ML20027A332 | 27 October 1978 | RO#77-054/03X-1 on 771102:CRD H-5 Uncoupled During Functional Testing Caused by Unlatched Inner Filter & Abnormally Long Uncoupling Rod.Inner Filter Pull Test in Reassembly Procedure & Improved QA Coverage Incorporated | |
ML19352A117 | 16 December 1974 | Ro:On 741213,during Refueling Outage Circumferential Cracks Found in Unit 2 Stainless Steel Loop B Bypass Line.Cause Not Stated.Corrective Action Being Reviewed | |
ML20003C378 | 27 May 1974 | Ro:On 740527,diesel Generator 2/3 Declared Inoperable Due to Unstable Load & Machine Inability to Carry Full Load. Cause Not Stated.Required Surveillance & Investigation Initiated | |
ML19352A119 | 29 September 1972 | Ro:On 720919,during Routine Calibr of Reactor Low Pressure Permissive Switches,Two Setpoints Drifted Above Tech Specs Value of 350 Psig.Switches Reset & Will Be Sent to Ctr of Trip Setting Span in Future |