent undesirable consequences. This finding has a cross-cutting aspect in the area of human performance, decision-making. Specifically, the licensee did not use conservative assumptions regarding the verification of the proper air flow through the safety-related gravity dampers in the emergency diesel generators G-01 and G-02 roomsency diesel generators G-01 and G-02 rooms  +
23:59:59, 30 June 2012  +
05000266  +  and 05000301  +
23:59:59, 30 June 2012  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:45:34, 21 February 2018  +
23:59:59, 30 June 2012  +
Failure to Establish Emergency Diesel Generator Ventilation System Testing  +