RS-22-073, Supplemental Information Regarding License Amendment Request -Adoption of Technical Specification Task Force (TSTF) Traveler TSTF-501, Revision 1, Relocate Stored Fuel Oil and Lube.

From kanterella
(Redirected from RS-22-073)
Jump to navigation Jump to search

Supplemental Information Regarding License Amendment Request -Adoption of Technical Specification Task Force (TSTF) Traveler TSTF-501, Revision 1, Relocate Stored Fuel Oil and Lube.
ML22139A152
Person / Time
Site: Byron, Braidwood  
(NPF-037, NPF-066, NPF-072, NPF-077)
Issue date: 05/19/2022
From: Lueshen K
Constellation Energy Generation
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
RS-22-073
Download: ML22139A152 (7)


Text

4300 Winfield Road Warrenville, IL 60555 630 657 2000 Office 10 CFR 50.90 RS-22-073 May 19, 2022 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Braidwood Station, Units 1 and 2 Renewed Facility Operating License Nos. NPF-72 and NPF-77 NRC Docket Nos. 50-456 and 50-457 Byron Station, Units 1 and 2 Renewed Facility Operating License Nos. NPF-37 and NPF-66 NRC Docket Nos. 50-454 and 50-455

Subject:

Supplemental Information regarding License Amendment Request -Adoption of Technical Specification Task Force (TSTF) Traveler TSTF-501, Revision 1, "Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control"

Reference:

Letter from K. Lueshen (Constellation Energy Generation, LLC) to Nuclear Regulatory Commission (NRC), "License Amendment Request -Adoption of Technical Specification Task Force (TSTF) Traveler TSTF-501, Revision 1, "Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control," dated April 21, 2022 (ML22111A300)

In the referenced letter, Constellation Energy Generation, LLC (CEG) submitted its application to adopt Technical Specification Task Force (TSTF) Traveler 501, Revision 1, "Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control" for Braidwood and Byron stations.

During the acceptance review period, an editorial correction was identified with the submitted Technical Specification pages contained in the application. This letter supplements the identified pages with the editorial corrections addressed.

There are no regulatory commitments contained in this request.

This letter does not affect CEG's conclusion that the proposed change presents no significant hazards consideration under the standards set forth in 10 CFR 50.92.

U.S. Nuclear Regulatory Commission May 19, 2022 Page 2 In accordance with 10 CFR 50.91, "Notice for public comment; State consultation," paragraph (b), CEG is transmitting a copy of this application and its attachments to the designated State of Illinois official.

Should you have any questions concerning this submittal, please contact Jason Taken at (630) 657-3660.

I declare under penalty of perjury that the foregoing is true and correct. Executed on the 19th May, 2022.

Respectfully, Kevin Lueshen Senior Manager - Licensing Constellation Energy Generation, LLC

Lueshen, Kevin Digitally signed by Lueshen, Kevin Date: 2022.05.19 10:41:11

-05'00'

U.S. Nuclear Regulatory Commission May 19, 2022 Page 3 Attachments:

1. Proposed Technical Specification Mark-ups (Braidwood)
2. Proposed Technical Specification Mark-ups (Byron) cc:

NRC Region III, Regional Administrator NRC Senior Resident Inspector, BWD,BYR NRC Project Manager, BWD,BYR Illinois Emergency Management Agency, Illinois Division of Reactor Safety

ATTACHMENT 1 Proposed Technical Specification Marked-Up Pages Braidwood Station Adoption of Technical Specification Task Force (TSTF) Traveler TSTF-501, Revision 1, "Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control" TS Pages 3.8.3-1

Diesel Fuel Oil 3.8.3 BRAIDWOOD UNITS 1 & 2 3.8.3 1 Amendment 98 3.8 ELECTRICAL POWER SYSTEMS 3.8.3 Diesel Fuel Oil LCO 3.8.3 The stored diesel fuel oil shall be within limits for each required Diesel Generator (DG).

APPLICABILITY:

When associated DG is required to be OPERABLE.

ACTIONS


NOTE-------------------------------------

Separate Condition entry is allowed for each DG.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more DGs with stored fuel volume

< 44,000 galless than a 7 day supply and

> 41,138 galgreater than a 6 day supply in storage tank(s).

A.1 Restore stored fuel oil volume to within limits.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> B. One or more DGs with stored fuel oil total particulates not within limit.

B.1 Restore fuel oil total particulates within limit.

7 days C. One or more DGs with new fuel oil properties not within limits.

C.1 Restore stored fuel oil properties to within limits.

30 days (continued)

ATTACHMENT 2 Proposed Technical Specification Marked-Up Pages Byron Station Adoption of Technical Specification Task Force (TSTF) Traveler TSTF-501, Revision 1, "Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control" TS Pages 3.8.3-1

Diesel Fuel Oil 3.8.3 BYRON UNITS 1 & 2 3.8.3 1 Amendment 106 3.8 ELECTRICAL POWER SYSTEMS 3.8.3 Diesel Fuel Oil LCO 3.8.3 The stored diesel fuel oil shall be within limits for each required Diesel Generator (DG).

APPLICABILITY:

When associated DG is required to be OPERABLE.

ACTIONS


NOTE-------------------------------------

Separate Condition entry is allowed for each DG.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more DGs with stored fuel volume

< 44,000 galless than a 7 day supply and

> 41,138 galgreater than a 6 day supply in storage tank(s).

A.1 Restore stored fuel oil volume to within limits.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> B. One or more DGs with stored fuel oil total particulates not within limit.

B.1 Restore fuel oil total particulates within limit.

7 days C. One or more DGs with new fuel oil properties not within limits.

C.1 Restore stored fuel oil properties to within limits.

30 days (continued)