ML20027A33227 October 1978RO#77-054/03X-1 on 771102:CRD H-5 Uncoupled During Functional Testing Caused by Unlatched Inner Filter & Abnormally Long Uncoupling Rod.Inner Filter Pull Test in Reassembly Procedure & Improved QA Coverage Incorporated
ML19352A11716 December 1974Ro:On 741213,during Refueling Outage Circumferential Cracks Found in Unit 2 Stainless Steel Loop B Bypass Line.Cause Not Stated.Corrective Action Being Reviewed
ML20003C37827 May 1974Ro:On 740527,diesel Generator 2/3 Declared Inoperable Due to Unstable Load & Machine Inability to Carry Full Load. Cause Not Stated.Required Surveillance & Investigation Initiated
ML19352A11929 September 1972Ro:On 720919,during Routine Calibr of Reactor Low Pressure Permissive Switches,Two Setpoints Drifted Above Tech Specs Value of 350 Psig.Switches Reset & Will Be Sent to Ctr of Trip Setting Span in Future