HL-2260, NPDES Noncompliance Notification:On 920529,all 3 Unit 1 Cooling Towers Were Overflowing.Caused by Restriction in Cooling Tower Return Flow.Cooling Tower Screens Cleaned11 June 1992NPDES Noncompliance Notification:On 920529,all 3 Unit 1 Cooling Towers Were Overflowing.Caused by Restriction in Cooling Tower Return Flow.Cooling Tower Screens Cleaned
ML20087A5033 January 1992NPDES Noncompliance Notification:On 911230 Sample Indicated That Chlorinated Water Was Being Discharged to Altamaha River.Caused by Failure of Valve Which Isolates Chlorine Addition Sys from Svc Water Sys Intake.Valve Replaced
HL-2002, NPDES Noncompliance Notification:On 911230,chlorinated Water Discharged Into Altamaha River Due to Internal Failure of Valve Which Isolates Chlorine Addition Sys from Svc Water Sys Intake.Failed Valve Replaced3 January 1992NPDES Noncompliance Notification:On 911230,chlorinated Water Discharged Into Altamaha River Due to Internal Failure of Valve Which Isolates Chlorine Addition Sys from Svc Water Sys Intake.Failed Valve Replaced
HL-1925, NPDES Noncompliance Notification:On 911107,sample from Cooling Tower Basin Recorded Value Greater than 2 Ppm Free Available Chlorine/Total Residual Chlorine.Caused by Malfunction of Valve Torque Switch.Valve Manually Secured15 November 1991NPDES Noncompliance Notification:On 911107,sample from Cooling Tower Basin Recorded Value Greater than 2 Ppm Free Available Chlorine/Total Residual Chlorine.Caused by Malfunction of Valve Torque Switch.Valve Manually Secured
ML20133F24030 July 1985NPDES Noncompliance Notification:On 850620,6,000 Gallons of Glycol Solution Discharged Into Altamaha River.State of Ga,Environ Protection Div Granted Util Permission for Disposal on 850619
ML19320A70127 June 1980NPDES Noncompliance Notification:On 800619,at Full Power Operation,Circulating Water Chlorination Sequence Was Automatically Activated,Resulting in Release of Free Available Chlorine in Cooling Water Blowdown
ML19323E41816 May 1980NPDES Noncompliance Notification:On 800512,facility Circulating Overflow Exceeded NPDES Limit of 0.2 Ppm Average Residual Chlorine & 0.5 Ppm Max Residual Chlorine. Chlorine Analyzer Repaired & Returned to Svc