Semantic search

Jump to navigation Jump to search
 Entered dateEvent description
ENS 5166319 January 2016 17:42:00

On January 19, 2016, while reviewing outage data, plant staff recognized that anomalous data collected in October, 2015, for the 21 Auxiliary Feed Pump time response loop resulted in an unanalyzed condition. Preliminary investigation has revealed that the condition most likely existed since April 20, 2015, when maintenance activities were performed on the auxiliary feedwater pump discharge pressure transmitter. Consequently, there were multiple instances when one of the other auxiliary feedwater pumps was removed from service, thus creating a condition which did not meet the accident analysis assumptions for auxiliary feedwater flow initial response. This event is being reported under the requirements of 10 CFR 50.72(b)(3)(ii)(B) as 'the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety.' This condition was corrected on November 20, 2015. The auxiliary feedwater pump discharge pressure transmitter instrument isolation valve was inadvertently left closed after the April 20, 2015 maintenance. The licensee has notified the NRC Resident Inspector and will notify the State of New Jersey, State of Delaware, and the local township.

  • * * RETRACTED ON 3/10/16 AT 1647 EST FROM JACK OSBORNE TO DONG PARK * * *

This event is being retracted. An engineering review determined that while the auxiliary feedwater flow loop response time test results did not meet the procedural acceptance criteria, the accident analysis assumptions remained valid. The ATWS (Anticipated Transient Without Scram) was the limiting accident, and the loop response time results were still bounded by the existing analyses. The failed loop response time did result in a condition prohibited by TS which will be reported in a Licensee Event Report (LER). This condition has been documented in the licensee's Corrective Action Program. The licensee has notified the NRC Resident Inspector. Notified R1DO (Dimitriadis).

ENS 505083 October 2014 17:44:00A Supplemental Supervisor failed a random Fitness For Duty test as determined by the Medical Review Officer. Unescorted access has been revoked pending review. Work performance investigation will be conducted. This event is being reported in accordance with 10CFR26.719(b)(2)(i). The licensee will notify the State of New Jersey and Delaware. The licensee has notified the NRC Resident Inspector.